1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. ...
Page 5
WARNING This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD), with sensitivity of 30mA at 0.1 sec or less. Otherwise, it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown.
Page 6
2. Precaution for Using R32 Refrigerant The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models. However, pay careful attention to the following points: WARNING The appliance shall be stored, installed and operated in a well ventilated room with indoor floor area larger than A ) [refer Table A] and without any continuously operating ignition source.
Page 7
CAUTION Installation (Space) Must ensure the installation of pipe-work shall be kept to a minimum. Avoid use dented pipe and do not allow acute bending. Must ensure that pipe-work shall be protected from physical damage. Must comply with national gas regulations, state municipal rules and legislation. Notify relevant authorities in accordance with all applicable regulations.
Page 8
CAUTION 2-8. Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. Initial safety checks shall include but not limit to:- That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking. That there is no live electrical components and wiring are exposed while charging, recovering or purging the system.
Page 9
CAUTION Removal and evacuation When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: •...
Page 10
CAUTION Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. ...
Page 11
3. Specification Model CS-RZ25VKRW CS-RZ35VKRW Indoor POS (EAN) 5025232889730 5025232889747 Model CU-RZ25VKR CU-RZ35VKR Outdoor POS (EAN) 5025232889808 5025232889815 Performance Test Condition Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. Min. Mid.
Page 12
Model CS-RZ25VKRW CS-RZ35VKRW Indoor POS (EAN) 5025232889730 5025232889747 Model CU-RZ25VKR CU-RZ35VKR Outdoor POS (EAN) 5025232889808 5025232889815 Type Cross-flow Fan Cross-flow Fan Material ASG20K1 ASG20K1 Motor Type DC / Transistor (8 poles) DC / Transistor (8 poles) Input Power 44.9 44.9...
Page 13
Model CS-RZ25VKRW CS-RZ35VKRW Indoor POS (EAN) 5025232889730 5025232889747 Model CU-RZ25VKR CU-RZ35VKR Outdoor POS (EAN) 5025232889808 5025232889815 Height mm (inch) 290 (11-7/16) / 542 (21-11/32) 290 (11-7/16) / 542 (21-11/32) (I/D / O/D) Width Unit mm (inch) 799 (31-15/32) / 780 (30-23/32)
Page 14
Model CS-RZ42VKRW CS-RZ50VKRW Indoor POS (EAN) 5025232889754 5025232889761 Model CU-RZ42VKR CU-RZ50VKR Outdoor POS (EAN) 5025232889822 5025232889839 Performance Test Condition Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. 0.90 4.20 4.60 0.90...
Page 15
Model CS-RZ42VKRW CS-RZ50VKRW Indoor POS (EAN) 5025232889754 5025232889761 Model CU-RZ42VKR CU-RZ50VKR Outdoor POS (EAN) 5025232889822 5025232889839 Type Cross-flow Fan Cross-flow Fan Material ASG20K1 ASG33 Motor Type DC / Transistor (8 poles) DC / Transistor (8 poles) Input Power 44.9 Output Power Cool Heat Cool...
Page 17
Model CS-RZ60VKRW CS-RZ71VKRW Indoor POS (EAN) 5025232889778 5025232889785 Model CU-RZ60VKR CU-RZ71VKR Outdoor POS (EAN) 5025232889846 5025232889853 Performance Test Condition Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. Min. Mid. Max. 0.98 6.00 6.60 0.98...
Page 18
Model CS-RZ60VKRW CS-RZ71VKRW Indoor POS (EAN) 5025232889778 5025232889785 Model CU-RZ60VKR CU-RZ71VKR Outdoor POS (EAN) 5025232889846 5025232889853 Type Cross-flow Fan Cross-flow Fan Material ASG33 ASG33 Motor Type DC / Transistor (8 poles) DC / Transistor (8 poles) Input Power Output Power Cool Heat Cool...
Page 20
Model CS-RZ80VKR Indoor POS (EAN) 5025232889792 Model CU-RZ80VKR Outdoor POS (EAN) 5025232889860 Performance Test Condition Phase, Hz Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 2.30 8.00 9.00 2.30 8.00 9.00 Capacity BTU/h 7840 27300 30700 7840 27300 30700 Kcal/h 1980...
Page 21
Model CS-RZ80VKR Indoor POS (EAN) 5025232889792 Model CU-RZ80VKR Outdoor POS (EAN) 5025232889860 Type Cross-flow Fan Material ASG33 Motor Type DC / Transistor (8 poles) Input Power Output Power Cool Heat Cool Heat Cool 1160 Speed Heat 1190 Cool 1350 Heat 1390 Cool 1400...
Page 22
Model CS-RZ80VKR Indoor POS (EAN) 5025232889792 Model CU-RZ80VKR Outdoor POS (EAN) 5025232889860 Height (ID / OD) mm (inch) 302 (11-29/32) / 795 (31-5/16) Unit Width (ID / OD) mm (inch) 1102 (43-13/32) / 875 (34-15/32) Depth (ID / OD) mm (inch) 244 (9-5/8) / 320 (12-5/8) Dimension Height (ID / OD)
Page 23
Example: The indoor units’ combination below is possible to connect to CU-2Z52VBR. (Total nominal capacity of indoor units is between 3.2kW to 7.7kW) 1) Two CS-RZ25VKRW only. (Total nominal cooling capacity is 5.0kW) Remarks for CU-3Z54VBR 1. At least two indoor units must be connected.
Page 25
4. Features Inverter Technology Wider output power range Energy saving Quick Cooling Quick Heating More precise temperature control Environment Protection Non-ozone depletion substances refrigerant (R32) Long Installation Piping Long piping up to 20 meters (RZ25/35/42VK) and 30 meters (RZ50/60/71/80VK) during single split connection only ...
