Use the Conettix D6686/D6682/D6680 Ethernet Network Adapter to connect a manufacturer’s automation software package to the D6600/D6100IPv6/D6100i when the software cannot receive network data (Figure 1). Refer to the Special Conettix D6600 Applications in the Conettix D6600/D6100IPv6/D6100i Network System Guide (P/N: 4998122712).
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 1.0 System Connection Direct Connection – RS-232 Figure 2 and Figure 3 show a D6600 System using any manufacturer’s automation software package directly connected to a D6600/D6100IPv6/D6100i. Figure 2: D6600 System – Direct Connect...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 2.0 Making the Right Connection 2.0 Making the Right Connection COM3 DB9 Connector The COM3 Port uses a standard DB9 female connector. The suggested connections to the computer are shown in Figure 4 to Figure 6.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.0 Computer Communication Protocols D6500 Mode Messages In D6500 Mode, the line number/group number sent to the computer is only one digit. Refer to Table 2. Table 2: D6600 Line Number/Group Number Conversion Table...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.1.5 Ademco 10-Digit Contact-ID (Message Type a) Contact D6500 Byte Description Example Table 7: Message Type a (Ademco 10-Digit) Byte Description Title Description Header Character Optional. Check with the computer automation software for compatibility.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.1.11 DNIS/ANI (Message Type N) DNIS/ANI D6500 Byte Description Example & Table 13: DNIS/ANI (Message Type N) Byte Description Title Description Header Character Optional. Check with the computer automation software for compatibility.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.1.13 FBI Super Fast (Message Type F) FBI Super D6500 Byte Description Fast Example 10 11 12 13 14 15 16 17 18 19 20 21 22 Table 15: FBI Super Fast (Message Type F) Byte Description...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.1.15 Link Test (Message Type 1) Link Test D6500 Byte Description Example 10 11 12 13 14 15 16 17 18 19 20 21 22 The D6600/D6100IPv6/D6100i can automatically generate this message at the programmed intervals.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols Table 25: SIA (Message Type S) Byte Description Title Description Header Optional. Check with the computer automation software for Character (h) compatibility. Message Type Receiver Receiver gateway number from 01 to 99.
Page 30
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols Optional Silent Knight SK1 (Message Type m): If Menu Item 2.5.16 in the D6600/D6100IPv6/D6100i Receiver is equal to 1, the following output is used. Silent Knight D6500 Byte Description...
Page 31
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols Table 28: Silent Knight Automation Format To Automation Report Code Description Note 2 5 16=0(EEZZ) 2 5 16=1(ZZ) Alarm Panic PAss 01 to 08: Alarm 01 to 08 sA0x...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.1.24 Silent Knight FSK1 (Message Type m) Silent Knight D6500 Byte Description FSK1 Example 10 11 12 13 14 15 16 17 18 19 “ … Table 29: Silent Knight FSK1 (Message Type m) Byte Description...
Page 33
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols Optional Silent Knight SK1 (Message Type m): If Menu Item 2.5.16 in the D6600/D6100IPv6/D6100i Receiver is equal to 1, the following output is used. Silent Knight D6500 Byte Description...
