1. Safety Precautions • Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. • Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. •...
Page 4
WARNING Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when refrigerant contacts with fire. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury. Must not use other parts except original parts described in catalog and manual. Using of refrigerant other than the specified type may cause product damage, burst and injury etc.
2. Specification Indoor CS-A9PKD CS-A12PKD Model Outdoor CU-A9PKD CU-A12PKD Performance Test Condition NEW JIS NEW JIS Phase, Hz Single, 50 Single, 50 Power Supply 2.65 2.65 3.52 3.54 Capacity BTU/h 9040 9040 12000 12100 kcal/h 2280 2280 3030 3040 Running Current Input Power 1.08k...
Page 7
Indoor CS-A18PKD CS-A24PKD Model Outdoor CU-A18PKD CU-A24PKD Performance Test Condition NEW JIS NEW JIS Phase, Hz Single, 50 Single, 50 Power Supply 5.30 5.30 7.03 7.03 Capacity BTU/h 18100 18100 24000 24000 kJ/h 19100 19100 25300 25300 Running Current 12.3 12.2 Input Power 1.72k...
3. Features • Air Purifying System with nanoe-G Deactivates and removes bacterial, viruses and mould. • Long Installation Piping CS/CU-A9PK, long piping up to 10 meters. CS/CU-A12PK, long piping up to 15 meters. CS/CU-A18PK, CS/CU-A24PK, long piping up to 25 meters. CS/CU-A28PK, long piping up to 30 meters.
8. Wiring Connection Diagram CS-A9PKD CU-A9PKD Resistance of Indoor Fan Motor Windings Resistance of Compressor Windings MODEL CS-A9PKD MODEL CU-A9PKD CONNECTION CWA921447 CONNECTION 2PS156D3DA02 BLUE-YELLOW 336Ω 4.228Ω YELLOW-RED 306Ω 3.841Ω Note: Resistance at 25°C of ambient temperature. Note: Resistance at 20°C of ambient temperature. Resistance of Outdoor Fan Motor Windings MODEL CU-A9PKD...
CS-A12PKD CU-A12PKD Resistance of Indoor Fan Motor Windings Resistance of Compressor Windings MODEL CS-A12PKD MODEL CU-A12PKD CONNECTION CWA921447 CONNECTION 2PS206D3DA06 BLUE-YELLOW 336Ω 3.252Ω YELLOW-RED 306Ω 4.313Ω Note: Resistance at 25°C of ambient temperature. Note: Resistance at 20°C of ambient temperature.
CS-A18PKD CU-A18PKD CS-A24PKD CU-A24PKD Resistance of Outdoor Fan Motor Windings Resistance of Compressor Windings MODEL CU-A18PKD / CU-A24PKD MODEL CU-A18PKD CU-A24PKD CONNECTION CWA951385J CONNECTION 2JS318D3AA04 2JS438D3CC04 BLUE-YELLOW 93Ω 1.618Ω 1.121Ω YELLOW-ORANGE 124Ω 3.718Ω 2.535Ω YELLOW-RED 98Ω Note: Resistance at 20°C of ambient temperature. Note: Resistance at 25°C of ambient temperature.
CS-A28PKD CU-A28PKD Resistance of Outdoor Fan Motor Windings Resistance of Compressor Windings MODEL CU-A28PKD MODEL CU-A28PKD CONNECTION CWA951294J CONNECTION 2JD514E3AA03 BLUE-YELLOW 102Ω 1.022Ω YELLOW-ORANGE 81Ω 2.142Ω YELLOW-RED 108Ω Note: Resistance at 20°C of ambient temperature. Note: Resistance at 25°C of ambient temperature.
11. Installation Instruction 11.1 Select the Best Location 11.1.3 Indoor/Outdoor Unit Installation Diagram 11.1.1 Indoor Unit • Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. • There should not be any heat source or steam near the unit.
11.2 Indoor Unit 11.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent if from the vibration. Dimension Model ○ ○ ○ ○ ○ ○ A9***, A12 *** 490 mm 82 mm 439 mm 432 mm 93 mm 145 mm...
Page 37
11.2.3 Indoor Unit Installation 11.2.3.1 For the right rear piping 11.2.3.2 For the right and right bottom piping 11.2.3.3 For the embedded piping (This can be used for left rear piping and bottom piping also.)
Page 38
11.2.4 Connect the Cable to the Indoor Unit The power supply cord, indoor and outdoor unit connection cable can be connected without removing the front grille. Install the indoor unit on the installing holder that mounted on the wall. Open the front panel and grille door by loosening the screw. Cable connection to the power supply through Isolating Devices (Disconnecting means).