Page 26
5. Location of Controls and Components Indoor Unit Anti-bacterial filter Aluminium fin Front panel Auto OFF/ON button Use when remote control is misplaced Horizontal airflow or a malfunction occurs. direction louver Indicator Manually adjustable. POWER Vertical airflow TIMER direction louver Powerful Sunlight Sensor Do not adjust...
Page 27
Remote Control Transmitter Transmitter OFF/ON OFF/ON Powerful/Quiet operation Powerful/Quiet operation ECO operation ECO operation Operation mode Airflow direction adjustment Operation mode Airflow direction adjustment Fan speed selection Fan speed selection Temperature setting Temperature setting Timer setting Timer setting Clock setting Clock setting RZ25VKRW, RZ35VKRW, RZ42VKRW RZ50VKRW, RZ60VKRW, RZ71VKRW, RZ80VKR...
Page 28
6. Dimensions Indoor Unit 6.1.1 CS-RZ25VKRW CS-RZ35VKRW CS-RZ42VKRW <Top View> <Side View> <Front View> <Side View> Air intake direction Air outlet Left piping direction Right piping hole <Bottom View> hole <Remote Control> 92.8 <Rear View> 41-61 <Remote Control Holder> Gas side Liquid side Relative position between the indoor unit and the installation plate <Front View>...
Page 29
6.1.2 CS-RZ50VKRW CS-RZ60VKRW CS-RZ71VKRW CS-RZ80VKR <Top View> <Side View> <Front View> <Side View> Air intake 1102 direction Air outlet Left piping Right piping direction hole <Bottom View> hole <Remote Control> <Rear View> 41-61 <Remote Control Holder> Gas side 63.5 Liquid side Relative position between the indoor unit and the installation plate <Front View>...
Page 30
Outdoor Unit 6.2.1 CU-RZ25VKR CU-RZ35VKR <Top View> Space necessary for installation 67.6 104.7 104.9 60.5 100 mm 100 mm 1000 mm Anchor Bolt Pitch 320 x 570 2-way valve at Liquid side <Side View> (High Pressure) <Side View> <Front View> 3-way valve at Gas side (Low Pressure)
Page 31
6.2.3 CU-RZ71VKR <Top View> Space necessary for installation (131) 34.7 100 mm 100 mm 1000 mm Anchor Bolt Pitch 360.5 × 613 2-way valve at Liquid side (High Pressure) 3-way valve at Gas side (Low Pressure) <Front View> <Side View> <Side View>...
Page 32
6.2.4 CU-RZ80VKR <Top View> Space necessary for installation 27.5 100mm 100mm 1000mm Anchor Bolt Pitch 360.5 × 613 <Side View> <Side View> <Front View> 3-way valve at Gas side (Low Pressure) 2-way valve at Liquid side Unit : mm (High Pressure) <Chassis>...
Page 39
9. Wiring Connection Diagram Indoor Unit 9.1.1 CS-RZ25VKRW CS-RZ35VKRW CS-RZ42VKRW TERMINAL FUSE301 HAJEM-A AC306 BOARD T3.15A L250V (WHT) (BLK) AC303 (WHT) AC304 NOISE FILTER (RED) CIRCUIT UP DOWN TEMP. FUSE LOUVER MOTOR 102°C 250V 4.5A G301 COMMUNICATION (OUTER) CIRCUIT (GRN)
Page 40
9.1.2 CS-RZ50VKRW CS-RZ60VKRW CS-RZ71VKRW CS-RZ80VKR 1 CN–CNT HAJEM-A (WHT) (WHT) TERMINAL BOARD AC306 (BLK) SW01 FUSE301 T3.15A L250V AC303 (WHT) NOISE FILTER UP DOWN CIRCUIT LOUVER MOTOR (OUTER) AC304 (RED) TEMP. FUSE 102°C (3A) LEFT RIGHT G301 (GRN) LOUVER MOTOR GROUNDING COMMUNICATION TERMINAL...
Page 41
Outdoor Unit 9.2.1 CU-RZ25VKR CU-RZ42VKR REMARKS YELLOW BLU : BLUE (YEL) OR T(W) BLK : BLACK SINGLE PHASE POWER SUPPLY TO INDOOR UNIT BLUE WHT : WHITE (BLU) (RED) RED : RED OR S(V) OR R(U) YLW : YELLOW (TRADEMARK) GRY : GRAY TERMINAL COMPRESSOR TERMINAL...
Page 42
9.2.2 CU-RZ35VKR YELLOW (YEL) OR T(W) REMARKS BLU : BLUE BLK : BLACK SINGLE PHASE POWER SUPPLY TO INDOOR UNIT WHT : WHITE RED : RED BLUE YLW : YELLOW (RED) (BLU) GRY : GRAY OR R(U) OR S(V) GRN : GREEN TERMINAL TRADEMARK PNK : PINK...
Page 43
9.2.3 CU-RZ50VKR CU-RZ60VKR CU-RZ71VKR YELLOW (YEL) OR T(W) REMARKS SINGLE PHASE BLU : BLUE POWER SUPPLY BLK : BLACK TO INDOOR UNIT WHT : WHITE RED : RED BLUE YLW : YELLOW (RED) (BLU) GRY : GRAY OR R(U) OR S(V) GRN : GREEN TRADEMARK TERMINAL...
Page 44
9.2.4 CU-RZ80VKR REACTOR YELLOW (YLW) TO INDOOR UNIT SINGLE PHASE POWER SUPPLY REMARKS : BLUE : BROWN BLUE TERMINAL TERMINAL : ORANGE : BLACK (BLU) (RED) BOARD BOARD : YELLOW : WHITE CONNECTOR (TRADEMARK) : GRAY : RED WHITE YLW/GRN COMP.
