FDCIO223
Input/Output Module (Transponder)
Technical Manual
Valid for product Version ES
009122_h_en_--
2016-05-04
50
Building Technologies
Control Products and Systems

Advertisement

Table of Contents
loading

Summary of Contents for Siemens FDCIO223

  • Page 1 FDCIO223 Input/Output Module (Transponder) Technical Manual Valid for product Version ES Building Technologies 009122_h_en_-- 2016-05-04 Control Products and Systems...
  • Page 2 Issued by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724-2424 www.siemens.com/buildingtechnologies Edition: 2016-05-04 Document ID: 009122_h_en_-- © Siemens Switzerland Ltd, 2006 2 | 72 Building Technologies 009122_h_en_-- Fire Safety 2016-05-04...
  • Page 3: Table Of Contents

    Table of contents About this document ................5 Applicable documents ................. 8 Download center ..................8 Technical terms and abbreviations .............. 9 Revision history ..................10 Safety ....................12 Safety instructions ..................12 Safety regulations for the method of operation ...........14 Standards and directives complied with............16 Release Notes ...................16 Structure and function .................
  • Page 4 3.4.4.4 Control without confirmation ......... 43 3.4.4.5 Control with confirmation ..........44 Diagnosis levels..................44 Behavior in degraded mode ............... 46 Accessories ....................47 3.7.1 Mounting foot FDCM291 ............. 47 3.7.2 U-rail TS35 ................. 47 3.7.3 Housing FDCH221 ..............47 3.7.4 Connection terminal DBZ1190-AB..........
  • Page 5: About This Document

    You can request the data sheet, mounting instructions, and technical manual for FDCIO223 with a product version ES <50 via the Customer Support Center (CSC). Contact the CSC by phone on +49 89 9221-8000.
  • Page 6 About this document Applicable documents Target groups The information in this document is intended for the following target groups: Target group Activity Qualification Product Manager Is responsible for information Has obtained suitable specialist passing between the manufacturer training for the function and for the and regional company.
  • Page 7 About this document Applicable documents Conventions for text marking Markups Special markups are shown in this document as follows: Requirement for a behavior instruction Behavior instruction with at least two operation sequences – Version, option, or detailed information for a behavior instruction Intermediate result of a behavior instruction End result of a behavior instruction Numbered lists and behavior instructions with an operation...
  • Page 8: Applicable Documents

    List of compatibility (for 'Sinteso™' product line) 009052 FS20 Fire detection system - Commissioning, Maintenance, Troubleshooting 009078 FS20 Fire detection system - Configuration 009124 Installation Input/output module (Transponder) FDCIO223, Housing FDCH221 009168 Data sheet Transponder FDCIO223 009718 Technical Manual Intelligent detector tester FDUD293 A6V10201154...
  • Page 9: Technical Terms And Abbreviations

    'Cerberus PRO' fire detection system I/O1 Input/output 1 I/O2 Input/output 2 Load factor for collective and conventional devices (1 KMK 100 µA) Non-addressed detector line (Siemens / GMT) Collective detector line Non-addressed detector line (industry standard) Conventional detector line Light-emitting diode MC link Maintenance and Commissioning Link;...
  • Page 10: Revision History

    About this document Revision history 1.4 Revision history The reference document's version applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version. The table below shows this document's revision history: Modification index Edition date...
  • Page 11 About this document Revision history Modification index Edition date Brief description 2015-06-17 Document applies to devices with ES 50 Change to date format in line with ISO 8601 specifications (yyyy-mm- dd format); editorial adjustments made; data sheet added to 'Applicable documents' chapter;...
  • Page 12: Safety

    Safety Safety instructions 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: Symbol for danger Signal word Nature and origin of the danger Consequences if the danger occurs Measures or prohibitions for danger avoidance Symbol for danger...
  • Page 13 Safety Safety instructions How risk of injury is presented Information about the risk of injury is shown as follows: WARNING Nature and origin of the danger Consequences if the danger occurs Measures / prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows: NOTICE Nature and origin of the danger...
  • Page 14: Safety Regulations For The Method Of Operation

    2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation,...
  • Page 15 Disregard of the safety regulations Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation.
  • Page 16: Standards And Directives Complied With

    Safety Standards and directives complied with 2.3 Standards and directives complied with A list of the standards and directives complied with is available from your Siemens contact. 2.4 Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible.
  • Page 17: Structure And Function

