Page 1
Introduction Safety notes Network topologies and redundancy SIMATIC NET Product characteristics SCALANCE X204RNA Installation SCALANCE X204RNA EEC (PRP) Connection Operating Instructions Functional description and configuration using Web based Management Approvals and marking Technical data Accessories and compatible devices References Dimension drawings...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
These Operating Instructions are valid for the following devices of the SCALANCE X- 200RNA product line SIMATIC NET SCALANCE X204RNA 6GK5204-0BA00-2KB2 SIMATIC NET SCALANCE X204RNA EEC 6GK5204-0BS00-3LA3 Names of the devices in these operating instructions The descriptions in these operating instructions always apply to the devices of the SCALANCE X-200RNA product line listed under "Validity of the Operating Instructions"...
Page 8
You will find detailed information in the section "Approvals and markings" in these operating instructions. Note The specified approvals apply only when the corresponding mark is printed on the product. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
The SCALANCE X204RNA is designed for operation with Safety Extra-Low Voltage (SELV) by a Limited Power Source (LPS). (This does not apply to the SCALANCE X204RNA EEC.) This means that only SELV / LPS complying with IEC 60950 1 / EN 60950 1 / VDE 0805 1 must be connected to the power supply terminals.
Page 10
When used in hazardous environments corresponding to Class I, Division 2 or Class I, Zone 2, the device must be installed in a cabinet or a suitable enclosure. General notices on use in hazardous areas according to ATEX (SCALANCE X204RNA only) WARNING...
Page 11
Take measures to prevent transient voltage surges of more than 40% of the rated voltage. This is the case if you only operate devices with SELV (safety extra-low voltage). Safety requirements 100 to 240 VAC (SCALANCE X204RNA EEC only) Safety requirements for installation According to the IEC 61131-2 standard and therefore in accordance with the EU directive 2006/95/EC (Low Voltage Directive), the devices are "open equipment"...
The SCALANCE X-200RNA can manage a maximum of 1023 MAC addresses. Note Make sure that the maximum permitted cable lengths for the relevant devices are not exceeded. You will find the permitted cable lengths in the technical specifications. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 14
SCALANCE X product line. You will find a list of usable network components in "Table 10-2 Compatible SCALANCE X devices (oversized frames - 1532 bytes) (Page 113)". SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Overview of the product characteristics Overview of the product characteristics The SCALANCE X204RNA and the SCALANCE X204RNA EEC have the same functionality and differ only in the environmental conditions, the input voltage ranges and the option of using SFP modules with the SCALANCE X204RNA EEC.
Page 16
PRP A, PRP B Note TP connectors of SCALANCE X204RNA EEC 2 x RJ-45 for connecting two end devices / network structures without PRP capability and optionally 2 x RJ-45 or 2 x SFP modules for connecting network structures capable of PRP.
SCALANCE X204RNA product characteristics Possible attachments The SCALANCE X204RNA has two RJ-45 jacks for connection of end devices or network segments not capable of PRP (P1 and P2) and two RJ-45 jacks for connecting the PRP networks LAN A and LAN B (PRP A and PRP B).
4.4.2 SCALANCE X204RNA TP interfaces SCALANCE X204RNA TP interfaces Connector pinout On the SCALANCE X204RNA, the TP interfaces are implemented as RJ-45 jacks with the MDI-X assignment (Medium Dependent Interface Autocrossover) of a network component. Figure 4-2 RJ-45 jack Table 4- 3...
Page 20
100 Mbps mode FD (full duplex). Note The SCALANCE X204RNA is a plug-and-play device that does not require settings to be made for commissioning. MDI / MDIX autocrossover function The advantage of the MDI / MDIX autocrossover function is that straight-through cables can be used throughout and external Ethernet crossover cables are unnecessary.