Page 47
10.2 Outdoor Unit 10.2.1 CU-RZ25VKR CU-RZ42VKR SINGLE PHASE POWER SUPPLY TO INDOOR UNIT TERMINAL REACTOR BOARD RAT2 RAT1 (GRY) (GRY) FUSE105 (15A 250V) DATA R206 R205 (RED) 15.8k OUTDOOR AIR TEMP. SENSOR (THERMISTOR) AC-BLK NOISE FILTER CIRCUIT (BLK) COMMUNICATION VJP15 t°...
Page 48
10.2.2 CU-RZ35VKR SINGLE PHASE POWER SUPPLY TO INDOOR UNIT TERMINAL REACTOR BOARD RAT2 RAT1 DATA (GRY) (GRY) (RED) COMMUNICATION CIRCUIT FUSE 2 FUSE 3 (20A 250V) (20A 250V) 15.8k FUSE 103 AC-BLK *R468 (20A 250V) (BLK) PFC CIRCUIT NOISE FILTER 220u CIRCUIT AC-WHT...
Page 49
10.2.3 CU-RZ50VKR CU-RZ60VKR CU-RZ71VKR REACTOR SINGLE PHASE POWER SUPPLY TO INDOOR UNIT RAT2 RAT1 (GRY) (GRY) TERMINAL BOARD 15.8k DATA (RED) 220u FUSE 2 FUSE 3 COMMUNICATION CIRCUIT PFC CIRCUIT FUSE 103 AC-BLK (25A 250V) (BLK) OUTDOOR AIR TEMP. SENSOR (THERMISTOR) NOISE FILTER t°...
Page 50
10.2.4 CU-RZ80VKR REACTOR TO INDOOR UNI T SINGLE PHASE POWER SUPP LY TERMINA L TERMINA L CONNEC TOR BOARD BOARD WHITE YLW/GRN L2-I L2-0 ACN1 ACL1 COM3 ELECTRONIC CONTROLLER (GRAY) (BLACK) (WHITE) (BLACK) (RED) CN-COM CN-COM (MAIN) (YELLOW) (YELLOW) FUSE3 R425 R159 R426...
Page 59
12. Installation Instruction 12.1 Select the Best Location 12.1.2 Indoor Unit Installation Diagram 12.1.1 Indoor Unit o i t o i t up drain hose (Front side) Do not install the unit in excessive oil fume area Right Right such as kitchen, workshop and etc.
Page 60
12.2 Indoor Unit 12.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent it from vibration. Ceiling Wall Wall More than 1 More than 1 More Indoor unit 2 screw than 2 Installation 222 mm plate 1 184 mm...
Page 61
12.2.2 To Drill a Hole in the Wall and Install a Sleeve of Piping Insert the piping sleeve to the hole. Wall Fix the bushing to the sleeve. Indoor Outdoor Cut the sleeve until it extrudes about 15 mm 15 mm from the wall.
Page 62
12.2.3 Indoor Unit Installation ● Do not turn over the unit without it’s shock absorber during pull out the piping. It may cause intake grille damage. ● Use shock absorber during pull out the piping to protect the intake grille from damage. Piping Piping Intake grille...
Page 63
Exchange the drain hose and the cap Rear view for left piping installation Connection cable Piping More than 950mm Drain hose (1/2 ~ 1.75HP) or 1150mm (2.0 ~ 3.0HP) Drain hose Connection cable Drain cap Drain hose Adjust the piping slightly downwards.
Page 64
Secure the connection cable onto the control board with the holder. Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively. Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason. Terminal Board Tape Earth Wire...
Page 65
12.2.5 Connect the Piping 12.2.5.1 Connecting the Piping to Indoor For connection joint of all models Additional Precautions For R32 Models when Please make flare after inserting flare nut (locate at connecting by flaring at indoor side joint portion of tube assembly) onto the copper pipe. (In case of using long piping) Ensure to do re-flaring of pipes before connecting to units to avoid leaking...
Page 66
12.2.5.3 Connecting the Piping to Outdoor Multi Decide piping length and then cut by using pipe cutter. Liquid side Remove burrs from cut edge. Make flare after inserting the Hall Union Flare Nut flare nut (locate at valve) onto the copper pipe. Align center Auxiliary pipe Connection pipe (male side)
Page 67
12.2.8 Check the Drainage Open front panel and remove air filters. (Drainage checking can be carried out without removing the front grille.) Pour a glass of water into the drain tray-styrofoam. Ensure that water flows out from drain hose of the indoor unit.
Page 68
12.3 Select the Best Location 12.3.1 Outdoor Unit If an awning is built over the unit to prevent direct Power supply cable ( ) sunlight or rain, be careful that heat radiation from the condenser is not obstructed. Connection cable ( ) ...
Page 69
12.4 Outdoor Unit 12.4.1 Install the Outdoor Unit After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.
Page 70
AIR PURGING METHOD IS PROHIBITED FOR R32 SYSTEM 12.4.3 Air Tightness Test on the Refrigerating System Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation. There is no extra refrigerant in the outdoor unit for air purging. ...
Page 71
12.4.4 Connect the Cable to the Outdoor Unit Remove the control board cover from the unit Note: by loosening the screw. Isolating Devices (Disconnecting means) should Cable connection to the power supply through have minimum 3.0 mm contact gap. Isolating Devices (Disconnecting means).
Page 72
12.4.5 Piping Insulation Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 6 mm or above.
Page 73
12.5 Wired Remote Controller Installation Manual 12.5.1 Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before installation. Electrical work must be installed by a licensed electrician. The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Page 74
12.5.2 Attached Accessories Name Diagram Remark Remote controller Remote controller cable Length (9.9 m) Screw Installing the remote controller to an outlet box (M4 machine pitched – 30 mm) (embedded cable) Screw Installing the remote controller to the wall (M4 self tapping – 14 mm) (exposed cable) Remote controller cable holder Holder for remote controller cable at control board...