Page 39
Remove the tapes and connect the power supply cord and connection cable between indoor unit and outdoor unit according to the diagram below. Secure the power supply cord and connection cable onto the control board with the holder. Close grille door by tighten with screw and close the front panel. Note: •...
Page 40
11.2.5 Wire Stripping And Connecting Requirement...
11.3 Outdoor Unit 11.3.1 Install the Outdoor Unit • After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.
Page 42
11.3.3 Evacuation of the Equipment Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve. Be sure to connect the end of the charging hose with the push pin to the service port. Connect the center hose of the charging set to a vacuum pump.
Page 43
11.3.4 Connect the cable to the Outdoor Unit Remove the control board cover from the unit by loosening the screw. Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5 × 1.5mm (1.0 ~ 1.5HP) or 5 × 2.5mm (2.0 ~ 2.5HP) flexible cord, type designation 60245 IEC 57 or heavier cord.
12. Installation Instruction (CS-A28PKD CU-A28PKD only) 12.1 Select the Best Location 12.1.3 Indoor/Outdoor Unit Installation Diagram 12.1.1 Indoor Unit • Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. • There should not be any heat source or steam near the unit.
12.2 Indoor Unit 12.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent if from the vibration. Dimension Model ○ ○ ○ ○ ○ ○ A28*** 590 mm 82 mm 539 mm 532 mm 169 mm 219 mm The center of installation plate should be at more than...
Page 46
12.2.3 Indoor Unit Installation 12.2.3.1 For the right rear piping 12.2.3.2 For the right and right bottom piping 12.2.3.3 For the embedded piping (This can be used for left rear piping and bottom piping also.)
Page 47
12.2.4 Connect the Cable to the Indoor Unit The inside and outside connection cable can be connected without removing the front grille. Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 6 × 1.5 mm flexible cord, type designation 60245 IEC 57 or heavier cord.
Page 48
12.2.5 Wire Stripping And Connecting Requirement...
12.3 Outdoor Unit 12.3.1 Install the Outdoor Unit • After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.
Page 50
12.3.3 Evacuation of the Equipment Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve. Be sure to connect the end of the charging hose with the push pin to the service port. Connect the center hose of the charging set to a vacuum pump.
Page 51
12.3.4 Connect the cable to the Outdoor Unit Remove the control board cover from the unit by loosening the screw. Cable connection to the power supply through Isolating Devices (Disconnecting means). Connect the approved polychloroprene sheathed power supply cord 3 × 4.0 mm type designation 60245 IEC 57 or heavier cord to the terminal board, and connect the others end of the cable to Isolating Devices (Disconnecting means).
13. Operation Control 13.1 Heating Operation • Heating operation can be set using remote control. • This operation is applied to warm the room temperature reaches the setting temperature set on the remote control. • The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C.
Page 53
13.1.1 Heating Operation Time Diagram (For CS-A9PK CU-A9PK and CS-A12PK CU-A12PK) 13.1.2 Heating Operation Time Diagram (For CS-A18PK CU-A18PK, CS-A24PK CU-A24PK and CS-A28PK CU-A28PK)
13.2 Cooling Operation • Cooling operation can be set using remote control. • This operation is applied to cool down the room temperature to the setting temperature set on the remote control. • The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C.
Page 55
13.2.2 Cooling Operation Time Diagram (For CS-A18PK CU-A18PK, CS-A24PK CU-A24PK and CS-A28PK CU-A28PK)
13.3 Soft Dry Operation • Soft Dry operation can be set using remote control. • Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room. • This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control.
Page 57
13.3.2 Soft Dry Operation Time Diagram (For CS-A18PK CU-A18PK, CS-A24PK CU-A24PK and CS-A28PK CU-A28PK)
13.4 Automatic Operation • Automatic operation can be set using remote control. • This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature. • After judged the temperature, the operation mode is determined by referring to the below standard. Cooling Operation ↑...
JX03 at indoor unit’s printed circuit board. 13.5 Indoor Fan Speed Control • Indoor fan speed can be set using remote control. 13.5.1 Fan Speed Rotation Chart Fan Speed (rpm) CS-A9PKD CS-A12PKD 1060 1100 1020 1080 SSLo QSHi 1030...
Page 60
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table. Fan speed rotates in the range of Hi, Me and Lo-. Deodorizing Control will be activated. For CS-A9PKD and CS-A12PKD Speed Mode SSLo Stop...
Page 61
For CS-A18PKD, CS-A24PKD and CS-A28PKD Speed Mode SSLo Stop Manual Normal Auto Manual Powerful Auto Manual Normal Auto Manual Normal Auto Manual Powerful Auto Auto Mode Judgment Manual Quiet Auto Manual Quiet Auto Manual Quiet -170 Auto -170...