Page 34
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols Table 31: Silent Knight Automation Format To Automation Report Code Description Note 2 5 16=0(EEZZ) 2 5 16=1(ZZ) Alarm Panic PAss 01 to 08: Alarm 01 to 08 sA0x...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.1.27 Telim (Message Type n) Telim D6500 Byte Description Example Table 34: Telim (Message Type n) Byte Description Title Description Header Optional. Check with the computer automation software for compatibility.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols SIA Mode Messages Use the SIA mode for central station monitoring. 3.2.1 Acron Super Fast (Message Type 9) Acron Super SIA Mode Description Fast Example <LF><CRC><9><sequence#><receiver#><line#>[#aaaa|CCCCCCCC]<CR> Table 41: Acron Super Fast (Message Type 9) Byte Description...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.2 Ademco Contact-ID (Message Type a) Contact-ID SIA Mode Description Example <LF><CRC><a><sequence#><receiver#><line#>[#aaaa|18QXYZGGCCC]<CR> Table 43: Ademco Contact-ID (Message Type a) Byte Description Title Description Standard line feed character. Cyclical redundancy check number.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.3 Ademco 10-Digit (Message Type b) 10-Digit SIA Mode Description Example <LF><CRC><a><sequence#><receiver#><line#>[#aaaaaaaaaa|58QXYZGGCCC]<CR> Table 45: Ademco 10-Digit (Message Type b) Byte Description Title Description Standard line feed character. Cyclical redundancy check number.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.4 Ademco 4-1 Express (Message Type b) 4-1 Express SIA Mode Description Example <LF><CRC><b><sequence#><receiver#><line#>[#aaaa|X]<CR> Table 47: Ademco 4-1 Express (Message Type b) Byte Description Title Description Standard line feed character.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.5 Ademco 4-2 Express (Message Type c) 4-2 Express SIA Mode Description Example <LF><CRC><c><sequence#><receiver#><line#>[#aaaa|XY]<CR> Table 49: Ademco 4-2 Express (Message Type c) Byte Description Title Description Standard line feed character.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.6 Ademco High Speed 4-8-1, SCANCOM 4-8-1 (Message Type f) SCANCOM 5-8-1, 6-8-1 - available upon request High Speed SIA Mode Description Example <LF><CRC><f><sequence#><receiver#><line#>[#aaaaaa|CCCCsCCCCsC]<CR> Table 51: Ademco High Speed 4-8-1, SCANCOM 4-8-1 (Message Type F) Byte Description...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.7 ADT SIA (Message Type S) ADT SIA SIA Mode Description Example <LF><CRC><S><sequence#><receiver#><line#>[#aaaa|<E><damm-dd- yytihh:mm:ss>data]<CR> Table 53: ADT SIA (Message Type S) Byte Description Title Description Standard line feed character.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.8 Caller ID (Message Type <TAB>) SIA Example SIA Mode Description <LF><CRC><TAB><sequence#><receiver#><line#>[#0000|&TTTTTTTTTTTTTTTT]<CR> Table 54: Caller ID (Message Type <TAB>) Byte Description Title Description Standard line feed character. Cyclical Redundancy Check number.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.9 CFSK (Message Type i) CFSK Example SIA Mode Description <LF><CRC><I><sequence#><Receiver#><line#>[#aaaaaa|TTEE]<CR> Table 55: CFSK (Message Type i) Byte Description Title Description Standard line feed character. Cyclical redundancy check number.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.10 Common Formats (Message Type <TAB>) Defined SIA Mode Description Messages SIA <LF><CRC><TAB><sequence#><receiver#><line#>[#aaaaaaaaaaaaaaaa|data]<CR> Example Table 56: Common Formats (Message Type <TAB>) Byte Description Title Description Standard line feed character.
Page 54
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols Undefined Messages When a common format message contains unprintable hexadecimal characters (unprintable characters are out of ASCII range 0x32-0x7E) or without an account block: SIA Example SIA Mode Description <LF><CRC><TAB><sequence#><receiver#><line#>[data]<CR>...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.11 DNIS/ANI (Message Type N) SIA Example SIA Mode Description <LF><CRC><N><sequence#><receiver#><line#>[#0000|Dddddddddddd&aaaaaaaaaa] <CR> Table 58: DNIS/ANI (Message Type N) Byte Description Title Description Standard line feed character. Cyclical redundancy check number.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.13 FBI Super Fast (Message Type F) FBI Super Fast SIA Mode Description Example <LF><CRC><F><sequence#><receiver#><line#>[#aaaa|TZZE]<CR> Table 63: FBI Super Fast (Message Type F) Byte Description Title Description Standard line feed character.