    Structure and function Overview 3 Structure and function 3.1 Overview The input/output module FDCIO223 is operated on the FDnet/C-NET and has two inputs/outputs. These can be configured as follows: Collective detector line and conventional detector line Control line Contact input The graphic below shows the integration of the module in the fire detection system.
  • Page 18: Details For Ordering

    FDCIO223 S24218-B102-A1 Input / output module (transponder) Scope of delivery 1x input/output module FDCIO223 2x resistors 560 , 0.25 W 2x resistors 680 , 0.25 W 2x resistors 2.7 k , 0.25 W 2x resistors 3.3 k , 0.25 W...
  • Page 19: Product Version Es

    Structure and function Overview 3.1.2 Product version ES The product version ES provides the technical status of a device in terms of software and hardware. The product version is provided as a two-digit number. You will find the details of your device's product version: On the packaging label On the product label or the type plate Product version on the packaging label...
  • Page 20: Setup

    Structure and function Setup 3.2 Setup The modules consist of the module carrier, the printed circuit board and the cover cap. The printed circuit board includes several LEDs. The LEDs indicate the status of the inputs and outputs and the operating condition of the modules. The cover cap of the printed circuit board is transparent such that the statuses of the LEDs are visible even when the housing is closed.
  • Page 21: Printed Circuit Board View

    Structure and function Setup 3.2.2 Printed circuit board view 12a 12b 11b 10a 10b 9a 9b Figure 5: Printed circuit board view 1 Terminals for ground connection of the module and for shielding of inputs/outputs 'I/O 1' and 'I/O 2' (black) 2 Jumper for ground fault monitoring of inputs/outputs 'I/O 1' and 'I/O 2' 3a Jumper for bridging the internal fuses: 'I/O 2' 3b Jumper for bridging the internal fuses: 'I/O 1'...
  • Page 22: Indication Elements

    Structure and function Setup 3.2.3 Indication elements The position numbers in the following chapters relate to the graphic in chapter 'Printed circuit board view [ 21]'. 3.2.3.1 Input/output module status display Primary side LEDs – Position number 12 Operating condition Flashing mode Graphic Normal...
  • Page 23 Structure and function Setup Secondary side LEDs – Position number 11 Operating condition Flashing mode Graphic Normal 'PWR SEC' flashes green every second 'FAULT SEC' Fault: 'PWR SEC' off No supply voltage (24 V) Input/output module defective 'FAULT SEC' Fault: 'PWR SEC' flashes green Input/output module...
  • Page 24: Status Display For The Lines

    Structure and function Setup 3.2.3.2 Status display for the lines One green (a) and one red (b) LED indicates the status of each input/output (LEDs with position numbers 9a, 9b and 10a, 10b). Their meaning depends on how the input/output is configured. Input/output is configured as an input (detector line or contact input) –...
  • Page 25 Structure and function Setup Operating condition Flashing mode Graphic Input not monitored, LED(a) flashes green e.g., during line startup or twice a second for while there is an open line five seconds (contact or an error on the input) FDnet/C-NET detector line LED(a) flashes green twice a second for 12 seconds (detector...
  • Page 26 Structure and function Setup Input/output is configured as an output (control line) – Position numbers 9 and 10 Operating condition Flashing mode Graphic Not active Both LEDs off No supply Incorrectly configured Standby LED(a) lights up green continuously LED(b) off Output activated LED(a) off LED(b) lights up red...
  • Page 27: Adjustment Elements

    Structure and function Setup 3.2.4 Adjustment elements Invert Normal Adjust I/O 1 I/O 2 Fuse Adjustment element Function Position Meaning Adjust push button Control line calibration ON / OFF The internal resistance of the control lines is measured I/O 1 Input/output 1: norm Setting for:...
  • Page 28 Structure and function Setup Jumper plugged in: The internal fuse of the input/output module is bridged Jumper not plugged in: The internal fuse is active Only the settings detailed above are permitted. If the 'Fuse' jumper is activated, fuses provided by the customer must be used instead of the internal fuses.
  • Page 29: Function

    3.3 Function 3.3.1 Overview A distinction is made in terms of the function between the primary and secondary sides of the FDCIO223 input/output module. The primary side represents the connection to the FDnet/C-NET. Both inputs/outputs are triggered on the secondary side.
  • Page 30: Power Supply

    Activation of the outputs in test mode/inspection mode will merely be signaled by means of LEDs on the input/output module. If the input/output module FDCIO223 is operated with a control panel FC20xx or FC72x, no control outputs will be triggered in the event of activation of these control panels in test mode/inspection mode.
  • Page 31: Earth Fault Monitoring