Page 62
• Auto Fan Speed during cooling operation: Indoor fan will rotate alternately between off and on as shown in below diagram. At the beginning of each compressor starts operation, indoor fan speed increases gradually for deodorizing purpose. For the first time the compressor operates, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the start of compressor.
• Auto Fan Speed during Heating operation. Indoor fan will rotate in the range of SLo → Me according to the heat exchanger temperature. (For A18PKD, A24PKD and A28PKD) (For A9PKD and A12PKD) 13.5.3 Manual Fan Speed Control • Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control. •...
13.7 Vertical Airflow Direction Control 13.7.1 Auto Control (Cooling and Soft Dry Operation Condition) • When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as shown in the diagram. • When stops operation using the remote control, the discharge vent is reset and stops at the closing position.
Page 65
For CS-A18PK, CS-A24PK and CS-A28PK Horizontal Upper limit/5° Closing position 40° / 140° Lower limit for heating mode/45° 13.7.2 Manual Control • When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow direction louver move up and down in the range shown in the diagram.
For CS-A18PK, CS-A24PK and CS-A28PK Horizontal Upper limit for heating mode 5° Closing position 15° / 140° 25° 35° 45° Lower limit for heating mode 13.8 Horizontal Airflow Direction Control 13.8.1 Auto Control • When the horizontal airflow direction is set to Auto using the remote control, the vanes swings left and right as shown in the diagram.
13.8.2 Manual Control • When the horizontal airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow direction vane move left and right in the range shown in the diagram. • The louver can be adjusted by pressing the button to the desired vane position. •...
Page 68
(Heating Operation condition) • When Powerful operation is set, the setting temperature will be automatically increased 3°C against the present setting temperature (Higher temperature: 30°C). • The Fan Speed will shift as shown below: • Vertical Airflow Direction:- o In “Manual” setting, the vane will automatically shift down 5° lower than previous setting. o In “Auto”...
13.10 Quiet Operation (For Cooling Operation or cooling region of Soft Dry Operation) • To provide quiet cooling operation condition. • Once the Quiet Operation is set at the remote control, the Quiet LED brightness will be dimmed. The sound level will reduce around 2dB(A) for Lo fan speed or 3dB(A) for Hi/Me fan speed against the present operation sound level.
Page 70
(Heating Operation condition) • When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates. The sound level will reduce either around 2 dB (Lo) or 3 dB (Hi, Me), against the present sound level operation. • Quiet setting of fan speed rpm refer to Indoor Fan Speed Control.
13.11 Timer Control 13.11.1 ON Timer • When the ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so that the room will reach nearly to the set temperature by the set time. •...
13.14 nanoe-G operation • This operation provides clean air by producing great amount of negative ions and distribute through the discharge airflow to capture or deactivate molds, bacteria or viruses. • nanoe-G operation start condition During unit running at any operation mode, if nanoe-G operation is activated, combination operation (operation mode + nanoe-G operation) starts.
Page 73
• nanoe-G check mode To enable nanoe-G check mode, during nanoe-G operation ON: If there is abnormal discharge, nanoe-G indicator blinks immediately. • Error detection control When nanoe-G indicator blinks, it indicates error listed below: Nanoe-G connector at main PCB open Judgment method •...
Error reset method • Press OFF/ON button to OFF the operation. • Press AUTO OFF/ON button at indoor unit to OFF the operation. • OFF Timer activates. • Power supply reset. nanoe-G breakdown error Judgment method • Hi-feedback voltage (at microcontroller) supplied to the nanoe-G system when nanoe-G operation is OFF;...
13.16 AUTO COMFORT and ECONAVI Operation • AUTO COMFORT start condition: When AUTO COMFORT button is pressed. • AUTO COMFORT stop conditions: When AUTO COMFORT button is pressed again. When unit is OFF by OFF/ON button. When unit is OFF when OFF TIMER activates. When unit is OFF by AUTO OFF/ON button at indoor unit.
Page 76
13.16.1.1 Signal Detection • Human Activity sensor will turns on according to infrared sensors signal detection. Signal detection Possible detected human Human Activity Indicator position area Sensor 1 Sensor 2 Left Center Right ■ ■ □ □ ■ ■ ■ □...
Page 77
13.16.1.7 Setting Position Judgment • According to installation position when there is only one activity area detected, the horizontal airflow direction louver position is fixed according to chart below: Horizontal airflow direction louver position Target area Left installation Center installation Right installation •...