Page 75
Embed an outlet box (JIS C 8336) into the wall. Outlet box may be purchased separately. Medium-sized square outlet box (obtain locally) Part No. DS3744 (Panasonic Co., Ltd.) or equivalent. Secure the remote controller lower case to the outlet box with the two accessory screws 3. Make sure that the lower case is flat against the wall at this time, with no bending.
Page 76
B. If Remote Controller Cable is Exposed Install the remote controller lower case to the wall with the two accessory screws 4. Fasten the screws properly until screw head is lower than the rib and reach the base of remote controller lower case to ensure they do not damage the PCB inside the remote controller 1.
Page 77
12.5.5 Connecting the Remote Controller Cable to Indoor Unit CAUTION Be sure to turn off the main power before installing and connecting the remote controller. Otherwise, it will cause the electrical shock. Open front grille complete Front grille complete (Please refer HOW TO TAKE OUT FRONT GRILLE).
Page 78
13. Installation and Servicing Air Conditioner using R32 13.1 About R32 Refrigerant For air conditioning refrigerants such as R410A, the refrigerants were collected back in order to prevent their air dissipation, to curbe the global warming impact, in case they were released into the atmosphere. In the “4th Environmental Basic Plan”, 80% reduction of greenhouse gas emissions by 2050 is required, and due to this requirement, further reduction in the emission of high greenhouse effect gas, such as CFCs, is required.
Page 79
2. Characteristic of Pressure As shown in Table 2, R32 does not have much difference in vapor pressure at the same refrigerant temperature comparing to R410A, but comparing to R22, it is higher at 1.6 times more. Thus, the same as in case of R410A, it is necessary to do installation and service using high-pressure tools and components.
Page 80
13.3 Refrigerant piping installation • Tools used in services 13.3.1 Required Tools R32 refrigerant air conditioners use the common parts as R410A air conditioners for two-way valves and three-way valves (diameters of service ports); thus, they maintain commonality in the maintenance of the compressive strength, the size of pipe flaring, and the size of flare nuts as R410A.
Page 81
3. Torque wrenches (diameters 1/2, 5/8) Manifold gauges / Charging hoses In order to strengthen the compressive strength, the diameters of wrenches change depending on the flare nut sizes. Torque wrenches Differences in charging hoses Differences in torque wrenches (common R410A) Normal 5.1 MPa 3.4 MPa...
Page 82
7. HFC refrigerant_Electric gas leakage tester 9. Refrigerant cylinders R32 refrigerant is often used for other mixed Refrigerant cylinders for R410A are painted in pink, refrigerant (R410A, R404A, R407C etc.). Therefore, and the ones for R32 are painted in other colors that the usage of existing HFC detectors is possible, but in might subject to change according to the international order to detect more accurately, we recommend to...
Page 83
11. Tools used for refrigerant piping installations and services Tools for R410A Common with R32 Possibility of usage for R22 ○ ○ Pipe cutters, reamers or scrapers ○ ○ Flare tools (clutch type) ○ ○ Torque wrench (1/4, 3/8) ○ ×...
Page 84
13.4 New installation, Relocation, Repairing of Refrigerant Cycle System The Procedures Relocation Repairing refrigerant cycle Installation Indoor / outdoor units and piping Pump down Refrigerant recovery • Displacing pipes and wires, and displacing indoor / outdoor units Prevention of impurity •...
Page 85
13.5 Piping installation of R32 13.5.1 Pipe materials used and flaring Copper pipes are used for refrigerant piping. Pipes Pipe thickness which comply with JIS Regulations need to be used. Room air conditioners which use R410A and R32 O and OL materials Thickness (mm) have higher pressure;...
Page 86
13.6 Installation, Relocation, and Service 13.6.1 Air purge and gas leak test for new installation (using new refrigerant pipes) using vacuum pump (From the point of view of global environment protection, do not release CFCs into the atmosphere during installation work) 1.
Page 87
13.6.2 Process of refrigerant recovery 1. Connect the center charging hose of manifold gauge to the in-let side of recovery device. 2. Connect the valves of the discharge side of recovery device and liquid side of refrigerant cylinder with red hose (charging hose).
Page 88
13.6.3 Relocation 1. Removing the air conditioning unit a) Recovery of outdoor unit refrigerant by pumping down Press “forced cooling button” (as a general rule, since 1998 the name of cooling testing button is changed, and this name is unified within the air conditioning industry), and then you are able to start cooling operation in which the room temperature is low, and you can recover the refrigerant from the outdoor unit.
Page 89
13.6.6 Re-insertion of refrigerant in service When re-insertion is needed, follow the procedures to ensure the insertion of new refrigerant at correct amount. 1. Attach charging hose (blue) to the service port of the outdoor unit. 2. Attach charging hose (red) to the vacuum pump. Fully open the 2-way and 3-way valves. 3.
Page 90
13.7 Repairing of refrigerant cycle / Brazing point 13.7.1 Preparation for repairing of refrigerant cycle / brazing Brazing which is a technique needed for repairing refrigerant cycle requires advanced technique and experience, and this brazing procedure can only be performed by the workers who completed “Gas Welding Skill Training” regulated by the Occupational Safety and Health Act, and went through the training programs of refrigerant operations.
Page 91
2. Cylinder without adjustment valve side gauge pressure is adjusted by the adjuster. Check the both side valves of the torch and open the cylinder valve to check the remaining refrigerant in the cylinder. Caution: Do not attach oil component on the connection port of the adjuster. Especially, use an oxygen cylinder adjuster which is no oil substance type.
Page 92
13.7.5 Types of flame Types of flame change based on the proportion of propane and oxygen. [Neutral Flame] Perform brazing with this flame (This is a flame when oxygen and propane are mixed at proper proportion, and has lesser effect on the brazed metals) White core flame 10 ~ 15 mm...