    FC72x, the procedures described are carried out either on the device or on the control panel. Localization To enable clear identification, the input/output module FDCIO223 can be set to localization mode from the control panel. Localization mode is signaled by the yellow LED (12b) for the primary side status display.
  • Page 32: Input/Output Configuration Options (Secondary Side)

    Structure and function Input/output configuration options (secondary side) 3.4 Input/output configuration options (secondary side) Both inputs/outputs can be configured independently of one another. The table below shows which configurations are possible for input/output 1 and input/output 2. Configuration Input/output 1 Input/output 2 Collective detector lines Conventional detector lines...
  • Page 33: Configuration As A Detector Line

    Structure and function Input/output configuration options (secondary side) 3.4.2 Configuration as a detector line The information in this chapter applies to the following types of detector line: Collective detector lines Collective detector lines for areas at risk of explosion Conventional detector lines A short-circuit on the detector line is never evaluated as an alarm.
  • Page 34: Conventional Detectors Which Can Be Connected

    Structure and function Input/output configuration options (secondary side) 3.4.2.2 Conventional detectors which can be connected Conventional detector line configured as SynoLINE300: – Synova 300 series fire detector Third-party products in accordance with 'Industrial conventional', e.g.: – Apollo Series 65 – Apollo Orbis You will find an overview of the detectors that can be connected in the 'List of compatibility':...
  • Page 35: Detector Line Design

    Whenever the detector line is switched on Circuit A maximum of 32 detectors can be connected (KMK = 32). FDCIO223 100 mAT Figure 6: Detector line circuit Recommendation: Install a 100 mAT fuse as shown in the graphic on collective and conventional detector lines to protect the EOL element from commissioning errors.
  • Page 36 Safety barrier SB3 can also be connected to the input/output module FDCIO223. This allows intrinsically safe detectors to be operated in ex-zones 1 and 2. If you operate the FDCIO223 in conjunction with a safety barrier SB3, the following points must be observed in particular:...
  • Page 37: Alarm Verification

    Input/output configuration options (secondary side) 3.4.2.5 Alarm verification To help prevent false alarms, the input/output module FDCIO223 features a form of alarm verification that can be activated as required. When alarm verification is activated, any alarm (1) that occurs will first be stored by the input/output module.
  • Page 38: Monitoring

    Structure and function Input/output configuration options (secondary side) 3.4.2.6 Monitoring The input/output module monitors the detector line for the following criteria: Alarm Open line Short-circuit Ground fault (only both inputs/outputs jointly, no line-specific fault message) 3.4.3 Configuration as a contact input The inputs/outputs of the input/output module can be configured as contact inputs.
  • Page 39 Structure and function Input/output configuration options (secondary side) Circuit The graphic below shows the various circuit options available for contact inputs: FDCIO223 40 mAT 2.7 k Figure 9: Circuit for contact inputs 1…3 Monitoring for open line and 4 Monitoring for open line only...
  • Page 40: Configuration As A Control Line

    Within the context of control, the secondary side external supply voltage (DC 24 V) is applied directly to the relevant output for the control lines via a relay. In the input/output module FDCIO223, internal fuses (0.7 AT self-resetting fuses: PTCs) are present on the control lines.
  • Page 41: Identical-Polarity Monitoring

    With this type of monitoring, the connected load's internal resistance is monitored. As a result, no monitoring resistors need to be installed. Calibration is only possible with the push button. Circuit featuring identical-polarity monitoring FDCIO223 24 V R = 30...3,3 k Figure 10: Circuit for control lines with identical-polarity monitoring 1 Internal fuse (0.7 AT)
  • Page 42: Reverse-Polarity Monitoring

    The load must be isolated from the monitoring voltage by means of a diode. Reverse-polarity monitoring must always be used in the case of electronic loads. Circuit featuring reverse-polarity monitoring FDCIO223 24 V 3.3 k 10 V Figure 11: Circuit for control lines with reverse-polarity monitoring Internal fuse (0.7 AT)
  • Page 43: Control Without Confirmation

    Structure and function Input/output configuration options (secondary side) 3.4.4.4 Control without confirmation Configuration The following configurations are supported in the case of control without confirmation: Once activated, the control remains permanently active Once activated, the control only remains active for a certain time. How long the contact remains active can be configured (pulse duration).
  • Page 44: Control With Confirmation

