— GENERAL PURPOSE DRIVES ACS580-01 drives, frames R6 to R9 Quick installation and start-up guide 3AXD50000009286 Rev F MUL EFFECTIVE: 2019-06-29...
Page 2
Document library on the Internet on the inside of the back cover. For manuals not available in the Document library, contact your local ABB representative. The QR code below opens an online listing of the manuals applicable to this product.
Table of contents 3 Table of contents List of related manuals in English Ratings and fuses IEC ratings at UN = 230 V, 400 V and 480 V ........7 UN = 230 V .
Page 7
R6…R9 Quick installation guide 7 Ratings and fuses IEC ratings at U = 230 V, 400 V and 480 V = 230 V Type Input Output ratings Max. Frame rating losses size ACS580 Max. Nominal use Light-duty use Heavy-duty use -01- current 3-phase U...
350 361 6036 1150 3AXD00000586715.xls L gG fuses Type Min. short- Input gG (IEC 60269) circuit current ACS580-01- current Nominal Voltage ABB type current rating 60269 size 3-phase U = 230 V 144A-2 1700 144.0 300000 OFAF0H200 171A-2 2300 171.0...
R6…R9 Quick installation guide 9 uR or aR fuses Type Min. short- Input uR or aR (DIN 43620 blade style) circuit current ACS580 Nominal Voltage Bussmann IEC 60269 current -01- current rating type size 3-phase U = 230 V 144A-2 1000 144.0 46500...
(3AXD50000044794 [English]). For start-up instructions, see chapter EN – Quick start-up guide on page 23. To read a manual, go to www.abb.com/drives/documents and search for the document number. Obey the safety instructions WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur: •...
1. Check the insulation of the motor cable and motor when the cable is disconnected from the drive. Measure the insulation resistance between each phase conductor and then between each phase conductor and the Protective Earth conductor using a measuring voltage of 1000 V DC. The insulation resistance of an ABB...
EN – R6…R9 Quick installation guide 13 motor must exceed 100 Mohm (reference value at 25 °C or 77 °F). For the insulation resistance of other motors, see the manufacturer’s instructions. Note: Moisture inside the motor casing will reduce the insulation resistance. If moisture is suspected, dry the motor and repeat the measurement.
14 EN – R6…R9 Quick installation guide Connect the power cables See figure on page 32. Use symmetrical shielded cable for motor cabling. If the cable shield is the sole PE conductor for drive or motor, make sure that is has sufficient conductivity for the PE.
33. It shows an example with one analog signal cable and one digital signal cable. Make the connections according to the macro in use. The default connections of the ABB standard macro are shown in section Default I/O connections on page 16.
16 EN – R6…R9 Quick installation guide Default I/O connections Default I/O connections of the ABB Standard macro are shown below. Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference: 0…10 V 1…10 kohm AGND...
EN – R6…R9 Quick installation guide 17 Install optional modules, if any See chapter Electrical installation in ACS580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000044794 [English]). Install side plates and covers See figure on page 33. IP21 1.
EN – Quick start-up guide 23 EN – Quick start-up guide This guide describes how to start-up the drive using the First start assistant on the assistant control panel. For complete information on start-up, see ACS580 standard control program firmware manual (3AXD50000016097 [English]). Before you start Ensure that the drive has been installed as described in chapter EN –...
Page 24
24 EN – Quick start-up guide The First start assistant guides you through the first start-up. The assistant begins automatically. Wait until the control panel enters the view shown on the right. Select the language you want to use by highlighting it (if not already highlighted) and pressing (OK).
Page 25
Refer to the motor nameplate for the following nominal value settings of the motor. Enter the values exactly as shown on the motor nameplate. Example of a nameplate of an induction (asynchronous) motor: ABB Motors motor M2AA 200 MLA 4 IEC 200 M/L 55 Ins.cl.
Page 26
26 EN – Quick start-up guide Check that the motor data is correct. Values are predefined on the basis of the drive size but you should verify that they correspond to the motor. Start with the motor type. Motor nominal cosΦ and nominal torque are optional.
Page 27
EN – Quick start-up guide 27 The first start is now complete and the drive is ready for use. Press (Done) to enter the Home view. The Home view monitoring the values of the selected signals is shown on the panel. 2 –...
Page 28
28 EN – Quick start-up guide 2 – Additional settings: Start, stop and reference values If you do not wish to use a macro, define the settings for start, stop and reference: Select Start, stop, reference and press (Select) (or Adjust the parameters according to your needs.
Page 29
EN – Quick start-up guide 29 2 – Additional settings: Limits Select Limits and press (Select) (or Adjust the parameters according to your needs. Select a parameter and press (Edit). After making the adjustments, go back to the Primary settings menu by pressing (Back).