Page 93
13.7.7 Selection of brazing material Use BAg brazing material (silver solder) to increase the welding performance. Tensile strength Composition of ingredients (%) Temperature (°C) Characteristics (Reference) Category Standard Brazing Base Number Solidus Liquidus Kgf•cm applications temp material Liquidity is good at low temperature, 49.0 14.5...
Page 94
13.7.10 Checking of brazing (insert) points 1. No impurity on the brazing point Gap 0.025 ~ 0.05 mm If dirt or oil is attached on the brazing point, the brazing filler metal does not reach to junction, and Inner diameter ø6.45 it may cause poor welding.
Page 95
Melting temperature of copper • • • • • • • Approx. 1083°C Maximum temperature obtained in propane and oxygen • • • • • • • Approx. 1083°C The important point is to heat the bonding part uniformly within a short period of time until reaching to the brazing temperature in the following manner.
Page 96
13.8 <Reference> Analysis method for no error code, no cooling / no warming 13.8.1 Preparation for appropriate diagnosis In order to obtain appropriate operation characteristics, minimum 15 minutes or more operation time [testing operation (rated operation)] is required. 1. Method of rated operation (rated operation) For the models which have two buttons of “emergency operation and forced cooling operation”, press forced cooling button once.
Page 97
1. Measuring temperature 1) Indoor unit suction temperature, release temperature, temperature difference, → Measure by thermometer 2) 2-way valve pipe temperature in cooling mode is low temperature (benchmark:5 ~ 10°C), in heating mode is medium temperature (benchmark:25 ~ 35°C). 3) 3-way valve pipe temperature in cooling mode is low temperature (benchmark:7 ~ 15°C) in heating mode is high temperature (benchmark:38 ~ 50°C).
Page 98
14. Operation and Control 14.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
Page 99
14.1.5 Automatic Operation This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode and indoor intake air temperature. During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the indoor intake air temperature.
Page 100
14.2 Indoor Fan Motor Operation 14.2.1 Basic Rotation Speed (rpm) A. Basic Rotation Speed (rpm) i. Manual Fan Speed [Cooling, Dry, Fan] Fan motor’s number of rotation is determined according to remote control setting. Remote control ○ ○ ○ ○...
Page 101
14.3 Outdoor Fan Motor Operation Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation. Compressor: Fan Speed Outdoor Fan: 30 sec 14.4 Airflow Direction ...
Page 102
2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close position.
Page 103
14.4.3 Horizontal Airflow (RZ50/60/71/80VK) Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below.
Page 104
14.6 Quiet Operation (Heating) Purpose To provide quiet heating operation compare to normal operation. Control condition Quiet operation start condition When “QUIET” button at remote control is pressed. Quiet operation stop condition When one of the following conditions is satisfied, quiet operation stops: ...
Page 105
14.9 Auto Restart Control When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power supply resumes.
Page 106
Example of wiring: Core HAJEM-A 240 mm Indoor Unit (XH type) Max 1900 mm #A K1KA04AA0347 (Maker: JST; Maker code: B4B-XHTV4) #B Maker: JST; Maker code: XHP-4 Note: The wire length from indoor unit to the external interface must be within 1.9 meters. The wire must be double insulation type and a ferrite core to be added to reduce noise.
Page 107
15. Operation Control (For Multi Split Connection) During multi split connection, indoor unit’s operation controls are same with single split connection unless specified in this chapter. 15.1 Cooling Operation 15.1.1 Thermostat Control Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting temperature <...
Page 108
15.4 Automatic Operation This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode, indoor intake and outdoor air temperature. During operation mode judgment, indoor fan motor (with speed of -Lo) and outdoor fan motor are running for 30 seconds to detect the indoor intake and outdoor air temperature.
Page 109
16. Protection Control 16.1 Protection Control for All Operations 16.1.1 Restart Control (Time Delay Safety Control) The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing OFF/ON button at remote control within this period. ...
Page 110
16.1.4 Compressor Overheating Prevention Control Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency are as below. If compressor discharge temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes, timer LED will be blinking.
Page 111
16.2 Protection Control for Cooling & Soft Dry Operation 16.2.1 Outdoor Air Temperature Control The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below. This control will begin 1 minute after the compressor starts. ...
Page 112
16.2.6 Odor Cut Control To reduce the odor released from the unit. Start Condition AUTO FAN Speed is selected during COOL or DRY operation. During freeze prevention control and timer preliminary operation, this control is not applicable. Control content ...
Page 113
16.3.3 Overload Protection Control The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown below. If the heat exchanger temperature exceeds 60°C, compressor will stop. 60°C Frequency Reduce 55°C 52°C Frequency Limited 49°C 46°C Free Indoor Heat...
Page 114
17. Servicing Mode 17.1 Auto OFF/ON Button Auto OFF/ON Auto OFF/ON Auto OFF/ON Button pressed Button pressed Button pressed 5 sec 5 sec Auto Operation Test Run Operation Stop Test Run Operation Stop (Forced Cooling Operation) (Forced Heating Operation) Beep Beep x 2 AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button is pressed.
Page 115
REMOTE CONTROL RECEIVING SOUND OFF/ON MODE The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote Control Receiving Sound Off/On Mode is in standby condition) and press “AC Reset”...
Page 116
17.2.6 Special Setting mode LCD display area: Special setting display area (highlighted in color) Function Options (If any) Cannot enter this special setting mode under the following conditions: 1 Operation ON. 2 Under [Real/ON/OFF] time setting mode. To enter zone 1 area: Normal display Enter Zone1 mode...
Page 117
Note: The functions described in the table may not be applicable to the model and may subject to change without further notice. Function Options Remark Name A, B, C, D Remote control number selection 1, 2, 3, 4, 5 Solar radiation sensitivity level adjustment [iAUTO-X/iAUTO/iCOMF, Cool &...
