Warning: by Mitsubishi Electric are used, fire or explosion may result. • Ask the dealer or an authorized technician to install the air • To dispose of this product, consult your dealer.
Page 4
SAFETY PRECAUTIONS Warning: 2. Precautions for devices that use • Note the following when building a heater in the air R410A refrigerant conditioning system. - Leave enough space between units for proper ventilation so that Caution: the indoor unit temperature does not exceed 40°C when windless. •...
PART NAMES AND FUNCTIONS-Indoor (Main) Unit 2. PART NAMES AND FUNCTIONS 2-1. Indoor (Main) Unit Air outlet Air inlet 2-2. Remote controller ■ PAR-21MAA Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button. <1>...
Page 7
PART NAMES AND FUNCTIONS-Remote controller <2> Display CENTRALLY CONTROLLED 1Hr. ON OFF CLOCK CHECK FILTER CHECK MODE TEST RUN STAND BY ERROR CODE FUNCTION NOT AVAILABLE DEFROST TEMP. ON/OFF I H J Current time/Timer Centralized control Timer OFF Timer indicator Operation mode: COOL, DRY,...
REFRIGERANT SYSTEM DIAGRAM 6. REFRIGERANT SYSTEM DIAGRAM Gas pipe thermistor TH23 Gas pipe Liquid pipe thermistor TH22 Brazed connection Heat exchanger Linear expansion valve Built-in strainers (#100-mesh and #50-mesh) Strainer (#100-mesh) Room temperature thermistor TH21 mm <in.> Capacity PEFY-P15,18NMHU-E2 PEFY-P24,27,30NMHU-E2 PEFY-P36,48,54NMHU-E2 Item Gas pipe...
TROUBLESHOOTING-How to check the parts 7. TROUBLESHOOTING 7-1. How to check the parts Parts name Check points Room temperature Disconnect the connector, then measure the resistance using a tester. thermistor (TH21) (Sorrounding temperature 10°C~30°C [50°F~86°F]) Liquid pipe thermistor Normal Abnormal (Refer to the <Thermistor characteristic (TH22) 4.3kΩ~9.6kΩ...
TROUBLESHOOTING-Setting of address switch 7-2. Setting of address switch Make sure that power source is turning off. Indoor unit control board S W 4 S W 2 S W 3 < At delivery (All models)> S W1 S W 4 9 10 0 1 2 3 4 5 6 7 8 9...
TROUBLESHOOTING-Setting of Dip-switch (at delivery) 7-3. Setting of Dip-switch (at delivery) Models Dip-SW S W2 S W4 S W7 PEFY-P15 220V NMHU-E2 240V 9 10 9 10 S W2 S W4 S W7 PEFY-P18 220V NMHU-E2 240V 9 10 9 10 S W2 S W4 S W7...
TROUBLESHOOTING-Function the LED of the indoor unit service board 7-5. Function the LED of the indoor unit service board Symbol LED operation under normal state LED1 At applying main power source Lighting LED2 At receiving MA transmission power source Lighting HWE1212A...
DISASSEMBLY PROCEDURE-Service panel 8. DISASSEMBLY PROCEDURE 8-1. Service panel Procedures Explanatory figure 1. Removing the service panel 1 (Figure 1-1) (1) Remove the four service panel 1 mounting screws. 2. Removing the service panels 2 and 3 (Figure 1-2) (1) Remove the five service panel 3 mounting screws. (2) Remove the two service panel 2 mounting screws.
DISASSEMBLY PROCEDURE-Control box 8-2. Control box Procedures Explanatory figure 1. Removing the control cover (Figure 2-1) (1) Remove the two control box cover mounting screws. (2) Remove the two terminal block cover mounting screws. * The above procedures will allow for the following services to be performed.
Page 19
DISASSEMBLY PROCEDURE-Control box Procedures Explanatory figure 2. Removing the control box (Figure 2-2) (1) Disconnect the wiring from the control board and the relay connectors. LEV1 wiring CN60•6P•White Relay connector• Fan motor wiring 9P•White Indoor temperature thermistor CN20•2P•Red wiring Liquid pipe temperature thermistor CN21•2P•White wiring Gas pipe temperature thermistor...
DISASSEMBLY PROCEDURE-Fan 8-3. Fan Procedures Explanatory figure 1. Remove the control box and its cover according to the procedures detailed in section 8-2. Control box (page18). 2. Removing the fan P45-71 models (Figures 3-1 and 3-2) (1) Remove the four motor base mounting screws. (2) Loosen the three bellmouth mounting screws, and remove the bellmouth.
DISASSEMBLY PROCEDURE-LEV•Pipe thermistor 8-4. LEV•Pipe thermistor Procedures Explanatory figure 1. Remove the service panel according to the procedures detailed in section 8-1. Service panel (page17). Drive motor 2. Remove the control box cover according to the procedures detailed in section 8-2. Control box Valving element (page18).
DISASSEMBLY PROCEDURE-Drain pump•Drain sensor 8-5. Drain pump•Drain sensor Procedures Explanatory figure 1. Remove the service panels 2 and 3 according to the procedures detailed in section 8-1. Service panel (page17). 2. Remove the control box cover according to the procedures detailed in section 8-2. Control box (page18).
DISASSEMBLY PROCEDURE-Drain pan 8-6. Drain pan Procedures Explanatory figure 1. Remove the cap from the service panel 3 , and check the drain pan for water. Drain water from the drain port if there is any. Drain pan *Protect the surroundings with a plastic sheet before draining water.
DISASSEMBLY PROCEDURE-Heat exchanger 8-7. Heat exchanger Procedures Explanatory figure 1. Remove the LEV and pipe sensor wiring according to the procedures detailed in section 8-4. LEV•Pipe thermistor (page21). 2. Remove the drain pump according to the procedures detailed in section 8-5. Drain pump•Drain sensor (page22).