    FC20xx FC72x AlgoRex 3.5 Diagnosis levels The FDCIO223 input/output module monitors its operation largely autonomously. The following diagnosis levels are derived from the different control measurements: Normal Observe information Replacement recommended...
  • Page 45 Structure and function Diagnosis levels Information displayed on Meaning Measures the detector exchanger and tester 'No deviation' Normal, no fault is present Input/output module is fully functional None 'maybe excha.' Observe information 'advice excha.' Replacement recommended 'needed excha.' Replacement necessary Any fault message Fault present Input monitoring error...
  • Page 46: Behavior In Degraded Mode

    Structure and function Behavior in degraded mode 3.6 Behavior in degraded mode Applicable for the FDnet/C-NET: When the main processor of the fire control panel fails, the control panel works in degraded mode operation. Depending on the control panel type, the fire control panel can continue to perform the most important alarming and signaling functions in degraded mode operation.
  • Page 47: Accessories

    Structure and function Accessories 3.7 Accessories 3.7.1 Mounting foot FDCM291 For device mounting on a DIN rail TS35 Two mounting feet must always be used Compatible with: – Input module FDCI22x(-CN) – Input/output module FDCIO22x(-CN) – Multi line separator module FDCL221-M –...
  • Page 48: Connection Terminal Dbz1190-Ab

    Structure and function Accessories 3.7.4 Connection terminal DBZ1190-AB Auxiliary terminal for connecting cables For T-branches of additional cabling, e.g., for cable shielding, detector heating units, sounder base, external alarm indicators, etc. For conductor cross-sections of 1…2.5 mm² 3 poles Order number: BPZ:4942340001 3.7.5 M20 x 1.5 metal cable gland For introducing a cable into a housing For cable diameters of 3.5…5.5 mm...
  • Page 49: Cable Ties 2.4 X 137

    Structure and function Accessories 3.7.7 Cable ties 2.4 x 137 For strain relief on the connection wires or generally for attachment Made from polyamide Compatible with: – Input module FDCI22x(-CN) – Input/output module FDCIO22x(-CN) – FDCL221 line separator – Multi line separator module FDCL221-M –...
  • Page 50: Planning

    Collective detector line for areas at risk of explosion (zone 1 and zone 2) – Conventional detector line – Control lines – Contact inputs 4.1 Compatibility The input/output module FDCIO223 is compatible with the following fire detection systems: Sinteso FS20 Cerberus PRO FS720 SIGMASYS AlgoRex Detector line Control panel...
  • Page 51: Defining The Mounting Site Of The Module And Configuration Of The Lines

    Planning Defining the mounting site of the module and configuration of the lines 4.2 Defining the mounting site of the module and configuration of the lines Define the type of application for the input/output module. See annex 'Planning the type of application, configuration overview [ 68]'.
  • Page 52: Mounting / Installation

    In the event of a shock pulse (application of force) on the input/output module FDCIO223, the duration of the maximum rebound behavior of the built-in relays is 10 ms. The shock does not negatively affect the function of the input/output module.
  • Page 53 Mounting / Installation Mounting with housing Cable with diameter >1.5 mm² If the cable diameters on the inputs/outputs are greater than 1.5 mm , auxiliary terminals must be used: In the case of cables with a diameter of 1.5…2.5 mm , the connection terminal DBZ1190-AB (accessories) can be used.
  • Page 54: Mounting In A Fire Control Panel

    Mounting / Installation Mounting in a fire control panel 5.2 Mounting in a fire control panel To make sure that the LEDs on the module remain visible at all times, the cover cap is transparent. Pick a suitable mounting position, ensuring that the LEDs will remain visible at all times during operation.
  • Page 55: Connecting Input/Output Module

    21]'. Do not connect the external DC 24 V power supply until you have configured the input/output module FDCIO223. Note the positive and negative poles. Only connect one wire per terminal. This is the only way to ensure the connection is failure-free for the entire service life of the device.
  • Page 56 Mounting / Installation Connecting input/output module Note the following with regard to the device connections. You will find an overview of the terminal assignments in chapter 'Printed circuit board view [ 21]'. The shielding of the FDnet/C-NET detector line must be connected to terminal The shielding of the 24 V secondary side power supply must be connected to terminal 16.
  • Page 57: Commissioning

    Commissioning Calibrating the control line 6 Commissioning The device is commissioned via the control panel. The exact procedure is described in the control panel documentation. NOTICE Before commissioning the device, check that the configuration of the inputs/outputs corresponds to the circuit. Conduct a performance check once commissioning is complete.
  • Page 58: Maintenance / Repair