Page 118
18. Troubleshooting Guide 18.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no Normal Pressure and Outlet Air Temperature (Standard) electrical problems before inspecting the refrigeration cycle. Gas pressure Outlet air temperature Such problems include insufficient insulation, problem with the (kg/cm (°C) power source, malfunction of a compressor and a fan.
Page 119
18.1.1 Relationship Between the Condition of the Air Conditioner and Pressure and Electric Current Cooling Mode Heating Mode Condition of the Electric current Electric current air conditioner Low Pressure High Pressure Low Pressure High Pressure during operation during operation Insufficient refrigerant ...
Page 120
18.2 Breakdown Self Diagnosis Function 18.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code) Every press of the button (up or down) will Once abnormality has occurred during operation, increase abnormality numbers and transmit the unit will stop its operation, and Timer LED abnormality code signal to the main unit.
Page 121
18.3 Error Code Table Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation No memory of failure — Normal operation — — Indoor fan only Indoor/outdoor wire terminal Indoor/outdoor operation can Indoor/outdoor After operation for ...
Page 122
Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation Check indoor/outdoor Wrong wiring and connection wire and connection Abnormal wiring or — — connecting pipe, expansion pipe piping connection valve abnormality Expansion valve and lead wire and connector ...
Page 123
18.4 Self-diagnosis Method 18.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused Faulty indoor unit PCB.
Page 124
18.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions During startup, error code appears when different types of indoor and outdoor units are interconnected. Malfunction Caused Wrong models interconnected. Wrong indoor unit or outdoor unit PCBs mounted. ...
Page 125
18.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 126
18.4.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor.
Page 127
18.4.5 H16 (Outdoor Current Transformer) Malfunction Decision Conditions An input current, detected by Current Transformer CT, is below threshold value when the compressor is operating at certain frequency value for 3 minutes. Malfunction Caused Lack of gas. Broken CT (current transformer).
Page 128
18.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm). Malfunction Caused ...
Page 129
18.4.7 H23 (Indoor Pipe Temperature Sensor 1 Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor 1 are used to determine sensor errors. Malfunction Caused Faulty connector connection.
Page 130
18.4.8 H24 (Indoor Pipe Temperature Sensor 2 Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor 2 are used to determine sensor errors. Malfunction Caused Faulty connector connection.
Page 131
18.4.9 H25 (nanoe-G Air Purifying System Abnormal) Malfunction Decision Conditions During standby of cooling and heating operation, nanoe-G breakdown occurs and air conditioner stops operation. Malfunction Caused Faulty indoor main PCB. Faulty indoor nanoe-G power module. Troubleshooting When abnormality indication starts again For safety reason and to prevent component breakdown, always switch off the power...
Page 132
18.4.10 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 133
18.4.11 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 134
18.4.12 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 135
18.4.13 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused Wrong models interconnected. Wrong indoor unit and outdoor unit PCBs used. Indoor unit or outdoor unit PCB defective.
Page 136
18.4.14 H59 (Human Activity Sensor Abnormality) Malfunction Decision Conditions Feedback signal of human activity sensor. Malfunction Caused Feedback signal is fixed at 0 VDC or 5 VDC continuously for 25 seconds during ECONAVI or AUTO COMFORT operation. Feedback signal is detected during ECONAVI or AUTO COMFORT off.
Page 137
18.4.15 H70 (Light Sensor Abnormality) Malfunction Decision Conditions Feedback signal of light sensor. Malfunction Caused Feedback value is 0 VDC continuously. Troubleshooting When abnormality indication starts again. For safety reason and to prevent Check the connector connection: component breakdown, always switch Turn off the power.
Page 138
18.4.16 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) 18.4.16.1 CU-RZ25/35/42/50/60/71VKRW Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused Operation stops due to short circuit inside the fan motor winding. ...
Page 139
18.4.16.2 CU-RZ80VKR Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused Operation stops due to short circuit inside the fan motor winding. Operation stops due to breaking of wire inside the fan motor.
Page 140
18.4.17 H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED flashing) Malfunction Decision Conditions Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation. ...
Page 141
18.4.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Conditions Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C). Malfunction Caused ...
Page 142
18.4.19 F11 (4-way Valve Switching Failure) Malfunction Decision Conditions When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during cooling and compressor operating, the 4-way valve is detected as malfunction. Malfunction Caused ...
Page 143
18.4.20 F90 (Power Factor Correction Protection) Malfunction Decision Conditions To maintain DC voltage level supply to power transistor. To detect high DC voltage level after rectification. Malfunction Caused During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at the outdoor unit main PCB senses abnormal DC voltage level for power transistors.
Page 144
18.4.21 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions The input current is low while the compressor is running at higher than the setting frequency. Malfunction Caused Lack of gas. 3-way valve close. Troubleshooting When F91 indication happens. For safety reason and to prevent component breakdown, always switch off the power before remove and...
Page 145
18.4.22 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused Compressor terminal disconnect. Faulty Outdoor PCB. Faulty compressor. Troubleshooting When F93 indication happens.
Page 146
18.4.23 F95 (Outdoor High Pressure Protection: Cooling or Soft Dry) Malfunction Decision Conditions During operation of cooling or soft dry, when outdoor unit heat exchanger high temperature data is detected by the outdoor unit heat exchanger thermistor. Malfunction Caused ...
Page 147
18.4.24 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooling and heating, when IPM temperature data (120°C) is detected by the IPM temperature sensor. Multi Models only Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated. Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is detected by the heat sink temperature sensor.
Page 148
18.4.25 F97 (Compress Overheating) Malfunction Decision Conditions During operation of cooling and heating, when compressor tank temperature data (103°C) is detected by the compressor tank temperature sensor. Malfunction Caused Faulty compressor tank temperature sensor 2/3 way valve closed ...