Page 59
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols Table 64: FBI Super Fast (Message Type F) Printer Output Characters Description FBI Super Fast format. Lxx: Line number. Grouped line numbers. Table 65: Event Code Table Code Zone/Event Type...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.14 ITI (Message Type I) ITI Example SIA Mode Description <LF><CRC><I><sequence#><receiver#><line#>[#aaaaa|GIZZEWN]<CR> Table 67: ITI (Message Type I) Byte Description Title Description Standard line feed character. Cyclical redundancy check number.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.16 RB2000 (Message Type R) Description RB2000 SIA Mode Description Example <LF><CRC><R><sequence#><receiver#><line#>[<VDS message>]<CR> Table 69: RB2000 (Message Type R) Byte Description Title Description Standard line feed character, hex 0A.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols Table 70: RB2000 (Message Type R) Printer Output Characters Description MM/DDsHH:MM Date and time. RB2000 format. Line number. ACCT Subscriber number, up to 12 characters(hex). xxxxxxxxxxxx RB2000_EVENT_R The raw data of RB2000 event.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.18 Scancom 4-16-1, 5-16-1, 6-16-1 - Available Upon Request (Message Type g) 4-16-1 SIA Mode Description Example <LF><CRC><g><sequence#><receiver#><line#> [#aaaaaa|CCCCsCCCCsCCCCsCCCCsC]<CR> Table 72: Scancom 4-16-1, 5-16-1, 6-16-1 - Available Upon Request (Message Type g) Byte...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.19 Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) 4-24-1 SIA Mode Description Example <LF><CRC><h><sequence#><receiver#><line#>[#aaaaaa|CCCCsCCCCs CCCCs CCCCsCCCCsCCCCsC]<CR> Table 74: Scancom 4-24-1, 5-24-1, 6-24-1 - Available Upon Request (Message Type h) Byte...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.22 Sescoa Super Speed (Message Type 7) Sescoa Super SIA Mode Description Speed <LF><CRC><7><sequence#><receiver#><line#>[#aaaa| IAAC]<CR> Example Table 78: Sescoa Super Speed (Message Type 7) Byte Description Title Description Standard line feed character.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.24 Silent Knight FSK1 (Message Type m) Silent Knight SIA Mode Description FSK1 Example <LF><CRC><m><sequence#><receiver#><line#>[#aaaa| EEZZ”ECZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ]<CR> Table 81: Silent Knight FSK1 (Message Type m) Byte Description Title Description Standard line feed character.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.25 Silent Knight FSK2 (Message Type m) Silent Knight SIA Mode Description FSK2 Example <LF><CRC><m><sequence#><receiver#><line#>[#aaaaaa| EEZZ”ECZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ]<CR> Table 84: Silent Knight FSK2 (Message Type m) Byte Description Title Description Standard line feed character.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.30 VONK (Message Type V) VONK Example SIA Mode Description <LF><CRC><V><sequence#><receiver#><line#>[#aa|123456789ABCDEFG]<CR> Table 90: VONK (Message Type V) Byte Description Title Description Standard line feed character. Cyclical redundancy check number.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols 3.2.31 X-SIA text (Message Type <TAB>) X-SIA Example SIA Mode Description <LF><CRC><TAB><sequence#><receiver#><line#>[#aaaa|EMMZZZZ*'TTTTTTTTTTTTT'NM/*** ]<CR> Table 91: X-SIA text (Message Type <TAB>) Byte Description Title Description Standard line feed character. Cyclical redundancy check number.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols Table 92: X-SIA Printer/LCD output Characters Description MM/DDsHH:MM Date and time. Line number. SIA format. AAAA Account code. SIA block code. SIA event code. ZZZZ Zone number. Text identifier.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication Protocols Input Command Processing Input devices, such as automation systems, send the commands described in Table 94 to the receiver. If the receiver does not recognize a command, it generates a REJECT COMMAND message, prints at connected printers, and sends an ASCII text message to the automation port.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications Appendix A: Contact ID Event Code Classifications Figure 26: Contact ID format 1234 E 123 01 123 1 - Customer (Subscriber Account Number) 2 - Event Qualifier - E = New Event, R = Restore...
Page 79
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications Table 96: Contact ID Event Code Classifications Event Type Zone Medical: Medical Emerg-Personal Emergency-# Pendant Emerg-Personal Emergency-# Transmitter Fail to report in Emerg-Fail to check in-#...
Page 80
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications Table 96: Contact ID Event Code Classifications (continued) Event Type Zone General Alarms: General Alarm Alarm-General Alarm-# Polling Loop Open Alarm-Polling Loop Open Polling Loop Short...
Page 81
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications Table 96: Contact ID Event Code Classifications (continued) Event Type Zone System Troubles: System Trouble Trouble-System Trouble AC Loss Trouble-AC Power Low System Batt Trouble-Low Battery...
Page 82
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications Table 96: Contact ID Event Code Classifications (continued) Event Type Zone Local Printer Trouble-Local Printer Failure Exp. Mod. DC Loss Trouble-Exp. Mod. DC Loss-# Exp. Mod. Low bat Trouble-Exp.
Page 83
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications Table 96: Contact ID Event Code Classifications (continued) Event Type Zone Sensor: Sensor TRBL-Global Trouble-Sensor Trouble-# Loss Of Supervision Trouble-RF Sensor Super.-# Loss Of Supervisn Trouble-RPM Sensor Super.-#...