SCALANCE X204RNA EEC product characteristics Possible attachments The SCALANCE X204RNA EEC has four RJ-45 jacks and two slots for SFP modules. The SFP modules can be used as an alternative to the two RJ-45 jacks PRP A and PRP B and are intended for the connection of the LAN A and LAN B networks.
4.5.2 SCALANCE X204RNA EEC TP interfaces SCALANCE X204RNA EEC TP interfaces Connector pinout On the SCALANCE X204RNA EEC, the TP interfaces are implemented as RJ-45 jacks with the MDI-X assignment (Medium Dependent Interface Autocrossover) of a network component. Figure 4-4...
100 Mbps mode FD (full duplex). Note The SCALANCE X204RNA EEC is a plug-and-play device that does not require settings to be made for commissioning. MDI / MDIX autocrossover function The advantage of the MDI / MDIX autocrossover function is that straight-through cables can be used throughout and external Ethernet crossover cables are unnecessary.
Page 24
Optical connection: Duplex LC connector Transmission speed The transmission speed of the optical Fast Ethernet ports is 100 Mbps. Transmission technique The transmission mode for 100Base-FX is specified in the IEEE 802.3 standard. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
As a general rule, the data on the C-PLUG is only compatible with devices having an identical order number and the same device name. Over and above this, the data of the SCALANCE X204RNA and the SCALANCE X204RNA is compatible.
Page 26
The slot for the C-PLUG is located as follows: ●With a SCALANCE X204RNA on the front of the device ●With the SCALANCE X204RNA EEC on the top of the device Refer to Figure 4-6 Position of the C-PLUG and SET button (Page 28) To insert the C-PLUG, remove the protective cover.
Releasing the button during this phase brings about a device restart (soft reset) All port LEDs flash alternately yellow/green at 2.5 Hz. The device is reset to the factory defaults. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 28
4.7 SET button Note On the SCALANCE X204RNA, the button is located below the C-PLUG compartment. On the SCALANCE X204RNA EEC, the button is on the top of the device in a recess next to the C-PLUG compartment. ① C-PLUG ②...
1. Both L power supplies are connected (redundant supply). 2. One L power supply is connected (non-redundant supply). 3. Power supply L1 and L2 are not connected or supply voltages are <14 V. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
2. Port LEDs go off, the red error LED is lit for approx. 10 seconds. 3. Following startup, the correct link status is indicated by the port LEDs after approximately 5 seconds. 4. The SCALANCE X-200RNA is now ready for operation. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
When installing the X204RNA EEC, select a location where only qualified service personnel or trained users have access to it. Operation of the SCALANCE X204RNA EEC at ambient temperatures of 60 °C - 70 °C is only permitted under these conditions.
Page 32
Minimum clearances when installing in cabinets Minimum clearance to devices below the X-200RNA 100 mm Minimum clearance to devices above the X-200RNA 100 mm Minimum lateral clearance to devices (X204RNA EEC only) 20 mm SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
3. Fit the connectors for the signaling contact. 4. Insert the terminal blocks into the sockets on the device. Figure 5-1 Mounting on the DIN rail based on the example of a SCALANCE X204RNA EEC SCALANCE X204RNA SCALANCE X204RNA EEC (PRP)
Page 34
Fitting the protective bracket ① Hang onto rail at top ② Lock in position below ③ Secure with the screw Figure 5-2 Mounting the protective bracket on the SCALANCE X204RNA EEC SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 35
2. Use a screwdriver to release the lower rail catch of the device and pull the lower part of the device away from the rail. Figure 5-3 SCALANCE X204RNA removing from a DIN rail (35 mm) SCALANCE X204RNA SCALANCE X204RNA EEC (PRP)
2. Connect the electrical cable connecting cables. 3. Fit the connectors for the signaling contact. 4. Insert the terminal blocks into the sockets on the SCALANCE X204RNA. For more exact dimensions, please refer to the section "Dimension drawings" (Page 119) in the manual.
