AC522 — 1 AC522 ● AC522 CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g. EN 60204-1. –...
AC522 Connection 1.4 Connection I/O bus Allocation between terminal number and signal name 8 yellow LEDs to display the signal states C0 - C7 1 green LED to display the state of the process supply voltage UP 1 red LED to display errors Label Terminal unit TU515/TU516 All I/O channels (digital and analog) are protected against reverse polarity,...
AC522 Connection > Inputs/Outputs 1.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 1.4.2 Inputs/Outputs Examples Fig. 1: Example for connection input 2019/11/15 3ADR024117M02xx, 11, en_US...
AC522 Recycling Fig. 2: Example for connection output 1.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 1.6 Certification 1.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
AI523 — 2 AI523 ● AI523 ● AI523-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 16
AI523 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 17
AI523 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
AI523 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 2.1 Assembly 3ADR024117M02xx, 11, en_US 2019/11/15...
AI523 Connection 2.4 Connection I/O bus Allocation between terminal number and signal name 16 yellow LEDs to display the signal states at the analog inputs (I0 - I15) 1 green LED to display the state of the process supply voltage UP 2 red LEDs to display errors Label Terminal unit...
AI523 Connection > Inputs 2.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 2.4.2 Inputs Example Fig. 3: Example for connection input 2019/11/15 3ADR024117M02xx, 11, en_US...
AI523 Recycling 2.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 2.6 Certification 2.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
AI531 — 3 AI531 ● AI531 ● AI531-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 24
AI531 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 25
AI531 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
AI531 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 3.1 Assembly 3ADR024117M02xx, 11, en_US 2019/11/15...
AI531 Connection 3.4 Connection I/O bus Allocation between terminal number and signal name 4 yellow LEDs to display the states at the inputs (I0 - I3) 4 yellow LEDs to display the states at the inputs (I4 - I7) 1 green LED to display the state of the process supply voltage UP 2 red LEDs to display errors Label Terminal unit...
AI531 Connection > Inputs 3.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 3.4.2 Inputs 2019/11/15 3ADR024117M02xx, 11, en_US...
AI531 Certification Example Fig. 4: Example for connection input 3.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 3.6 Certification 3ADR024117M02xx, 11, en_US 2019/11/15...
AI531 Recycling 3.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
AI581-S — 4 AI581-S ● AI581-S ● AI581-S-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
AI581-S Connection 4.4 Connection I/O bus System LED Allocation between terminal number and signal name 4 yellow/red LEDs to display the signal states of the analog inputs 2 rotary switches for setting the PROFIsafe address 1 green LED to display the state of the process supply voltage UP 2 red LEDs to display errors Label Terminal unit TU582-S(-XC)
AI581-S Connection > Inputs 4.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 4.4.2 Inputs Example Fig. 5: Example for connection input AC500-S Safety User Manual For a detailed description of the electrical connection of the module, please refer to the "AC500-S Safety User Manual".
AI581-S Recycling 4.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 4.6 Certification 4.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
AO523 — 5 AO523 ● AO523 ● AO523-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 39
AO523 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 40
AO523 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
AO523 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 5.1 Assembly 2019/11/15 3ADR024117M02xx, 11, en_US...
AO523 Connection 5.4 Connection I/O bus Allocation between terminal number and signal name 16 yellow LEDs to display the signal states at the analog outputs (O0 - O15) 1 green LED to display the state of the process supply voltage UP 2 red LEDs to display errors Label Terminal unit...
AO523 Connection > Outputs 5.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 5.4.2 Outputs Example Fig. 6: Example for connection output 3ADR024117M02xx, 11, en_US 2019/11/15...
AO523 Recycling 5.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 5.6 Certification 5.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
AX521 — 6 AX521 ● AX521 ● AX521-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 47
AX521 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 48
AX521 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
AX521 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 6.1 Assembly 2019/11/15 3ADR024117M02xx, 11, en_US...
AX521 Connection 6.4 Connection I/O bus Allocation between terminal number and signal name 4 yellow LEDs to display the signal states at the analog inputs (I0 - I3) 4 yellow LEDs to display the signal states at the analog outputs (O0 - O3) 1 green LED to display the state of the process supply voltage UP 2 red LEDs to display errors Label...
AX521 Connection > Outputs 6.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 6.4.2 Inputs Example Fig. 7: Example for connection input 6.4.3 Outputs 3ADR024117M02xx, 11, en_US 2019/11/15...