Page 84
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications Table 96: Contact ID Event Code Classifications (continued) Event Type Zone Failed to Close Trouble-Fail to Close (Restore not applicable) Auto-Arm Failed Trouble-Auto Arm Failed (Restore not applicable)
Page 85
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications Table 96: Contact ID Event Code Classifications (continued) Event Type Zone Access Program Access-ACS Prog. Exit-User # (Restore not applicable) Mode Exit Access Threat Level Access-ACS Threat Level Chg.
Page 86
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications Table 96: Contact ID Event Code Classifications (continued) Event Type Zone 24 Hour Zone Bypass-24 Hour Bypass-# Bypass Burg. Bypass Bypass-Burg. Bypass-# Group Bypass Bypass-Group Bypass-User #...
Page 87
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix A: Contact ID Event Code Classifications Table 96: Contact ID Event Code Classifications (continued) Event Type Zone Program Mode Trouble-Program Mode Entry (Restore not applicable) Entry Program Mode Exit Trouble-Program Mode Exit (Restore not applicable)
Page 89
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix B: Internal Messages Table 97: Internal Messages (continued) Internal Messages D6500 SIA Output Printer Output Output Printer Off Line X 20 [NVZ] PRINTER OFF LINE External PRT Error X 21 [NVT] EXTERNAL PRINTER ERROR...
Page 90
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix B: Internal Messages Table 97: Internal Messages (continued) Internal Messages D6500 SIA Output Printer Output Output Slotx/Linex (Lxx) No X 63 [NUT04] NO DATA RECEIVED Data Received Slotx/Linex (Lxx) X 64 [NYW02]...
Page 91
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix B: Internal Messages Table 97: Internal Messages (continued) Internal Messages D6500 SIA Output Printer Output Output C900 Switched to X 87 [NSC0004] C900 SWITCHED TO INTERCEPT Intercept C900 Switched to X 82...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix C:Modem4/Modem IIIa2 Messages Appendix C: Modem4/ModemIIIa² Messages For lines that are grouped, Gxx appears instead of Lxx. The GV4 (v2.x.x and higher)/B5512/B4512 send 4-digit user and point numbers. Panels using Modem4 send 4-digit Point and User data.
Page 135
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix C: Modem4/Modem IIIa Table 98: Modem4/ModemIIIa² Messages Event Device/Mode Display/Explanation Comments Printer: dd/dd tt:tt Lxx ACC aaaa USER LEVEL SET User Level Set by User +++ACC aaaa CODE ID=ccc ID=iii D6500 Mode:...
Page 136
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix C: Modem4/Modem IIIa Table 98: Modem4/ModemIIIa² Messages Event Device/Mode Display/Explanation Comments Printer: dd/dd tt:tt Lxx ACC aaaa WALK TEST START Walk Test Start by User +++ACC aaaa INVISIBLE POINTS (Invisible Points) +++ACC aaaa...
Page 137
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix C: Modem4/Modem IIIa ZONEX and Comex Translation These items supply additional information related to Appendix C: Modem4/ModemIIIa Messages. Some of these numbered items are also referenced in the Comments section of Appendix C.
Page 138
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix C: Modem4/Modem IIIa Table 100: User ID to Comex Translation COMEX 001-005 0-13 601-608 14-21 701-708 22-29 801-808 30-37 B01-B08 38-45 C01-C08 46-53 D01-D08 54-61 E01-E08 62-69 F01-F08 70-249 2. When the D7112 is transmitting a test report in Modem II format, the area number is sent to the automation system if the output format is in SIA communications mode.
Page 139
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix C: Modem4/Modem IIIa 6. For the D7112, unless otherwise specified, Table 101 is the basis for the zone digit “z” and ID translation; however, actual IDs only go up to 25. Table 101:...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix E: Pulse Output Appendix E: Pulse Output Table 103 to Table 111 vary depending on the account number specified and the digit parameter programmed using the drop-down menus in Menu Item 3.1.7 Event 3/1 or 4/1 (Figure 27).
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix F: Format ID(by Message Type)–D6600 only Appendix F: Format ID (by Message Type) – D6600 Only If D6600 Menu Item 2.5.17 equals 1, the following outputs apply. Generic D6500 Byte Description Example...