Page 149
18.4.26 F98 (Input Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is detected by checking the input current value being detected by current transformer (CT) with the compressor running.
Page 150
18.4.27 F99 (DC Peak Detection) Malfunction Decision Conditions During startup and operation of cooling and heating, when inverter DC peak data is received by the outdoor internal DC Peak sensing circuitry. Malfunction Caused DC current peak due to compressor failure. ...
Page 151
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 19.1 CS-RZ25VKRW CS-RZ35VKRW CS-RZ42VKRW 19.1.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 19.1.1.1...
Page 152
5 Detach the Earth wire screw, lead wires AC306 (Black) and AC304 (Red) from the terminal board. 9 Detach connectors as labeled from the electronic controller. Then pull out main controller gently. 8 Pull out the main electronic controller AC303 halfway.
Page 153
19.1.1.4 To Remove Control Board 12 Remove 4 screws holding the control board then pull out the control board. Figure 6 19.1.1.5 To Remove Cross Flow Fan and Indoor Fan Motor Figure 7 15 Remove the bearing by pulling it out gently. 14 Remove the 2 screw from the evaporator Figure 8...
Page 155
WARNING High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 19.2 CS-RZ50VKRW CS-RZ60VKRW CS-RZ71VKRW CS-RZ80VKR 19.2.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures...
Page 156
19.2.1.3 To Remove Electronic Controller Detach the Earth wire screw, lead wires AC306 (Black) and AC304 (Red) from the terminal board. Detach connectors as labeled from the Pull out the main electronic controller. Then pull out the mai electronic controller. controller gently.
Page 157
19.2.1.5 To Remove Control Board 12 Remove 4 screws holding the control board then pull out the control board. Figure 6 19.2.1.6 To Remove Cross Flow Fan and Indoor Fan Motor Figure 7 Holdfast Remove the screw from the evaporator. Remove the bearing by pulling it out gently.
Page 159
19.3 Outdoor Electronic Controller Removal Procedure 19.3.1 CU-RZ25VKR CU-RZ35VKR Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove the Control Board as follows: Screws Top Panel Release 3 Terminal Screws Connectors, L, N and Earth Wire Screw.
Page 160
19.3.2 CU-RZ42VKR CU-RZ50VKR CU-RZ60VKR Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove the Control Board as follows: Fig. 1 Fig. 4 Remove the 8 screws of the Front Panel. Fig.
Page 161
19.3.3 CU-RZ71VKR Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove 2 screws for the plate of Terminal Board Cover. Top Panel Screw Plate of Terminal Board Cover Screws Screws Screws Fig.
Page 162
19.3.4 CU-RZ80VKR Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 4 screws of the Top Panel. Remove the Control Board. Fig. 4 Remove the 8 screws of the Electronic Controller. Fig. 1 Remove the 10 screws of the Front Panel. Fig.
Page 163
20. Technical Data Technical data provided are based on the air conditioner running under free frequency. 20.1 Sensible Capacity Chart 20.1.1 CS-RZ25VKRW CU-RZ25VKR Cooling Indoor (°C) Outdoor DB (°C) 2318 2289 477 2424 2424 468 2530 2530 460 2636 2294 451 2782 2629 270 2730 2511 338 2545 2447 415...
Page 184
21.3 Piping Length Correction Factor The characteristic of the unit has to be corrected in accordance with the piping length. 21.3.1 CS-RZ25VKRW CU-RZ25VKR CS-RZ35VKRW CU-RZ35VKR CS-RZ42VKRW CU-RZ42VKR 1.02 Cooling Capacity 1.00 1.0119 1.0000 0.98 0.9792 0.96 0.9550 0.94 0.9085 0.92 0.90...
Page 186
22. Exploded View and Replacement Parts List 22.1 Indoor Unit 22.1.1 CS-RZ25VKRW CS-RZ35VKRW CS-RZ42VKRW CWH5 5025J CWH5 5051J CS-RZ25VKRW CS-RZ35VKRW CS-RZ42VKRW 49612 49613 49611 -068 -068 -069 49611 49612 49613 -068 -068 -069 Note The above exploded view is for the purpose of parts disassembly and replacement.
Page 187
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-RZ25VKRW CS-RZ35VKRW REMARK CHASSIS COMPLETE ACXD50C00440 ← FAN MOTOR L6CBYYYL0195 ← CROSS-FLOW FAN COMPLETE CWH02C1159 ← BEARING ASSY CWH64K1006 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C02750 ACXB30C24420 FLARE NUT (LIQUID) CWT251048 ←...
Page 188
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-RZ25VKRW CS-RZ35VKRW REMARK SHOCK ABSORBER (LEFT) ACXG70-01020 ← SHOCK ABSORBER (RIGHT) ACXG70-01030 ← C. C. CASE ACXG50-48660 ← MODEL LABEL ACXF85-06880 ACXF85-06890 (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
Page 189
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-RZ42VKRW REMARK CHASSIS COMPLETE ACXD50C00440 FAN MOTOR L6CBYYYL0195 CROSS-FLOW FAN COMPLETE CWH02C1159 BEARING ASSY CWH64K1006 SCREW - CROSS-FLOW FAN CWH551146 EVAPORATOR ACXB30C24430 FLARE NUT (LIQUID) CWT251048 FLARE NUT (GAS) CWT251032 CONTROL BOARD CASING ACXH10-00870 TERMINAL BOARD COMPLETE ACXA28C00260...
Page 190
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-RZ42VKRW REMARK SHOCK ABSORBER (LEFT) ACXG70-01020 SHOCK ABSORBER (RIGHT) ACXG70-01030 C. C. CASE ACXG50-48660 MODEL LABEL ACXF85-06900 (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O” marked parts are recommended to be kept in stock.