Pin 3 Pin 4 L2 +24 VDC Note Since the SCALANCE X204RNA EEC does not have a redundant power supply, the power supply must be connected between L1 and N1. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 38
24 VDC power supply CAUTION If the SCALANCE X204RNA is supplied over long 24 V power supply lines or networks, measures are necessary to prevent interference by strong electromagnetic pulses on the supply lines. These can result, for example, due to lightning or switching of large inductive loads.
Page 39
WARNING Danger from line voltage The SCALANCE X204RNA EEC has a power supply of 100 .. 240 VAC or 24 .. 250 VDC. This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended.
The signaling contact remains activated until the error/fault is eliminated or until the current status is applied as the new desired status using the button. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
LEDs). Note During startup, the signaling contract is always active (signals "error/fault"). Connecting the SFP transceiver Connecting the SFP transceiver The SFP modules are supplied with power via the SFF slot of the SCALANCE X204RNA EEC. Grounding Grounding SCALANCE X204RNA The housing is made of plastic.
If the browser is started again within the timeout, the session continues to be used. Note To use SNMP Management and traps, you require a network management station. This does not ship with IE switches. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Note The screens described in this section apply to the SCALANCE X-200RNA devices. The screens of the SCALANCE X204RNA EEC were chosen to illustrate the examples. Any significant deviations from the screens of the SCALANCE X204RNA are pointed out or shown.
Page 45
For security reasons, make sure that you change the original factory-set passwords. 4. Click the "Log On" button to start the logon. Note By clicking on "Logon using a secure HTTPS connection", you select a secure connection with SSL encryption. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
200RNA with the corresponding LEDs. The meaning of the LED displays is described in the section "Displays" (Page 29) in these Operating Instructions. Figure 7-2 LED simulation of the SCALANCE X204RNA EEC SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 47
Functional description and configuration using Web based Management 7.3 LED simulation of the WBM Figure 7-3 LED simulation of the SCALANCE X204RNA SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
WEB management is no longer possible. ● Support When you click this link, you open a SIEMENS AG support page. SIEMENS Support is, however, only accessible when your PC has a connection to the Internet.
● (p) The setting was made by the Simple Network Time Protocol (SNTP). System Up Time (read-only) The time since the last reboot. Device Type (read-only) The type designation of the device. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
The following screen contains information on device-specific vendor and maintenance data such as the order number, serial number, version numbers etc. Figure 7-5 System Identification & Maintenance I&M 0 Here, you can see the individual parameters for Identification & Maintenance. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Temporary Internet Files menu in the section with the Settings button. Check for newer versions of stored pages Automatically Below the text , the check box must be selected. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
FPGA configuration from suitable files on your client PC. Note Following a firmware update, delete the cache of the Web browser. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 53
Name and directory path of the file from which you want to load the new SSL key. SSL Certificate File Name and directory path of the file from which you want to load the new SSL certificate. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 54
If individual settings are necessary for specific devices, these must be made online. The stored configuration data is coded and, as a result, these files cannot be edited with a text editor. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
The version of the firmware running on the SCALANCE X-200RNA. FW Build The date on which the firmware running on the SCALANCE X-200RNA was created is displayed here. Order Number The order number of the device is shown here. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
In this dialog, if you are the administrator, you can change the passwords for Admin and User. The password can be up to a maximum of 16 characters (7-bit ASCII) long. Figure 7-9 System Passwords You apply your settings with Set Values. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
● Set Fault Mask Figure 7-10 Select/Set button configuration Enable Select/Set Functions You can enable or disable the individual functions of the button by checking or unchecking the relevant box. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
The "Sys.Up Time" column shows the time since the SCALANCE X-200RNA was last restarted in the format HH:MM:SS. Refresh Click on this button to refresh the display. Clear With this button, you can delete the content of the log table. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
The module to which the C-PLUG belongs. C-PLUG Device Type (read-only) The device type of the C-PLUG. Configuration Revision (readonly) Configuration version of the C-PLUG. File System (readonly) Data system of the C-PLUG. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 60
● Copying the current configuration on the C-PLUG with associated restart ● Copying the factory configuration to the C-PLUG with associated restart ● Deleting the configuration stored on the C-PLUG SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
● Up: Power supply 1 (line 1) is applied. ● Down: Power supply 1 is not applied or is below the permitted voltage. Power Line 2 (SCALANCE X204RNA only, not illustrated) SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
(the signaling contact has not responded and the fault LED is not lit). 7.6.2 PRP configuration PRP configuration The PRP-specific parameters are entered in the PRP Config screen. Figure 7-14 PRP configuration SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Setting the fault mask on the device Optionally, the fault mask can be set using the SET/SEL button on the SCALANCE X- 200RNA. For more detailed information, refer to the section "SET button" (Page 27). SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 64
(line 1 or line 2) or when the voltage is too low (less than 14 V). (Since the SCALANCE X204RNA EEC does not have a redundant power supply, this screen is not displayed for it).
