Summary of Contents for Samsung DVM-S AM080JXVHGH/ET
Page 1
Disassembly and Reassembly Repairs must be carreid out by trained professional. For any repairs, please contact our service provider or independent qualified professional. Parts Procedure Remark Electrical 1) You must cut-off the power before equipment Part you work-on 2) Remove 12 screws from the cabinet (Use + screw driver) AM080JXVHGH/ET, AM100JXVHGH/ET, AM120JXVHGH/ET, AM080JXVHGR/ET,...
Page 2
Parts Procedure Remark 3) Remove 8 screws from the cabinet (Use + screw driver) AM140JXVHGH/ET, AM160JXVHGH/ET, AM180JXVHGH/ET, AM200JXVHGH/ET, AM220JXVHGH/ET, AM140JXVHGR/ET, AM160JXVHGR/ET, AM180JXVHGR/ET, AM200JXVHGR/ET, AM220JXVHGR/ET, AM140JXVHGH/EU, AM160JXVHGH/EU, AM180JXVHGH/EU, AM200JXVHGH/EU, AM220JXVHGH/EU 4) Remove 4 screws and separate cover control box (Use + screw driver) 5) Power, Compressor, Valve, Motor, Sensor connector connected to ASSY PCB remove.
Page 3
Disassembly and Reassembly Parts Procedure Remark 6) 2 screws had fixed in terminal block cover when change power terminal block then, communication terminal block remove 7) 2 screws had fixed in terminal block after remove 4 screws had fixed to Cabinet for terminal block protection remove.
Page 4
Disassembly and Reassembly AM160FNBDEH/320FNBDEH/500FNBDEH Parts Procedure Remark CABINET TOP/ Carried out after shut off the power FRONT/BACK before disassembly. Remove the 4 screws from the left and right of the CABI TOP, and then separate it. 2) Remove the 2 screws from the ASSY CABI FRONT upper part and then separate the ASSY CABI FRONT upward after incline CABINET forward.
Page 5
Parts Procedure Remark Control BOX 4) Remove the 4 screws and then pull the COVER CONTROL to upward, and separate it. 5) Remove the 2 screws from the ASSY CONTROL BOX. 6) Separate the C/BOX from the product. CABINET LF/RH Remove the 4 screws from the BRACKET COND UP, and separate it.
Page 6
Disassembly and Reassembly Parts Procedure Remark CABINET LF/RH 8) Remove the 2 screws from the front and rear and then separate the ASSY CABI LF to side. 9) Remove the 2 screws from the ASSY CABI...
Page 7
Parts Procedure Remark ASSY PHE Remove the 8 screws from the side of the ASSY CABI RH.
Page 8
Disassembly and Reassembly AM160/250FNBFEB, AM160/250FNBFGB Parts Procedure Remark CABINET Stop the air conditioner operation and shut off the main power. Remove the 4 screws in CABI TOP left/right side and then separate it. 2) Remove the 2 screws in ASSY CABI FRONT upper part.
Page 9
Parts Procedure Remark CABINET 5) Remove the 2 screws and open the HINGE PBA PLATE. 6) Pull the SLIDE PBA and then separate the WIRE CONNECTOR. 7) Remove the 6 screws from the ASSY CONTROL BOX. 8) Remove the 4 screws from the BRACKET UPPER and separate it.
Page 10
Disassembly and Reassembly Parts Procedure Remark CABINET 9) Loosen the CONDUIT from ASSY CONTROL COOLER IN lower part and then separate the TEMP SENSOR. 10) Loosen the CONDUIT from ASSY CONTROL COOLER IN lower part and then separate the TEMP SENSOR. 11) Replace of REACTOR and FAN is available after remove the ASSY CABI LF.
Page 11
Parts Procedure Remark CABINET 12) When need CONDUIT control for temperature sensor : Remove the 4 screws in ASSY CONTROL COOLER side. PIPE When you need to replace parts, weld zone 8 places that should separate. ■ Replace the COMP ①...
Page 12
Disassembly and Reassembly Parts Procedure Remark PHE & COMP When separate the water piping and refrigerant nipple : Remove the M5 screws from the ASSY CABI SIDE LH. 2) When separate the water piping : Remove the QUICK FASTENER and then moved horizontally and separate it.
Page 13
Disassembly and Reassembly Repairs must be carreid out by trained professional. For any repairs, please contact our service provider or independent qualified professional. Fan / Motor disassembly and reassembly guide for DVM S outdoor unit (small/large chassis) Parts Procedure Remark 1) You must cut-off the power before you work-on 2) As shown in the right picture,...
Page 14
Parts Procedure Remark 3) After releasing the Boss bolt in the center of the fan, Lift up the fan and separate it. 4) After releasing 4 bolts for motor fastening, Lift the motor and separate it. ※ First, Motor wire should be separated from C/Box.