AX521 Recycling Example Fig. 8: Example for connection output 6.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 6.6 Certification 6.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
AX522 — 7 AX522 ● AX522 ● AX522-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 55
AX522 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 56
AX522 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
AX522 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 7.1 Assembly 2019/11/15 3ADR024117M02xx, 11, en_US...
AX522 Connection 7.4 Connection I/O bus Allocation between terminal number and signal name 8 yellow LEDs to display the signal states at the analog inputs (I0 - I7) 8 yellow LEDs to display the signal states at the analog outputs (O0 - O7) 1 green LED to display the state of the process supply voltage UP 2 red LEDs to display errors Label...
AX522 Connection > Outputs 7.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 7.4.2 Inputs Example Fig. 9: Example for connection input 7.4.3 Outputs 3ADR024117M02xx, 11, en_US 2019/11/15...
AX522 Recycling Example Fig. 10: Example for connection output 7.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 7.6 Certification 7.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
CD522 — 8 CD522 ● CD522 ● CD522-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
CD522 Connection 8.4 Connection I/O bus Allocation between terminal number and signal name 3 yellow LEDs to display the signal states of the encoder 0 input 3 yellow LEDs to display the signal states of the encoder 1 input 2 green LEDs to display the 5-V-power-supply states 2 yellow LEDs to display the signal state of the digital input I3 and I11 8 yellow LEDs to display the input/output signal states 2 yellow LEDs to display the signal states of the PWM/pulse outputs...
CD522 Connection > Inputs 8.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 8.4.2 Inputs Example Example for connection input Ix 3ADR024117M02xx, 11, en_US 2019/11/15...
CD522 Connection > Outputs 8.4.3 Inputs/Outputs Example Example for connection as an input Example for connection as an output 8.4.4 Outputs Push-pull outputs 2019/11/15 3ADR024117M02xx, 11, en_US...
CD522 Certification Example Example for connection as output with UP reference Example for connection as output with ZP reference Examples for connection encoder/sensors, see description CD522. 8.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 8.6 Certification 3ADR024117M02xx, 11, en_US 2019/11/15...
CD522 Recycling 8.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
CI541-DP — 9 CI541-DP ● CI541-DP ● CI541-DP-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 71
CI541-DP WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 72
CI541-DP NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
CI541-DP Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 9.1 Assembly 2019/11/15 3ADR024117M02xx, 11, en_US...
CI541-DP Connection 9.4 Connection I/O bus Allocation between terminal number and signal name 6 yellow LEDs to display the signal states of the analog inputs/outputs (AI0 - AI3, AO0 - AO1) 8 yellow LEDs to display the signal states of the digital inputs (DI0 - DI7) 8 yellow LEDs to display the signal states of the digital outputs (DO0 - DO7) 2 green LEDs to display the supply voltage UP and UP3 3 red LEDs to display errors (CH-ERR1, CH-ERR2, CH-ERR3)
CI541-DP Connection > Inputs/Outputs 9.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 9.4.2 Inputs/Outputs Example Analog Input Fig. 11: Example for connection input AIx 3ADR024117M02xx, 11, en_US 2019/11/15...
CI541-DP Certification Example Analog Output Fig. 12: Example for connection output AOx Example Digital Input Fig. 13: Example for connection input DIx Example Digital Output Fig. 14: Example for connection output DOx 9.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead.
CI541-DP Recycling 9.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
CI542-DP — 10 CI542-DP ● CI542-DP ● CI542-DP-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 80
CI542-DP WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 81
CI542-DP NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
CI542-DP Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 10.1 Assembly 3ADR024117M02xx, 11, en_US 2019/11/15...
CI542-DP Connection 10.4 Connection I/O bus Allocation between terminal number and signal name 8 yellow LEDs to display the signal states of the configurable digital inputs/outputs (DC0 - DC7) 8 yellow LEDs to display the signal states of the digital inputs (DI8 - DI15) 8 yellow LEDs to display the signal states of the digital outputs (DO8 - DO15) 2 green LEDs to display the supply voltage UP and UP3 3 red LEDs to display errors (CH-ERR1, CH-ERR2, CH-ERR3)
CI542-DP Connection > Inputs/Outputs 10.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 10.4.2 Inputs/Outputs Example Input or Output Example for connection as an input Example for connection as an output 2019/11/15 3ADR024117M02xx, 11, en_US...
CI542-DP Recycling Example Digital Input Fig. 15: Example for connection input DIx Example Digital Output Fig. 16: Example for connection output DOx 10.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 10.6 Certification 10.7...