Page 153
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix F: Format ID(by Message Type)–D6600 only Table 114 shows examples for each format that the receiver supports. If Menu Item 2.5.17 = 1, the following message type follows a specific format ID. If Menu Item 2.5.17 = 0, the output to automation follows the standard message type ID.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix G: SIA Report Codes Appendix G: ADT SIA Report Codes Table 117: ADT SIA Report Codes Description ADT SIA System Event System Reset Reset Memory AC Fail AC Restore AC Fail 4 hour...
Page 157
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix G: SIA Report Codes Description ADT SIA Burglary BA Burg Alarm BA PT Bypass BA Restore BA Trouble BA PT Unbypass Description ADT SIA Open/Close BA Auto Close BA Auto Close with Bypass – within Group...
Page 158
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix G: SIA Report Codes Description ADT SIA Panic Hold-Up Alarm Hold-Up Point Trouble (sensor trouble) Hold-Up Restore Hold-Up Point Bypass Hold-Up Point Unbypass Hostage Alarm (Duress) Hostage Restore Medical Alarm Medical Restore...
Page 159
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix G: SIA Report Codes Description ADT SIA Change Early Open Change Holiday Change Latest Close (sent to CMC only if Closing sched is altered) Change Open Time, schedule change Change Time, time/date reset...
Page 160
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix G: SIA Report Codes Description ADT SIA Point Restore, general alarm restore Untyped Diagnostics BA Weak Battery FA Weak Battery HA Weak Battery SA Weak Battery UA Weak Battery Description ADT SIA...
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix I: SafeCom Messages (D6600 Only) Appendix I: SafeCom Messages (D6600 Only) In D6500 Mode, the line number sent to the computer is only one digit. Refer to Table 119. If Virtual Line is 00, it is disabled. The D6600 reports the actual D6600 line card number.
Page 170
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix I: SafeCom Messages (D6600 Only) Table 120: SafeCom Messages - Line Card or Account Signals Event Device/ Display Notes on Auto Mode Output System Startup hprrl00000100t 6500 <header>[#0000|0100] Printer dd/dd tt:tt Sxx SYSTEM STARTUP...
Page 175
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix I: SafeCom Messages (D6600 Only) Modem II - PID 6500 hprrlaaaa0322ezzzt 0x72, Expanded, <header>[#aaaa|0322ezxx] without Status Printer dd/dd tt:tt Sxx aaa>(aaaa) e zzz Report >>>>>>>>>>>>>>> aaa>XXXXXXXX Modem II - PID 6500 hprrlaaaa0322ezzzt 0x72, Expanded, <header>[#aaaa|0322ezzz]...
Page 176
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix I: SafeCom Messages (D6600 Only) Table 122: Explanation of Automation Output Items (within Message Body only) Character Meaning Radio account number (in hex), range: 001 to 9C4. Input number, range: 1 to 8.
Page 177
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix I: SafeCom Messages (D6600 Only) Table 124: Explanation of Printer Output Items (continued) Character Meaning Event code. eeee eeee Event codes for Zone 1 thru 8 (Ademco 4-9 High Speed only). Type code.
Page 178
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix I: SafeCom Messages (D6600 Only) Modem IIe Format DD/MM HH:MM:SS NNN > (DDDD) AA EE ZZZ Modem IIe messages are reported as AA EE ZZZ where AA is the area code, EE is the event code from Table , and ZZZ is the zone or user code.
Page 179
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | Appendix I: SafeCom Messages (D6600 Only) Table 125: Supported Event Codes (continued) Code Meaning Code Meaning Fail to open. Reboot Fail to close. Parameter checksum failure. Area watch by user ZZZ. Force perimeter instant by user ZZZ.
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | J: Acknowledgement from Automation Software to D6600/D6100i Receiver Appendix J: Acknowledgement from Automation Software to D6600/D6100IPv6 Receiver If a response other than a valid ACK or NAK is received, the receiver will transmit the last message again.
This CRC calculation section is referenced from the SIA DC-07 Computer Interface Standard. The calculations for CRCs to the Bosch receivers are performed in the same manner. CRCs are based on treating bit strings as representations of polynomials with coefficients of 0 and 1 only.
Automation Information The Bosch receivers send events over the network using UDP/IP to the IP Address of the PC that the automation software is running on and the port # that the automation is listening for the receiver on.