Page 65
An error/fault can be signaled in the following ways depending on the configuration of the SCALANCE X-200RNA: Signaling contact, fault LED, SNMP trap, entry in the log table and the syslog. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 66
An error/fault can be signaled in the following ways depending on the configuration of the SCALANCE X-200RNA: Signaling contact, fault LED, SNMP trap, entry in the log table and the syslog. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Enter the subnet mask of the SCALANCE X-200RNA here. Note After changing the IP address, to be able to connect to the SCALANCE X-200RNA again, the new address will need to be entered in the WEB browser manually. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 68
E-mail Here, you specify whether or not events are sent to an e-mail address. BOOTP Here, you specify whether the IP address can be obtained using the Bootstrap Protocol. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
The "Ping" screen appears if you click the "Agent" folder icon. In this screen, you can send a PING to another device in the network to check whether it can be reached. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 70
Enter the IP address of the target device here. Repeat Here, enter how often the ping should be sent. Ping The ping is started when you click the "Ping" button. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
In the SNMP Configuration screen, you make the basic settings for SNMP. Enable the check boxes according to the SNMP functionality you want to use. For detailed settings (for example traps), there are separate menu items in WBM. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 72
Here, you enter the read community string (maximum of 63 characters) for the SNMP protocol. Read/Write Community String Here, you enter the write community string (maximum of 63 characters) for the SNMP protocol. Traps This enables / disables the sending of SNMPv1/v2c traps. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Here, you enter the addresses of the stations to which a SCALANCE X-200RNA will send traps. Enable Trap Click on the check box next to the IP addresses to enable the sending of traps to the corresponding stations. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
It shows all existing SNMPv3 groups. The access rights of these groups can also be found in the table. Figure 7-22 SNMPv3 Groups By clicking the "New Entry" button or clicking on an entry, the "SNMPv3 Group Configuration" screen is displayed. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 75
By clicking the "Set Values" button, you create a group according to the parameters set above. Current Entries By clicking the "Current Entries" button, you exit the "SNMPv3 Group Configuration" screen and return to the "SNMPv3 Groups" screen. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Figure 7-24 SNMPv3 Users By clicking the "New Entry" button or clicking on an entry, the "SNMPv3 Users Configuration" screen is displayed. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 77
By clicking the "Set Values" button, you create a user according to the parameters set above. Current Entries By clicking the "Current Entries" button, you exit the "SNMPv3 Users Configuration" screen and return to the "SNMPv3 Users" screen. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Permitted values for the WBM timeout: 0-3600 (seconds) 0 means: There is no automatic logout. CLI (TELNET, SSH, Serial) (sec) Here, you specify the CLI timeout. Permitted values for the CLI timeout: 60-600 (seconds) SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
SCALANCE X-200RNA. The following options are available: ● The SCALANCE X-200RNA sends an e-mail with the error message ● The SCALANCE X-200RNA triggers an SNMP trap. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 80
● The SCALANCE X-200RNA writes an entry in the log file. ● The SCALANCE X-200RNA writes an entry to the Syslog server. Figure 7-27 Agent Event Configuration with the SCALANCE X204RNA EEC SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 81
Authentication Failure There was an SNMP access with a bad password or inadequate access rights. Power Error (SCALANCE X204RNA only) This event occurs only when the power supply line 1 and line 2 are monitored. It indicates that there was a change to line 1 or line 2.