CI5x1 — 11 CI5x1 ● CI501-PNIO ● CI501-PNIO-XC ● CI511-ETHCAT ● CI521-MODTCP ● CI521-MODTCP-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 88
CI5x1 Hot Swap WARNING! Risk of explosion or fire in hazardous environments during hot swapping! Hot swap must not be performed in flammable environments to avoid life-threatening injury and property damage resulting from fire or explosion. WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock –...
Page 89
CI5x1 NOTICE! Risk of damage to I/O modules! Modules with index below F0 can be damaged when inserted or removed from the terminal unit in a powered system. NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration.
Page 90
CI5x1 Device Min. required device index for I/O module as of FW Version 3.0.14 DO526 DO526-XC DO561 DO562 DO571 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 NOTICE! The section "Hot Swap" is only valid for CI501-PNIO(-XC) and CI521-MODTCP(-XC). 3ADR024117M02xx, 11, en_US 2019/11/15...
CI5x1 Connection 11.4 Connection Fig. 17: CI501-PNIO (example ) I/O bus Allocation between terminal number and signal name 6 yellow LEDs to display the signal states of the analog inputs/outputs (AI0 - AI3, AO0 - AO1) 8 yellow LEDs to display the signal states of the digital inputs (DI0 - DI7) 8 yellow LEDs to display the signal states of the digital outputs (DO0 - DO7) 2 green LEDs to display the supply voltage UP and UP3 3 red LEDs to display errors (CH-ERR1, CH-ERR2, CH-ERR3)
CI5x1 Connection > Inputs/Outputs 11.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 11.4.2 Inputs/Outputs Example Analog Input Fig. 18: Example for connection input AIx 3ADR024117M02xx, 11, en_US 2019/11/15...
CI5x1 Certification Example Analog Output Fig. 19: Example for connection output AOx Example Digital Input Fig. 20: Example for connection input DIx Example Digital Output Fig. 21: Example for connection output DOx 11.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead.
CI5x1 Recycling 11.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
CI5x2 — 12 CI5x2 ● CI502-PNIO ● CI502-PNIO-XC ● CI512-ETHCAT ● CI522-MODTCP ● CI522-MODTCP-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 98
CI5x2 Hot Swap WARNING! Risk of explosion or fire in hazardous environments during hot swapping! Hot swap must not be performed in flammable environments to avoid life-threatening injury and property damage resulting from fire or explosion. WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock –...
Page 99
CI5x2 NOTICE! Risk of damage to I/O modules! Modules with index below F0 can be damaged when inserted or removed from the terminal unit in a powered system. NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration.
Page 100
CI5x2 Device Min. required device index for I/O module as of FW Version 3.0.14 DO526 DO526-XC DO561 DO562 DO571 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 NOTICE! The section "Hot Swap" is only valid for CI502-PNIO(-XC) and CI522-MODTCP(-XC). 3ADR024117M02xx, 11, en_US 2019/11/15...
CI5x2 Connection 12.4 Connection Fig. 22: CI502-PNIO (example ) I/O bus Allocation between terminal number and signal name 8 yellow LEDs to display the signal states of the configurable digital inputs/outputs (DC0 - DC7) 8 yellow LEDs to display the signal states of the digital inputs (DI8 - DI15) 8 yellow LEDs to display the signal states of the digital outputs (DO8 - DO15) 2 green LEDs to display the supply voltage UP and UP3 3 red LEDs to display errors (CH-ERR1, CH-ERR2, CH-ERR3)
CI5x2 Connection > Inputs/Outputs 12.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 12.4.2 Inputs/Outputs Example Input or Output Example for connection as an input Example for connection as an output 3ADR024117M02xx, 11, en_US 2019/11/15...
CI5x2 Recycling Example Digital Input Fig. 23: Example for connection input DIx Example Digital Output Fig. 24: Example for connection output DOx 12.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 12.6 Certification 12.7...
CM582-DP — 13 CM582-DP ● CM582-DP ● CM582-DP-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
CM582-DP Connection 13.4 Connection The connection part may be different on various terminal base types. See installation instructions of the specific terminal base suitable for this CPU for connection specifications. 5 LEDs for state display Label Interface for PROFIBUS TA524 Dummy Communication Module Sign for XC version 2019/11/15 3ADR024117M02xx, 11, en_US...
CM582-DP Certification 13.4.1 Interface for PROFIBUS Pin Assignment Signal Description Not connected Not connected RxD/TxD-P Receive/Transmit positive CNTR-P Control signal for repeater, positive DGND Reference potential for data exchange and +5 V +5 V (power supply for the bus termi- nating resistors) Not connected RxD/TxD-N...