Page 78
13.16.1.9 ECONAVI Demo Mode • To enable ECO DEMO mode, during unit is OFF (power standby): • To disable ECO Demo MODE: Transmit ECO Demo signal again. • Operation details Infrared sensor Human Activity Sensor Vane position Fan speed Sensor 1 Sensor 2 Left Center...
Page 79
13.16.1.10 Human Activity Sensor Abnormality • Abnormality detection: Connector disconnection / Wire cut abnormality Sensor judge Hi level continuously for 25 seconds Circuit abnormality 70 seconds after power ON, if human activity sensor judge Lo level continuously for 25 seconds •...
Page 80
13.16.2 Sunlight Sensor • During ECONAVI operation, the sunlight sensor detects sunlight intensity coming through windows and differentiates between sunny and cloudy or night to further optimize energy saving by adjusting the temperature. • Sunlight judgment is as following 13.16.2.1 Sunlight Intensity Reset •...
Page 81
13.16.2.3 Judge Ambient Condition • According to sunlight intensity over a period of time, the system will analyze the ambient condition is sunny, cloudy or night. 13.16.2.4 Temperature Shift • In a room without window or with thick curtain, the sunlight sensor will judge as cloudy/night. 13.16.2.5 Sunlight Sensor Check Mode •...
Page 82
13.16.2.6 Sunlight Sensor Abnormality • Abnormality detection: When ECONAVI is ON, if the sunlight intensity value below minimum level continuously for 24 hours, the sunlight sensor disconnection error counter will increase by 1 time. If the ECONAVI is OFF, the 24 hours timer will be reset, but the sunlight sensor disconnection error counter will not be reset.
14. Protection Control (For A9/12PK) 14.1 Restart Control (Time Delay Safety Control) • When the thermo-off temperature (temperature which compressor stops to operate) is reached during: - Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation. Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
14.6 Compressor Reverse Rotation Protection Control • If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor heat exchanger is 2.5°C (cooling mode)/5°C (heating mode) or less for continuous 2 minutes, compressor will stop and restart automatically.
14.10 4-Way Valve Control • 4-way valve always on during Heating operation. (except deicing operation) • When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating position for 5 minutes. • This is to prevent the refrigerant flow process sound for being occur. 14.11 Outdoor Fan Motor Control •...
14.14 Deice Control Deice starts to prevent frosting at outdoor heat exchanger. • Normal Deice Deice operations detection commences after 30 minutes of Heating operation starts or 60 minutes after previous deice operation. If the TRS (Thermal Reed Switch) senses the outdoor piping temperature drops to -3°C (TRS CLOSE) or less for 50 sec.
Page 87
Normal Deice Time Diagram Overload Deice Time Diagram...
(For A18/24/28PK) 14.15 Restart Control (Time Delay Safety Control) • When the thermo-off temperature (temperature which compressor stops to operate) is reached during:- Cooling / Heating operation - the compressor stops for 3 minutes (minimum) before resume operation. Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation. •...
14.20 Compressor Reverse Rotation Protection Control • If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor heat exchanger is 2.5°C (cooling mode)/5°C (heating mode) or less for continuous 2 minutes, compressor will stop and restart automatically.
14.22 Overload Protection Control • Outdoor Fan Control If the temperature of the Outdoor Heat Exchanger less than -3°C, Outdoor Fan is ON. The Outdoor Fan stop, when Outdoor Heat Exchanger temperature is Tb or more according to Outdoor Air Temperature region as table below: The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C.
14.25 Cold Draft Prevention Control 14.26 Deice Control Deice starts to prevent frosting at outdoor heat exchanger. • Normal Deice Deice operation detection commences in Heating operation starts or 60 minutes after previous deice operation. If the outdoor piping temperature drops to -4°C for 50 sec. continuously during compressor is in operation, deice will start.
Page 92
a) Normal Deice Time Diagram b) Overload Deice Time Diagram...
15. Servicing Mode 15.1 Auto OFF/ON Button Auto OFF/ON Auto OFF/ON Auto OFF/ON Button Pressed Button Pressed Button Pressed 5 sec 5 sec Auto Operation Test Run Operation Stop Various Setting Mode Stop (Forced Cooling Operation) “Beep” 2 x “Beep” AUTO OPERATION MODE The Auto Operation will be activated immediately once the Auto OFF/ON button is pressed.
15.2 Remote Control Button 15.2.1 SET Button • To check current remote control transmission code and store the transmission code to EEPROM: Press “Set” button continuously for 10 seconds by using pointer. Press “Timer Set” button until a “beep” sound is heard as confirmation of transmission code change. 15.2.2 RESET (RC) •...