Here, you can set the recipient, sender and the SMTP server. Figure 7-29 Agent E-Mail Configuration E-mail address Here, you specify the e-mail address of the recipient. SMTP server IP address SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Setting the Syslog server Here, you can specify the address of the Syslog server. Figure 7-30 Agent Syslog Configuration Syslog Server IP Address Enter, the IP address of the Syslog server. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
There are several ways of identifying the SCALANCE X-200RNA in the configuration of the DHCP server: ● with the MAC address ● with a freely defined client ID ● with the system name Figure 7-31 Agent DHCP Configuration DHCP Mode SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 85
DHCP client ID For the DHCP mode "via Client ID", you can assign an identification string here that is assigned to a SCALANCE X-200RNA and will be evaluated by the DHCP server. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
(p). Time Synchronization This box is read-only and shows when the last time-of-day synchronization took place. SNTP Mode The protocol type used is displayed here: SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 87
Once the system time has been adopted the first time from the time server, it is updated cyclically with renewed polls to the time server. Here, you specify how often the updates take place. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Switch functionality The "Switch Configuration" screen appears if you click the "Switch" folder icon. In this screen, you specify the aging time of the SCALANCE X-200RNA. Figure 7-33 Switch Configuration SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Overview of the configuration of the ports The "Port Status" screen appears if you click the "Ports" folder icon. The screen shows the configuration for data transfer for all ports of the SCALANCE X- 200RNA. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 90
Port status The five columns of the table display the following information: Port This shows the port (with the SCALANCE X204RNA also the SFP slot) to which the following information relates. Type Displays the type of port. This information is important because difference modules and therefore different ports can be used in some slots.
The screen shows the dynamically learnt MAC addresses in the FDB table for all ports. In addition to this, to allow PRP diagnostics, the screen also shows whether the displayed MAC addresses are listed in the duplicate filter or in the proxy node table. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 92
Shows whether the MAC address is listed as a source MAC address in the duplicate filter table. Proxy node Shows whether the MAC address is listed as a source MAC address in the proxy node table. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
The "Packet Size Statistics" page displays how many packets of which size were received at each port. If you click the "Reset Counters" button, you reset the counters for all ports. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 94
There is a separate element in the graphic for each of the following ranges: ● 64 bytes ● 65 - 127 bytes ● 128 -255 bytes ● 256 - 511 bytes SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
The "Packet Type Statistics" page displays how many frames of the type "unicast", "multicast", and "broadcast" were received and sent at each port. If you click the "Reset Counters" button, you reset the counters for all ports. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 96
This page displays the number of frames received at each port graphically. The display depends on the packet type. There is a separate element in the graphic for each of the following ranges: ● Unicast ● Multicast ● Broadcast SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Total number of bad received frames. ● CRC Number of frames whose content did not match the CRC checksum. ● Undersize Number of frames with a length less than 64 bytes. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 98
This page displays the number of bad frames graphically. The display is dependent on the cause of the error. There is a separate element in the graphic for each of the following causes of error: ● Bad Frames ● CRC ● Undersize SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 99
With the "Previous Port" and "Next Port" buttons, you can change to the display of the previous or next port. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
● Received "A Frames" at PRP B Port Number of valid A frames received at port PRP B (error). If you click the "Reset Counters" button, you reset the counters for all ports. Figure 7-42 PRP Statistic SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
→ Entry type "Certificates" → Type of certificate "Declaration of conformity" Example German: "EG Konformitätserklärung SCALANCE X204RNA", Example English: "Declaration of Conformity SCALANCE X204RNA ". EMC directive (electromagnetic compatibility) The SCALANCE X-200RNA devices meet the requirements of the EC directive: 2004/108/EEC "Electromagnetic Compatibility"...