CM582-DP Recycling 13.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
CM589-PNIO(-4) — 14 CM589-PNIO(-4) ● CM589-PNIO ● CM589-PNIO-XC ● CM589-PNIO-4 ● CM589-PNIO-4-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
CM589-PNIO(-4) Connection 14.4 Connection The connection part may be different on various terminal base types. See installation instructions of the specific terminal base suitable for this CPU for connection specifications. 5 LEDs for state display 2 rotary switches for setting the I/O device identifier Label Ethernet network interfaces TA524 Dummy Communication Module...
CM589-PNIO(-4) Certification 14.4.1 Ethernet Network Interface Pin Assignment Signal Description TxD+ Transmit data + TxD- Transmit data - RxD+ Receive data + Not used Not used RxD- Receive data - Not used Not used Shield Cable shield Functional earth In corrosive environment, please protect unused connectors using the TA535 accessory.
CM589-PNIO(-4) Recycling 14.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
DA501 — 15 DA501 ● DA501 ● DA501-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 119
DA501 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 120
DA501 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
DA501 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 15.1 Assembly 2019/11/15 3ADR024117M02xx, 11, en_US...
DA501 Connection 15.4 Connection I/O bus Allocation between terminal number and signal name 16 yellow LEDs to display the signal states of the digital inputs DI0 - DI15 4 yellow LEDs to display the signal states of the analog inputs AI0 to AI3 2 yellow LEDs to display the signal states of the analog outputs AO0 to AO1 8 yellow LEDs to display the signal state of the configurable digital inputs/outputs DC16 to DC23...
DA501 Connection > Inputs/Outputs 15.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 15.4.2 Inputs/Outputs Examples Fig. 25: Example for connection input DIx Fig. 26: Example for connection input AIx 3ADR024117M02xx, 11, en_US 2019/11/15...
DA501 Certification Fig. 27: Example for connection output AOx Example for connection as an input Example for connection as an output 15.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 15.6 Certification 2019/11/15 3ADR024117M02xx, 11, en_US...
DA501 Recycling 15.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
DA502 — 16 DA502 ● DA502 ● DA502-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
DA502 Connection 16.4 Connection I/O bus Allocation between terminal number and signal name 16 yellow LEDs to display the signal states of the digital outputs DO0 - DO15 4 yellow LEDs to display the signal states of the analog inputs AI0 to AI3 2 yellow LEDs to display the signal states of the analog outputs AO0 to AO1 8 yellow LEDs to display the signal state of the configurable digital inputs/outputs DC16 to DC23...
DA502 Connection > Inputs/Outputs 16.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 16.4.2 Inputs/Outputs Examples Fig. 28: Example for connection output DOx Example for connection as an input Example for connection as an output 2019/11/15 3ADR024117M02xx, 11, en_US...
DA502 Recycling Fig. 29: Example for connection input AIx Fig. 30: Example for connection output AOx 16.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 16.6 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
DC522 — 17 DC522 ● DC522 ● DC522-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 134
DC522 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 135
DC522 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
DC522 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 17.1 Assembly 3ADR024117M02xx, 11, en_US 2019/11/15...
DC522 Connection 17.4 Connection I/O bus Allocation between terminal number and signal name Sensor power supply 24 VDC / 0.5 A 16 yellow LEDs to display the signal states at the digital inputs/outputs (C0 - C15) 1 green LED to display the state of the process supply voltage UP 4 red LEDs to display errors Label Terminal unit...
DC522 Cleaning 17.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 17.4.2 Inputs/Outputs Example Example for connection as an input Example for connection as an output 17.5 Cleaning Cleaning instruction...
DC522 Recycling 17.6 Certification 17.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
DC523 — 18 DC523 ● DC523 ● DC523-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 142
DC523 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 143
DC523 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
DC523 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 18.1 Assembly 3ADR024117M02xx, 11, en_US 2019/11/15...
DC523 Connection 18.4 Connection I/O bus Allocation between terminal number and signal name Sensor power supply 24 VDC / 0.5 A 24 yellow LEDs to display the signal states at the digital inputs/outputs (C0 - C23) 1 green LED to display the state of the process supply voltage UP 4 red LEDs to display errors Label Terminal unit...
DC523 Cleaning 18.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 18.4.2 Inputs/Outputs Example Example for connection as an input Example for connection as an output 18.5 Cleaning Cleaning instruction...
DC523 Recycling 18.6 Certification 18.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
DC532 — 19 DC532 ● DC532 ● DC532-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 150
DC532 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 151
DC532 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
DC532 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 19.1 Assembly 3ADR024117M02xx, 11, en_US 2019/11/15...
