Summary of Contents for LG LAU095HV

  • Page 1 This Owner's Manual is provided and hosted by Appliance Factory Parts. LAKEWOOD LAU095HV Owner's Manual Shop genuine replacement parts for LAKEWOOD LAU095HV Find Your LAKEWOOD Air Conditioner Parts - Select From 1 Models -------- Manual continues below --------...
  • Page 2 MODEL : General Wall Mounted-Inverter Type CAUTION Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel. - 101 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 3 4. Gas Charging (After Evacuation) ................39 5. Cycle Troubleshooting Guide ..................40 6. Electric Parts Troubleshooting Guide ...............41 7. Self-diagnosis Function .....................46 - 2 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 4 Part 1 General Information 1. Safety Precautions ......................4 2. Nomenclature........................7 - 3 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 5 Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug. There is risk of fire or electrical shock. - 4 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 6 Be sure to turn off power switch before connecting or disconnecting connector, or parts damage may be occur. - 5 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 7 Check the drainage of the indoor unit after the repair. If drainage is faulty the water may enter the room and wet floor. - 6 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 8 Nano Plasma F+4Way+(A/changeove)+A/clean+Oxygen generator 4way+(Nano)Plasma F+Negative ion+A/Clean+Oxygen generator Dry contact Basic + Low A Serial No. LG Model Development Serial No. - 7 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 9 1. List of Controls & Functions ..................9 2. Basic Mode Controls......................10 3. Special Mode Controls....................12 4. Utility Functions ......................13 5. Protection Functions & Controls .................16 - 8 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 10 Oil Equalizing Control To protect compressor NOTE: The Exploded View SVC Manual has the particular Function table for each model. - 9 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 11 • While in defrost control, the indoor and outdoor fans are turned off. • Compressor 2minutes delay - After compressor off, the compressor can restart minimum 2 minutes later. - 10 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 12 Heating thermo off +0.5°C(+1°F) Setting Temp. Cooling thermo off -0.5°C(-1°F) Switching point -2°C(-4°F) Cooling Cooling Mode Heating operation operation operation - 11 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 13 • In this operation, before we feel cold the set temperature and air volume is set automatically to save energy. - 12 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 14 Cooling CYCLE 30 Min 13 Min 60 Sec 120 Sec Comp. Comp. Indoor Fan Setting Step Indoor Fan Setting Step - 13 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 15 (Setting temp. -0.5˚C(-1˚F)) Sleep time ( hour ) NOTE: Some Models are different by swing width and swing pattern. - 14 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 16 - State of operation ON/OFF - Operation mode/setting temp./selected airflow speed - Sleep timer mode/remaining time of sleep timer - Chaos Swing - 15 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 17 Comp. Step 4 3˚C(37.4˚F) Comp. Step 2 Comp. off T1: 0 ~ 2°C(32~35.6°F) NOTE: Some Models are different by T1. - 16 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 18 Heater-on conditions : Outdoor temp. ≤ 0˚C (32˚F) and heating mode Heater-out conditions : Outdoor temp. > 1˚C (34˚F) - 17 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 19 Indoor Super low speed Start ° low speed Pre-Heat Deice STEP Model (kBtu/h) Compressor Frequency 65Hz(Step 5) 80Hz(Step 5) - 18 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 20 2) Outdoor piping temperature is below than –6°C (21.2°F, Option) for starting defrosting operation. Defrosting Comp. Freqency Model (kBtu/h) Defrosting Comp. Frequency 90Hz 77Hz 90Hz - 19 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 21 5) Hot Gas bypass valve/Oil separator bypass valve make OFF after 75 seconds from the time of 30Hz. NOTE: Comp.frequency and EEV pulse is different each models. - 20 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 22 3. When the frequency changes, the rotation speed of the compressor changes resulting in an changed refrigerant circu- lation. This leads to changeable amount of the heat exchange per unit. - 21 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 23 Fc-2 Fc-1 Fc-2 Free Freq. T on : 85°C(185°F) (Model by Model) T off : 95°C(203°F) (Model by Model) - 22 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 24 If the temperature reached Toff condition system will count 5 times after that and system will stop with error code. Heat Sink temp Toff=85°C(185°F) T2=75°C(167°F) T1=70°C(158°F) 5 Hz 5 Hz COMP frequency frequency frequency Down Down - 23 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 25 • If CT2 occurs 5 times within one hour, the appliance turn off and displays ERROR CODE 7. Model CT 1 CT 1 CT 2 (kBtu/h) (Cooling) (Heating) 7.5A 7.5A - 24 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 26 If CT2 occurs 5 times in 1 hour,stop the operation and shows Error Code 22 Model CT 1 CT 1 CT 2 (kBtu/h) (Cooling) (Heating) 15.5A - 25 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 27 -13 °C(8.6°CF) COMP Freq. Free Fc-1 Fc-2 Fc-2 Fc-1 Free Fh min T off : 110°C(230°F) T2 : 100°C(212°F) - 26 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 28 D-Pipe temp Toff(105)°C(221°F) T2(95)°C(203)°F T1(90)°C(194)°F 5 Hz 5 Hz COMP Down Down Expansion Stop control Pulse Up Pulse Up valve - 27 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 29 System will stop if this situation occurs 5 times in 1 hour and error code will be generated (Error Code 33). Toff(105)°C(221)°F D-Pipe temp T2(95)°C(203)°F T1(90)°C(194)°F COMP Step On-time On time Expansion Stop Pulse valve control control - 28 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 30 O/D fan Set speed Set speed Set speed Model T1 [˚C(˚F)] T2 [˚C(˚F)] 18kBtu/h 18(64) 24kBtu/h 16(61) 30kBtu/h 0(32) - 29 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 31 3) During this operation,if operating Hz couldn’t be changed by safety control ,stop this operation. Operating process : Raise the operating HZ up to 70,and after 20 sec.