    7 Maintenance / Repair 7.1 Status query Status query on the detector exchanger and tester The FDCIO223 input/output module is equipped with the MC link (Maintenance and Commissioning Link). You will find more information in documents 007227 and 009718. Status queries with detector exchanger and tester FDUD292 or intelligent detector tester FDUD293 are only possible with devices of the 'Sinteso' product line on the FDnet.
  • Page 59: Specifications

    Specifications Technical data 8 Specifications 8.1 Technical data You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable documents' chapter: Document 009168 FDnet/C-NET detector line Operating voltage DC 12…33 V Operating current Max.
  • Page 60 Specifications Technical data Detector lines at I/O1, I/O2 Can be configured as: Collective detector line Collective detector line for areas at risk of explosion Conventional detector line Number of detectors per detector line Max. 32 Collective detector key figures KMK Max.
  • Page 61 Specifications Technical data Message evaluation for: Alarms 1 s (can be increased by the alarm response time) Faults 1 s (can be increased by the filter time) Ground fault 60 s Compatibility Collective Collective detector line for areas at risk of explosion Conventional detector line For details, see 'List of compatibility' and 'Annex' chapter...
  • Page 62 Specifications Technical data Control line Output voltage in active state 24 V nominal (= secondary-side supply voltage) Output current per control line in active Max. 2 x 1 A or 1x 1.5 A in housing state FDCH221 and an operating temperature of max.
  • Page 63 Specifications Technical data Ambient conditions -25…+60 °C Operating temperature/permissible ambient temperature Storage temperature -30…+65 °C Air humidity 85 % rel. (no freezing or condensing at low temperature) Protection categories (IEC 60529): When mounted on a U-rail in a fire IP30 control panel With housing FDCH221 IP65...
  • Page 64: Dimensions

    Specifications Dimensions 8.2 Dimensions 43.5 46.5 A = Ø 4.5 Figure 14: Module dimensions Figure 15: Dimensions for housing FDCH221 64 | 72 Building Technologies 009122_h_en_-- Fire Safety 2016-05-04...
  • Page 65: Master Gauge For Recesses

    Specifications Master gauge for recesses 8.3 Master gauge for recesses B = Ø 5.0 Figure 16: Master gage for recesses of housing FDCH221 8.4 Environmental compatibility and disposal This equipment is manufactured using materials and procedures which comply with current environmental protection standards as best as possible.
  • Page 66: Annex

    9 Annex 9.1 Compatibility The table below shows the devices which, together with the FDCIO223, are approved according to EN 54-13. It is possible to connect additional devices as per the 'List of compatibility'. However, these devices have not been tested according to EN 54-13.
  • Page 67 Annex Compatibility 'Cerberus' point detectors OOH740 G211070 110 series collective and conventional point detectors OP110 G212033 OH110 G212059 HI110 G212004 HI112 G212015 Manual call points (collective) DM1101 DM1103 G295036 DM1104 G299068 FDM1101 G209148 Manual call points (conventional) MT320C FDM1101A G209149 Collective devices and manual call points for potentially explosive atmospheres Safety barrier SB3 DM1101...
  • Page 68: Configuration Sheets

    Annex Configuration sheets 9.2 Configuration sheets 9.2.1 Planning the type of application, configuration overview Mounting site ________________ Mode of mounting On DIN rail TS35 in a cabinet / control panel housing With housing FDCH221 Configuration of input/output 'I/O 1' Collective detector line Collective detector line for areas at risk of explosion Conventional detector line Contact input...
  • Page 69: Configuring The Control Line, Configuration Overview

    Annex Configuration sheets 9.2.3 Configuring the control line, configuration overview Parameters Input/output 'I/O 1' Input/output 'I/O 2' Same polarity Same polarity Polarity of control and monitoring systems in Reverse polarity, for electronic load Reverse polarity, for electronic load relation to one another Activation Permanent Permanent...
  • Page 70: Index

    Fault messages ..........44 Configuration ........... 29 FDCIO223 inputs/outputs Software ............32 Secondary side ..........29 Configuration overview ........68 FDCIO223 status display Configuration sheet .......... 51 LED ..............22 Control Fire Control Group ........... 43 Calibrating the control line ....... 57 Fire control panel failure Control panel ...........
  • Page 71 Adjustment element ........28 Product version ..........19 Primary side Communication with the control panel via the detector line ..........29 FDCIO223 status display ........ 22 Power supply ..........30 Line status display .......... 24 Product label Line separator Product version ..........19 Function............
  • Page 72 Issued by © Siemens Switzerland Ltd, 2006 Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID: 009122_h_en_-- FD20/FD720 Edition: 2016-05-04 Register 5...