DC532 Connection 19.4 Connection I/O bus Allocation between terminal number and signal name 16 yellow LEDs to display the signal states at the digital inputs (I0 - I15) 16 yellow LEDs to display the signal states at the digital outputs (C16 - C31) 1 green LED to display the state of the process supply voltage UP 4 red LEDs to display errors Label...
DC532 Connection > Inputs/Outputs 19.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 19.4.2 Inputs Example Fig. 31: Example for connection input Ix 19.4.3 Inputs/Outputs 2019/11/15 3ADR024117M02xx, 11, en_US...
DC532 Recycling Example Example for connection as an input Example for connection as an output 19.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 19.6 Certification 19.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
DI524 — 20 DI524 ● DI524 ● DI524-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 158
DI524 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 159
DI524 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
DI524 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 20.1 Assembly 3ADR024117M02xx, 11, en_US 2019/11/15...
DI524 Connection 20.4 Connection I/O bus Allocation between terminal number and signal name 32 yellow LEDs to display the signal states at the digital inputs I0 to I31 1 green LEDs to display the states of the process supply voltage UP 4 red LEDs to display errors Label Terminal unit...
DI524 Cleaning 20.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 20.4.2 Inputs Example Fig. 32: Example for connection input Ix 20.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead.
DI524 Recycling 20.6 Certification 20.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
DI581-S — 21 DI581-S ● DI581-S ● DI581-S-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
DI581-S Connection 21.4 Connection I/O bus System LED Allocation between terminal number and signal name 16 yellow/red LEDs to display the signal states of the digital inputs I0 to I15 8 Test pulse outputs T0 to T7 2 rotary switches for setting the PROFIsafe address 1 green LED to display the state of the process supply voltage UP 2 red LEDs to display errors Label...
DI581-S Connection > Inputs 21.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 21.4.2 Inputs Example Fig. 33: Example for connection input Ix AC500-S Safety User Manual For a detailed description of the electrical connection of the module, please refer to the "AC500-S Safety User Manual".
DI581-S Recycling 21.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 21.6 Certification 21.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
DO524 — 22 DO524 ● DO524 ● DO524-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 172
DO524 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 173
DO524 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
DO524 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 22.1 Assembly 3ADR024117M02xx, 11, en_US 2019/11/15...
DO524 Connection 22.4 Connection I/O bus Allocation between terminal number and signal name 32 yellow LEDs to display the signal states at the digital outputs (O0 to O31) 1 green LEDs to display the state of the process supply voltage UP 4 red LEDs to display errors Label Terminal unit...
DO524 Certification 22.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 22.4.2 Outputs Example Fig. 34: Example for connection output 22.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead.
DO524 Recycling 22.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
DO526 — 23 DO526 ● DO526 ● DO526-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 180
DO526 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 181
DO526 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
DO526 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 23.1 Assembly 3ADR024117M02xx, 11, en_US 2019/11/15...
DO526 Connection 23.4 Connection I/O bus Allocation between terminal number and signal name 8 yellow LEDs to display the signal states of the outputs O0 to O7 3 green LEDs to display the states of the process supply voltage UP, UP3 and UP4 2 red LEDs to display errors Label Terminal unit...
DO526 Cleaning 23.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 23.4.2 Outputs Example Fig. 35: Example for connection output 23.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead.
DO526 Recycling 23.6 Certification 23.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
DX522 — 24 DX522 ● DX522 ● DX522-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
Page 188
DX522 WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 189
DX522 NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
DX522 Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 24.1 Assembly 3ADR024117M02xx, 11, en_US 2019/11/15...
DX522 Connection 24.4 Connection I/O bus Allocation between terminal number and signal name 8 yellow LEDs to display the signal states at the digital inputs (I0 - I7) 8 yellow LEDs to display the signal states at the digital relay outputs (R0 - R7) 1 green LED to display the state of the process supply voltage UP 2 red LEDs to display errors Label...
DX522 Connection > Outputs 24.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 24.4.2 Inputs Example Fig. 36: Example for connection input 24.4.3 Outputs If the relay outputs have to switch inductive DC loads, free-wheeling diodes must be circuited in parallel to these loads.
DX522 Recycling If the relay outputs have to switch inductive AC loads, spark suppressors are required. 24.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 24.6 Certification 24.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
DX531 — 25 DX531 ● DX531 CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g. EN 60204-1. –...
Page 196
DX531 H = Hot swap Hot swap System requirements for hot swapping of I/O modules: – Hot-swappable terminal units have the appendix TU5xx-H. – I/O modules as of index F0. – Communication interface modules CI5xx as of index F0. The index of the module is in the right corner of the label. NOTICE! Risk of damage to I/O modules! Modules with index below F0 can be damaged when inserted or removed from...