Page 102
When operating the product with a device that does not comply with these standards, adherence to the corresponding values cannot be guaranteed. Explosion protection directive (ATEX) The SCALANCE X204RNA device meets the requirements of the EC directive: SCALANCE X204RNA SCALANCE X204RNA EEC (PRP)
Page 103
94/9/EC (ATEX95) "Equipment and protective systems intended for use in potentially explosive atmospheres" Note When using (installing) the SCALANCE X204RNA in hazardous area zone 2, make absolutely sure that the associated conditions are adhered to. You will find these conditions on the SIMATIC NET Manual Collection.
Page 104
● CSA C22.2 No. 60950-1-03 cULus Approval for Industrial Control Equipment Underwriters Laboratories Inc. complying with ● UL 508 ● CSA C22.2 No. 142-M1987 For use in Pollution Degree 2 Environment SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 105
1 octave/min, 20 sweeps X204RNA EEC 5 – 9 Hz: 3.5 mm 15 g, 11 ms duration 9 – 150 Hz: 1 g 6 shocks per axis 10 cycles per axis SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 106
Approvals and marking 8.1 Approvals and marking SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Duplex LC connector X pinning 100 Mbps (with SFP module) full duplex X204RNA 1 x 4-pin 1 x 2-pin X204RNA EEC 2 + 2 max. 2 1 x 3-pin 1 x 3-pin SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 108
0 - 75 m IE FC TP marine / cable + 10 m TP cord trailing / flexible / FRNC / festoon / food cable + 10 m TP cord over IE FC outlet RJ-45 X204RNA X204RNA EEC SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 109
3000 m at max. 50 °C Note Note the orientation of the installed SCALANCE X204RNA and X204RNA EEC If a SCALANCE X204RNA or X204RNA EEC are mounted on a vertical rail, an ambient temperature of maximum +40 °C is permitted. SCALANCE X204RNA SCALANCE X204RNA EEC...
Page 116
With other devices, the firmware version is specified (= V.x.x) because the device functionality is set in the firmware. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
References 11.1 References Sources of information and other documentation System manual "SIMATIC NET Industrial Ethernet Network Manual" The system manuals are only available from the CS home page. (http://support.automation.siemens.com/WW/view/en/27069465/) SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Cyclic Redundancy Check. A checksum used in transmission protocols to detect errors in frames. DCP (Discovery and basic Configuration Protocol) is used to detect nodes without an IP address and to assign a basic configuration to them, for example IP address. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 124
►High Speed Redundancy and ►MRP methods. Media Redundancy Protocol A method specified in the IEC 61158 Type 10 standard for increasing network availability in a ring topology. See also ►Media redundancy. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 125
The particular advantage of RMON is that it is independent of location. The acquired data can be analyzed at any point in the network with suitable reporting software. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 126
SFP modules fit in an SFF slot and can be replaced simply and quickly (hot swapping). Signaling contact Floating relay contact via which the detected error states can be signaled. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 127
With this protocol, an interactive connection can be established to another device in the LAN or on the Internet. The user then has the same options as when directly connected to this device with a terminal. Twisted Pair SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 128
Web Based Management. With WBM, configuration and diagnostics are handled with an Internet browser. Entries made by the user are sent to the device using the HTTP protocol and the device transfers its replies by HTTP to the user. SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...
Page 132
Time-of-day synchronization, 96 UTC time, 97 Time zone, 97 Timeout, 87 UL approval, 8 to UL 508, 116 to UL 60950, 116 User Name, 86 UTC time, 97 Web Based Management, 50 SCALANCE X204RNA SCALANCE X204RNA EEC (PRP) Operating Instructions, , C79000-G8976-C294-03...