(option) recover to the last value. - 30 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 32 Part 3 Test Run 1. Check before Test Run....................32 2. Test Run Flow chart .......................33 3. Test Run Detail........................34 - 31 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 33 2.0 MΩ as a result of refrigerant accumulation in the internal compressor. If the insulation resistance is less than 2.0 MΩ, turn on the main power supply. - 32 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 34 Refer to Troubleshooting After Hot Start Guide Normal NOTE: When outdoor temperature is low,the unit is operated to Heating mode - 33 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 35 The pressure of the gas side Refrigerant TEMP. service valve. 35°C (95°F) 4~5kg/cm G(56.8~71.0 P.S.I.G.) R410A 35°C (95°F) 8.5~9.5kg/cm G(120~135 P.S.I.G.) - 34 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 36 4. Gas Charging (After Evacuation) .................39 5. Cycle Troubleshooting Guide..................40 6. Electronic Parts Troubleshooting Guide ..............41 7. Self-diagnosis Function....................46 - 35 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 37 Open Pressure check (with charging cylinder) Open Open (Servicing) Open Gas releasing (with charging cylinder) Open Open (Servicing) - 36 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 38 – Open the low-pressure valve on the charge set slightly to air purge from the charge hose. (5) Set the 2-way valve to the closed position. - 37 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 39 (4) Disconnect the charge hose from the vacuum pump. – Vacuum pump oil. If the vacuum pump oil becomes dirty or depleted, replenish as needed. - 38 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 40 1 minute and then repeat the procedure (pumping down-pin). - 39 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 41 When the room air humidity is relatively lower temperature difference is larger. - 40 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 42 Replace the P.C.B. 2) The output voltage of Power : 15V Module (SMPS) 3) IC01D(LD1085), IC04D(7805) : DC 5V - 41 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 43 : DC +5V Check point • Check the connecting circuit between MICOM PIN and CN-DISP1 PIN • Check receiver ass'y - 42 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 44 Check the electrical wiring diagram of Outdoor side. Check the open or short of connecting wires between Indoor and Outdoor. - 43 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 45 Check the electrical wiring diagram of Outdoor side. Check the open or short of connecting wires between Indoor and Outdoor. - 44 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 46 The voltage of Pin No 1(orange) and 3(black) of CN-FAN. About AC 160V over About AC 50V over SSR is not damaged Check SSR - 45 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 47 (BLDC fan model only) 3 sec 10 times 10 times • D-Pipe TH. is short or open. 3 sec (4 LED Model) - 46 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 48 8 times Discharge Pipe Temp. High (INV) 3 times 2 times Discharge Pipe Temp. High (Cons.) 3 times 3 times - 47 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 49 6 times 2 times Heat sink temp. high Heat sink sensor (open/ short) 6 times 5 times Open / Short - 48 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 50 R03H ~ R06H, C02H, C03H (air : about 10kΩ at 25°C(77°F), pipe : about 5kΩ at 25°C(77°F) - 49 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 51 9k,12kBtu/h Model Heat-sink Thermistor resistans check R-T Graph Ω 20 30 40 50 60 70 80 90 100110 120 130 Temperature[˚C] - 50 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 52 Check IC01K, IC02K,D01K~D03K, Install ground connection from outdoor ZD01K~ZD03K, R01K~R10K, unit. (In case power outlet has no earth port) C01K~C04K - 51 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 53 Assembling state of screw between INV-IC & ¡ normal : over 10MΩ Heat-sink DC 15V output of Power module. Ω - 52 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 54 (refer marking on pcb and component) - Spec of R01N (1kΩ), R02N (1.65kΩ) is correct - Direction of diode (D01N, D02N) is right - 53 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 55 (Soldering state & Direction) - remove obstacles in connected to outdoor pcb - R01F~R05F, C01F~C03F, outdoor unit assembly (CN-FAN2) Q01F~Q04F, ZD01F - 54 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 56 - Check soldering state of - Measure resistance of TH. in outdoor pcb assembly R07H, R08H, C04H (about 200kΩ at 25°C(77°F)). - 55 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 57 8. If the resistance of the sensor is 0 or 5VDC, then sensor is abnormal. ¡ Repair or Change the PCB. - 56 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 58 ¡ Check the another indoor unit. * CH05 is displayed at indoor unit, CH53 is displayed at out- door unit. - 57 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 59 5. Check the insulation from water at IPM part. ¡ Check the trace of water. 6. Check the IPM circuit. - 58 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 60 2. Check the fan operation is right. 3. Check the current. 4. Check the install condition. 5. Check the internal circuit. - 59 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 61 • Check the DC Link Voltage. Check Point 1. Check the power source. 2. Check the DC Link Voltage. - 60 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 62 2. Check the install condition for over load. (Trans1, B/Diode, Diode, Resistance) 3. Check the SVC V/V open. 4. Check the leakage of refrigerant. - 61 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 63 Check the connection of "U, V, W" Check the short check point "A" Check with the error code "21" - 62 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 64 1. If the resistance of the sensor is only , the check Is possible. 2 If the error occurs again after the reset , change the PCB. - 63 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 65 3. If the resistance of the sensor is 0 kΩ or ∞, then sensor is abnormal. Ω If the voltage of the sensor is 0 V or 5VDC, then sensor is abnormal. - 64 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 66 • Check the poor soldering. Check Point • CH 60 1. Check the insertion condition of EEPROM. 2. Check the poor soldering - 65 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 67 1. Check the install condition for over load. (Refrigerant, Pipe length, Blocked, …) 2. Check the Outdoor temp. is very high. - 66 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 68 JAN. 2008 P/NO : MFL41161601 - 100 - Copyright ©2008 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...