Page 197
DX531 Device Min. required device index for I/O module as of FW Version 3.0.14 AI531-XC AI561 AI562 AI563 AO523 (-XC) AO561 AX521 (-XC) AX522 (-XC) AX561 CD522 (-XC) DA501 (-XC) DC522 (-XC) DC523 (-XC) DC532 (-XC) DC561 DC562 DI524 (-XC) DI561 DI562 DI571...
DX531 Connection 25.4 Connection I/O bus Allocation between terminal number and signal name 8 yellow LEDs to display the signal states at the digital inputs (I0 - I7) 4 yellow LEDs to display the signal states at the digital relay outputs (R0 - R3) 1 green LED to display the state of the process supply voltage UP 2 red LEDs to display errors Label...
DX531 Connection > Outputs 25.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 25.4.2 Inputs 25.4.3 Outputs If the relay outputs have to switch inductive DC loads, free-wheeling diodes must be circuited in parallel to these loads.
DX531 Recycling 25.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 25.6 Certification 25.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
DX581-S — 26 DX581-S ● DX581-S ● DX581-S-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
DX581-S Connection 26.4 Connection I/O bus System LED Allocation between terminal number and signal name 8 yellow/red LEDs to display the signal states of the digital inputs I0 to I7 4 Test pulse outputs T0 to T3 8 yellow/red LEDs to display the signal states of the digital outputs O0 to O7 2 rotary switches for setting the PROFIsafe address 1 green LED to display the state of the process supply voltage UP 2 red LEDs to display errors...
DX581-S Connection > Inputs/Outputs 26.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 26.4.2 Inputs/Outputs Examples Fig. 37: Example for connection input Ix 2019/11/15 3ADR024117M02xx, 11, en_US...
DX581-S Certification Fig. 38: Example for connection output Ox AC500-S Safety User Manual For a detailed description of the electrical connection of the module, please refer to the "AC500-S Safety User Manual". 26.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead.
DX581-S Recycling 26.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
PD501-4CH — 27 PD501-4CH ● PD501-4CH CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g. EN 60204-1. –...
PD501-4CH Connection 27.4 Connection I/O bus Allocation between terminal number and signal name 4 yellow LEDs to display the signal states of the analog inputs I0 to I3 8 yellow LEDs to display the signal states of the outputs M0 to M3 1 green LED to display the state of the process supply voltage UP 2 green LEDs to display the states of the motor supply voltages UP3 and UP4 4 red LEDs to display errors CH-ERR1 to CH-ERR4...
PD501-4CH Cleaning 27.4.1 Process Supply Voltage CAUTION! The process supply voltage must be included in the earthing concept (e. g. earthing of the minus pole). 27.4.2 Inputs/Outputs 4 analog inputs 3x 0.5 mm² + shield 1 analog output 2x 2.5 mm² 4 digital outputs External connection between I4+ and 10 V for Motor drivers...
PD501-4CH Recycling 27.6 Certification 27.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
PM595 — 28 PM595 ● PM595-4ETH-F ● PM595-4ETH-M-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
PM595 Connection 28.4 Connection I/O bus for connection of I/O modules 2x 5 LEDs to display the states of the fieldbuses Cover for battery and display 5 LEDs to display the states of the processor module 5 LEDs (reserved) 2x2 RJ45 interfaces for fieldbuses Slot for memory card Reset button Button (reserved)
PM595 Connection > Serial Interface COM2 28.4.1 Power Supply Pin Assignment Pin Assignment Label Function Description +24 VDC Positive pin of the power supply voltage +24 VDC Positive pin of the power supply voltage Negative pin of the power supply voltage Terminal block Terminal block removed...
PM595 Cleaning Serial Signal Interface Description Interface +5 V 5 V supply out RS-232 Receive data Input RxD/TxD-N RS-485 Receive/Transmit Negative RS-232 Clear to send Input Shield Functional earth NOTICE! Risk of corrosion! Unused connectors and slots may corrode if XC devices are used in salt-mist environments.
PM595 Recycling 28.6 Certification 28.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
PM56xx-2ETH — 29 PM56xx-2ETH ● PM5610-2ETH ● PM5630-2ETH ● PM5630-2ETH-XC ● PM5650-2ETH ● PM5650-2ETH-XC ● PM5670-2ETH ● PM5670-2ETH-XC ● PM5675-2ETH ● PM5675-2ETH-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! –...