16. Troubleshooting Guide 16.1 Refrigeration cycle system In order to diagnose malfunctions, make sure that there are no Normal Pressure and Outlet Air Temperature (Standard) electrical problems before inspecting the refrigeration cycle. Gas Pressure Outlet air Temperature Such problems include insufficient insulation, problem with the (kg/cm (°C) power source, malfunction of a compressor and a fan.
Page 96
16.1.1 Relationship between the condition of the air conditioner and pressure and electric current Cooling Mode Heating Mode Condition of the Electric current Electric current air conditioner Low Pressure High Pressure Low Pressure High Pressure during operation during operation Insufficient refrigerant (gas leakage) Clogged capillary tube or strainer...
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 17.1 CS-A9PKD CS-A12PKD 17.1.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 17.1.1.1...
WARNING High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 17.2 CS-A18PKD CS-A24PKD CS-A28PKD 17.2.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 17.2.1.1...
Page 102
17.2.1.3 To remove electronic controller Figure 13 Figure 14 Figure 15 17.2.1.4 To remove discharge grille Figure 16...
Page 103
17.2.1.5 To remove control board Figure 17 17.2.1.6 To remove cross flow fan and indoor fan motor Figure 18 Figure 19...
19. Exploded View and Replacement Parts List 19.1 Indoor Unit 19.1.1 CS-A9PKD CS-A12PKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 127
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-A9PKD CS-A12PKD REMARK CHASSIS COMPLETE CWD50C1653 ← FAN MOTOR CWA921447 ← CROSS FLOW FAN COMPLETE CWH02C1149 ← BEARING ASS’Y CWH64K007 ← SCREW - CROSS FLOW FAN CWH551146 ← ION GENERATOR CWH94C0043 ←...
Page 128
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-A9PKD CS-A12PKD REMARK CWG861497 ← SHOCK ABSORBER (LEFT) CWG713386 ← SHOCK ABSORBER (RIGHT) CWG713387 ← C.C.CASE CWG569049 CWG569050 INSTALLATION INSTRUCTION CWF615796 ← (Note) • All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
Page 129
19.1.2 CS-A18PKD CS-A24PKD CS-A28PKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 130
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-A18PKD CS-A24PKD CS-A28PKD REMARK CHASSIS COMPLETE CWD50C1654 ← ← FAN MOTOR ARW7671AC ARW7627AC ← CROSS FLOW FAN COMPLETE CWH02C1150 ← ← BEARING ASS’Y CWH64K007 ← ← SCREW - CROSS FLOW FAN CWH551146 ←...
19.2 Outdoor Unit 19.2.1 CU-A9PKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 133
19.2.2 CU-A12PKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 134
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-A9PKD CU-A12PKD REMARK CHASSIS ASSY CWD50K2112 CWD52K1308 SOUND PROOF MATERIAL CWG302255 CWG302110 FAN MOTOR BRACKET CWD541075 CWD541157 SCREW - FAN MOTOR BRACKET CWH551217 ← FAN MOTOR CWA951674 CWA951692 SCREW - FAN MOTOR MOUNT CWH55252J CWH55406J PROPELLER FAN ASSY...
Page 135
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-A9PKD CU-A12PKD REMARK C.C.CASE CWG568886 CWG568887 WIRE NET CWD041057A CWD041111A (Note) • All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). • “O” marked parts are recommended to be kept in stock.
Page 136
19.2.3 CU-A18PKD CU-A24PKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 137
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-A18PKD CU-A24PKD REMARK CHASSIS ASSY CWD52K1270 CWD50K2087 COMPRESSOR 2JS318D3AA04 2JS438D3CC04 ANTI - VIBRATION BUSHING CWH50055 ← NUT - COMPRESSOR MOUNT CWH561049 ← PACKING CWB81043 ← CONDENSER CWB32C3667 CWB32C2679 SOUND PROOF BOARD CWH151267 CWH151051 FAN MOTOR BRACKET CWD541154...
Page 138
19.2.4 CU-A28PKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 139
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-A28PKD REMARK CHASSIS ASSY CWD50K2087 COMPRESSOR 2JD514E3AA03 ANTI - VIBRATION BUSHING CWH50055 NUT - COMPRESSOR MOUNT CWH561049 PACKING CWB81043 CONDENSER CWB32C2681 SOUND PROOF BOARD CWH151056 FAN MOTOR BRACKET CWD541055 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR CWA951294J...
Page 140
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-A28PKD REMARK SHOCK ABSORBER (LEFT) CWG713124 C.C.CASE CWG568890 TUBE ASS’Y CWT025826 (Note) • All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). • “O” marked parts are recommended to be kept in stock. Printed in Malaysia SY0113-0...