Page 191
22.1.2 CS-RZ50VKRW CS-RZ60VKRW CS-RZ71VKRW CS-RZ80VKR CWH 55025J CWH 55051J CS-RZ50VKRW CS-RZ60VKRW CS-RZ71VKRW CS-RZ80VKR 49614 49615 49616 49617 -069 -069 -069 -069 49614 49615 49616 49617 -069 -069 -069 -069 Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 192
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-RZ50VKRW CS-RZ60VKRW REMARK CHASSIS COMPLETE ACXD50C01590 ← FAN MOTOR L6CBYYYL0193 ← CROSS-FLOW FAN COMPLETE CWH02C1136 ← BEARING ASSY CWH64K1010 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C02760 ACXB30C24650 PARTICULAR PIECE CWD933067B ←...
Page 193
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-RZ50VKRW CS-RZ60VKRW REMARK ACXG86-00130 ← SHOCK ABSORBER (RIGHT) ACXG70-01220 ← SHOCK ABSORBER (LEFT) ACXG70-01230 ← C. C. CASE ACXG50-48680 ← MODEL LABEL ACXF85-06910 ACXF85-06920 (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). ...
Page 194
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-RZ71VKRW CS-RZ80VKR REMARK CHASSIS COMPLETE ACXD50C01590 ← FAN MOTOR L6CBYYYL0194 ← CROSS-FLOW FAN COMPLETE CWH02C1136 ← BEARING ASSY CWH64K1010 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C24660 ← PARTICULAR PIECE CWD933067B ←...
Page 195
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-RZ71VKRW CS-RZ80VKR REMARK ACXG86-00130 ← SHOCK ABSORBER (RIGHT) ACXG70-01220 ← SHOCK ABSORBER (LEFT) ACXG70-01230 ← C. C. CASE ACXG50-48680 ← MODEL LABEL ACXF85-06930 ACXF85-06940 (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). ...
Page 196
22.2 Outdoor Unit 22.2.1 CU-RZ25VKR CU-RZ35VKR CU-RZ25VKR 65804 F85- 0523 65804 F85- 0523 CU-RZ35VKR 65805 F85- 0524 65805 F85- 0524 CU-RZ35VKR Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 197
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ25VKR CU-RZ35VKR REMARK CHASSIS COMPLETE CWD52K1399 ← FAN MOTOR BRACKET CWD541157 ← SCREW - FAN MOTOR BRACKET CWH551217 ← FAN MOTOR L6CAYYYL0064 ← SCREW - FAN MOTOR MOUNT CWH55252J ← PROPELLER FAN ASSY CWH03K1100 ←...
Page 199
22.2.2 CU-RZ42VKR CU-RZ50VKR CU-RZ60VKR CU-RZ42VKR 65806 -052 65806 -052 CU-RZ50VKR 65807 -052 65807 -052 CU-RZ60VKR 65808 -052 65808 -052 CU-RZ50VKR CU-RZ60VKR Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 200
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ42VKR CU-RZ50VKR REMARK CHASSIS COMPLETE CWD52K1277 ← FAN MOTOR BRACKET CWD541167 ← SCREW - FAN MOTOR BRACKET CWH551217 ← FAN MOTOR L6CAYYYL0064 ← SCREW - FAN MOTOR MOUNT CWH55252J ← PROPELLER FAN ASSY CWH03K1066 ←...
Page 202
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ60VKR REMARK CHASSIS COMPLETE CWD52K1277 FAN MOTOR BRACKET CWD541167 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR L6CAYYYL0064 SCREW - FAN MOTOR MOUNT CWH55252J PROPELLER FAN ASSY CWH03K1066 NUT - PROPELLER FAN CWH56053J COMPRESSOR 9RD132XAB21...
Page 203
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ60VKR REMARK PANASONIC BADGE CWE373439 INVERTER BADGE CWE373441 INSTALLATION INSTRUCTION ACXF60-34050 BAG - COMPLETE CWG87C900 FLEXIBLE PIPE (L-TUBE) CWH5850080 PACKING - L. TUBE CWB81012 CWG861078 BASE BOARD - COMPLETE CWG62C1144 SHOCK ABSORBER (LEFT)
Page 204
22.2.3 CU-RZ71VKR 65809 -052 65809 -052 Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 205
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ71VKR REMARK CHASSIS COMPLETE ACXD52K00280 FAN MOTOR BRACKET ACXD54-00140 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR L6CAYYYL0076 SCREW - FAN MOTOR MOUNT CWH551106J PROPELLER FAN ASSY ACXH03K00070 NUT - PROPELLER FAN CWH56053J COMPRESSOR 9KD240XBA21...
Page 206
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ71VKR REMARK PANASONIC BADGE CWE373439 INVERTER BADGE CWE373441 INSTALLATION INSTRUCTION ACXF60-34050 BAG - COMPLETE CWG87C900 FLEXIBLE PIPE (L-TUBE) CWH5850080 PACKING - L. TUBE CWB81012 CWG861461 BASE BOARD - COMPLETE ACXG62C00940 SHOCK ABSORBER (LEFT)
Page 207
22.2.4 CU-RZ80VKR 65810 -052 65810 -052 Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service part.
Page 208
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ80VKR REMARK CHASSIS COMPLETE CWD52K1190 FAN MOTOR BRACKET CWD541127 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR EHDS80C60AC SCREW - FAN MOTOR MOUNT CWH551323 PROPELLER FAN ASSY CWH00K1006 NUT - PROPELLER FAN CWH561092 COMPRESSOR 9KD240XBA21...
Page 209
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ80VKR REMARK PANASONIC BADGE CWE373439 INVERTER BADGE CWE373441 INSTALLATION INSTRUCTION ACXF60-34050 BAG - COMPLETE CWG87C900 FLEXIBLE PIPE (L-TUBE) CWH5850080 PACKING - L. TUBE CWB81012 CWG861154 BASE BOARD - COMPLETE CWG62C1081 SHOCK ABSORBER (LEFT)