PM56xx-2ETH Connection 29.4 Connection Status displays (7-segment) Triangle displays for ”Item” Square displays for ”Status” Status LEDs Function keys MC: Slot for the SD Memory Card TA525: Label The connection part may be different on various terminal base types. See installation instructions of the specific terminal base suitable for this CPU for connection specifications.
PM56xx-2ETH Recycling For PM5630-2ETH(-XC), the maximum number of communication modules is limited to 2. Only following terminal bases can be used: – TB5600-2ETH(-XC) – TB5610-2ETH(-XC) – TB5620-2ETH(-XC) 29.5 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead.
Page 229
PM5xx (-y) CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g. EN 60204-1. –...
PM5xx (-y) Cleaning 30.4 Connection Status displays (7-segment) Triangle displays for ”Item” Square displays for ”Status” Status LEDs Function keys MC: Slot for the SD Memory Card TA525: Label The connection part may be different on various terminal base types. See installation instructions of the specific terminal base suitable for this CPU for connection specifications.
PM5xx (-y) Recycling 30.6 Certification 30.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
TB56xx-2ETH — 31 TB56xx-2ETH ● TB5600-2ETH ● TB5600-2ETH-XC ● TB5610-2ETH ● TB5610-2ETH-XC ● TB5620-2ETH ● TB5620-2ETH-XC ● TB5640-2ETH ● TB5640-2ETH-XC ● TB5660-2ETH ● TB5660-2ETH-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! –...
TB56xx-2ETH Disassembly XC Version XC = eXtreme Conditions Extreme conditions Terminal bases for use in extreme ambient conditions have no sign for XC version. The figure 3 in the Part no. 1SAP3... (label) identifies the XC version. 31.1 Assembly 31.2 Disassembly 2019/11/15 3ADR024117M02xx, 11, en_US...
TB56xx-2ETH Dimensions 31.3 Assembly with Screws NOTICE! Damage to the modules without using wall mounting accessory! Wall mounting accessories (TA526) prevent bending and damaging the modules during assembly with screws. Inserting the wall mounting accessories TA526 is mandatory. TA526 are snapped on the rear side of the module like DIN rails. One TA526 is turned by 180°.
TB56xx-2ETH Connection > CAN Interface The dimensions are in mm and in brackets in inch. 31.5 Connection I/O bus Slot for processor module Slots for communication modules Interface for CAN Power supply 24 VDC Serial interface COM1 Ethernet network interfaces Holes for wall mounting 31.5.1 CAN Interface...
TB56xx-2ETH Connection > Power Supply Interface Signal Description Terminal block Terminal block CAN_SHLD Shield of the bus line removed inserted CAN_H Bus line, receive/transmit line, HIGH Not connected NOTICE! Unused connector! Make sure that the terminal block is always connected to the terminal base, even if you do not use the interface.
TB56xx-2ETH Recycling 31.6 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 31.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
TB51x-TB54x — 32 TB51x-TB54x ● TB511-ARCNET ● TB511-ETH ● TB511-ETH-XC ● TB521-ARCNET ● TB521-ETH ● TB521-ETH-XC ● TB523-2ETH ● TB541-ETH ● TB541-ETH-XC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! –...
TB51x-TB54x Disassembly XC Version XC = eXtreme Conditions Extreme conditions Terminal bases for use in extreme ambient conditions have no sign for XC version. The figure 3 in the Part no. 1SAP3... (label) identifies the XC version. 32.1 Assembly 32.2 Disassembly 3ADR024117M02xx, 11, en_US 2019/11/15...
TB51x-TB54x Dimensions 32.3 Assembly with Screws NOTICE! Damage to the modules without using wall mounting accessory! Wall mounting accessories (TA526) prevent bending and damaging the modules during assembly with screws. Inserting the wall mounting accessories TA526 is mandatory. TA526 are snapped on the rear side of the module like DIN rails. One TA526 is turned by 180°.
TB51x-TB54x Connection The dimensions are in mm and in brackets in inch. 32.5 Connection I/O bus Slot for processor module Slots for communication modules Interface for FieldBusPlug, not for terminal base TB523-2ETH Power supply 24 VDC Serial interface COM1 Network interfaces: TB5xx-ETH: Ethernet, TB5xx-ARCNET: ARCNET TB5x1: Serial interface COM2, TB523-2ETH: second Ethernet network interface Holes for wall mounting 3ADR024117M02xx, 11, en_US...
TB51x-TB54x Connection > Serial Interface COM2 32.5.1 Power Supply Pin Assignment Pin Assignment Label Function Description +24 VDC Positive pin of the power supply voltage +24 VDC Positive pin of the power supply voltage Negative pin of the power supply voltage Terminal block Terminal block removed...
TB51x-TB54x Connection > Ethernet Network Interface Serial Signal Interface Description Interface +5 V 5 V supply out RS-232 Receive data Input RxD/TxD-N RS-485 Receive/Transmit Negative RS-232 Clear to send Input Shield Functional earth NOTICE! Risk of corrosion! Unused connectors and slots may corrode if XC devices are used in salt-mist environments.
TB51x-TB54x Certification 32.5.6 Fieldbus-neutral Interface Pin Assignment FieldBusPlug Signal Description in Serial Mode +24 V Standard power supply Diagnosis pin Standard power supply Serial data Serial data NOTICE! Risk of corrosion! Unused connectors and slots may corrode if XC devices are used in salt-mist environments.
TB51x-TB54x Recycling 32.8 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.
TU582-S — 33 TU582-S ● TU582-S 24 VDC ● TU582-S-XC 24 VDC CAUTION! Risk of injury and damaging the product! Improper installation and maintenance may result in injury and can damage the product! – Installation and maintenance have to be performed according to the technical rules, codes and relevant standards, e.g.
TU582-S Dimensions 33.3 Assembly with Screws NOTICE! Damage to the modules without using wall mounting accessory! Wall mounting accessories (TA526) prevent bending and damaging the modules during assembly with screws. Inserting the wall mounting accessories TA526 is mandatory. TA526 is snapped on the rear side of the module like DIN rails. Fasten module with screws (M4, max 1.2 Nm) from the front side.
TU582-S Connection The dimensions are in mm and in brackets in inch. 33.5 Connection I/O bus (10 pins, male) to electrically connect the previous terminal unit, the CPU terminal base or the communication interface module to the terminal unit I/O bus (10 pins, female) to electrically connect other terminal units Plug (1x 50 pins and 2x 57 pins) to electrically connect the inserted I/O modules With a screwdriver inserted in this place, the terminal unit and the adjacent terminal unit can be shoved from each other...
TU582-S Recycling 33.6 Cleaning Cleaning instruction Do not use cleaning agent for cleaning the device. Use a damp cloth instead. 33.7 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive.
TU5xx — 34 TU5xx ● ① TU515 24 VDC ● ① TU531 230 VAC ● ① TU541 24 VDC ● ② TU516(-XC) 24 VDC ● ② TU532(-XC) 230 VAC ● ② TU542(-XC) 24 VDC ● ③ TU516-H(-XC) 24 VDC ● ③...
Page 255
TU5xx WARNING! Electric shock due to wrongdoing during hot swapping! To avoid electric shock – follow these conditions for hot swapping: – Digital outputs are not under load. – Input/output voltages above safety extra low voltage/ protective extra low voltages (SELV/PELV) are switched off. –...
Page 256
TU5xx NOTICE! Risk of damage to I/O modules! Do not perform hot swapping if any I/O module with firmware version lower than 3.0.14 is part of the I/O configuration. For min. required device index see table below. Hot swapping is only allowed for I/O modules. Processor modules and communication interface modules must not be removed or inserted during operation.
TU5xx Assembly Device Min. required device index for I/O module as of FW Version 3.0.14 DO572 DO573 DX522 (-XC) DX531 DX561 DX571 FM562 XC Version XC = eXtreme Conditions Extreme conditions Terminal units for use in extreme ambient conditions have no sign for XC version.
TU5xx Assembly with Screws 34.2 Disassembly 34.3 Assembly with Screws NOTICE! Damage to the modules without using wall mounting accessory! Wall mounting accessories (TA526) prevent bending and damaging the modules during assembly with screws. Inserting the wall mounting accessories TA526 is mandatory. TA526 is snapped on the rear side of the module like DIN rails.
TU5xx Cleaning 34.5 Connection Fig. 39: TU516 for example I/O bus (10 pins, male) to electrically connect the previous terminal unit, the CPU terminal base or the communication interface module to the terminal unit I/O bus (10 pins, female) to electrically connect other terminal units 3a Plug (2x 25 pins) to electrically connect the inserted I/O modules 3b For TU515, TU516(-H)(-XC), TU541 and TU542(-H)(-XC): Plug (2x 19 pins) to electrically connect the inserted I/O modules...
TU5xx Recycling 34.7 Certification 34.8 Recycling Disposal and recycling information This symbol on the product (and on its packaging) is in accordance with the European Union's Waste Electrical and Electronic Equipment (WEEE) Directive. The symbol indicates that this product must be recycled/disposed of separately from other household waste.