SYSTEM AIR CONDITIONER OUTDOOR UNIT AM036FXMDCH AM048FXMDCH AM053FXMDCH AIR CONDITIONER CONTENTS Product Specifications Disassembly and Reassembly Troubleshooting PCB Diagram Wiring Diagram Reference Sheet Check Operation & Amount of Refregent Automatically Checking Refer to the service manual in the GSPN(see the rear cover) for the more information.
Contents Product Specifications ............................................... 1. The Feature of Product 1-1 Featres ..................................................2. Product Specifications Disassembly and Reassembly ....................Troubleshooting ..........................1. Error Display ........................................................2. Error Code ..................3. How to take measures for each symptom 3-1 Communicaion error between indoor and outdoor units during tracking(Error Code:E201) ..
High efficient G-Fin & epoxy acrylic coating has increased heat transfer and hydrophilicity on heat exchanger. Company A Diameter Ø8 Ø7 Heat transfer surface area Pressure Evaporation 14.1% loss in heat Condensation exchanger 10.3% Internal heat transfer performance 30.8% Pressure resistance Same Company A Samsung Electronics...
Saturated liquid refrigerant Temperature Low temperature gas refrigerant Low temperature liquid refrigerant Cross section of the Cross section of the Sub-cooled conventional inter-cooler Turbo inter-cooler liquid refrigerant *Increased heat transfer area with Shell & Tube type Turbo Inter-cooler Samsung Electronics...
Page 5
Corrosion is evident after 1,000 hours of test Company A * Tested by Samsung Long piping/High level difference technology Longest piping length is allowed up to 175m (equivalent length) and Maximum 50m of level difference is allowed for more flexible installation.
Page 6
• Silent mode can be adjusted in 3 levels depending on the level of noise. Highest temperature 6 hours 12 hours of silent mode Operation time 7 : 00 13 : 30 19 : 00 7 : 00 Samsung Electronics...
Page 7
• Displaying 15 main data including high pressure of system - Outdoor temperature - Discharge temperature of the compressor - Condensing temperature • Using the DIP switch on the outdoor unit PCB, you can limit the running current of the system Samsung Electronics...
Page 8
Convenient product installation Service valve is not exposed to keep the neat appearance and pipe can be connected in 4 different directions which provide flexible installation and maintenance services. Conventional * For models with 9kW or larger (Flare type connection) Samsung Electronics...
Disassembly and Reassembly Necessary Tools Item Remark +Screw Driver Monkey Spanner –Screw Driver Nipper Electric Motion Driver L-Wrench Samsung Electronics...
Page 11
Cabinet Front RH. (Use + Screw Driver) Cabi Top 1) Unscrew and remove 9 screws on each side of the Cabinet-Top. (Use +Screw Driver) Cabi Install Front 1) Unscrew and remove 1 screw in the Cabinet-Install Front. (Use +Screw Driver) Samsung Electronics...
Page 12
2) Unscrew and remove 4 screws in the Guard Cond. (Use + Screw Driver) Cabi Back RH 1) Pull the sensor from Cabi Back RH. 2) Unscrew and remove 4 screws on each side of the Cabinet Back RH. (Use + Screw Driver) Samsung Electronics...
Page 13
Disassembly and Reassembly Parts Procedure Remark Cabi Install Back 1) Unscrew and remove 1 screw in the Cabinet-Install Back. (Use +Screw Driver) Cabi Front LF 1) Unscrew and remove 10 screws in the Cabinet-Front LF. (Use +Screw Driver) Samsung Electronics...
Page 14
Disassembly and Reassembly Parts Procedure Remark 1) Turn 2 mounting nuts as shown in the picture and remove it. (Use L Wrench or Monkey Spanner or Socket Wrench ) Samsung Electronics...
Page 15
1) Separate the Fan Propeller. 2) Unscrew and remove the 8 Motor mounting screws. (Use +Screw Driver) 3) Disconnect the Motor wire from Ass’y Control Out. Bracket Motor 1) Unscrew and remove 2 mounting screws in Bracket Motor. (Use + Screw Driver) Samsung Electronics...
Page 16
Disassembly and Reassembly Parts Procedure Remark Control Out 1) Disconnect 9 Connectors from Ass’y control Out. 2) Unscrew and remove 1 mounting screw in Control Out. (Use + Screw Driver.) 3) Separate Ass’y Control Out. Samsung Electronics...
Page 17
Ass'y Tube Suction 1) Separate 2 parts of the pipe using a welder. Ass'y Tube 4Way 1) Unscrew and remove 2 mounting screws in Oil Separator. (Use + Screw Driver.) 2) Separate 2 parts of the pipe using a welder. Samsung Electronics...
Page 18
1) Unscrew and remove 1 mounting nut in bottom of the cover. (Use Adjustable Wrench) 2) Separate the Compressor Felt. 3) As shown in the picture, unscrew and remove 3 mounting screws from the bottom. (Use L-Wrench or Monkey Spanner or Socket Wrench) Samsung Electronics...
Page 19
Disassembly and Reassembly Parts Procedure Remark Cond Out 1) Unscrew and remove 3 screws on each side of the Ass’y Cond Out. (Use + Screw Driver) Samsung Electronics...
Check the outdoor unit PCB communication each unit and replace the indoor unit PCB line and connector then replace the PCB. after checking out lines. Samsung Electronics...
Page 23
PCB then find an indoor unit that hampers communication by making a connection to each unit and replace indoor unit PCB after checking out lines. Good Defective 0.7V 0.7V Samsung Electronics...
Red-On, Green-On, Orange-Blinking and if the MAIN PBA connector (CN39) 7-segment on the outdoor unit main PBA does not display anything, change the main PBA Outdoor unit inverter PBA is normal [7-segment on FXMDCH series Main PBA (Common)] inverter PBA LED] Samsung Electronics...
Check if everything is normal and end service on temperature sensor similar to the values on the table on the right side? Change the outdoor unit PBA Turn on the power Check if everything is normal and end service Samsung Electronics...
On the high/low-pressure Refill refrigerant after vacuum sensor terminals of the PCB, is the value of voltage 5V, between pins 3 and 4? mark is the 1st pin on the PCB. Replace high/low-pressure sensor Samsung Electronics...
Check the relevant indoor fan Is the indoor EEV working properly? Check the relevant EEV Is the sensor on indoor heat exchanger shows the temperature correctly? Refer to temperature sensor error section to check for error Check for indoor air inlet blockage Samsung Electronics...
Do the values of S-net and Replace a high pressure sensor Manifold gauge correspond? Does indoor/outdoor EEV Check the relevant EEV operate well? Is there any clogged place Check the piping in the piping (ex. filter)? Check the amount of refrigerant Samsung Electronics...
(ex. filter)? Is there any leakage in liquid pipe valve or discharge check valve of the stop-side outdoor unit when Replace the relevant components several outdoor units are in operation? Check the amount of refrigerant Samsung Electronics...
S-net and Manifold gauge Replace a high pressure sensor correspond? Does indoor/outdoor EEV Check the relevant EEV operate well? Is there any Check the piping clogged place in the piping (ex. filter)? Check the amount of refrigerant Samsung Electronics...
3) If 3-phase power is normal check the phase of the power line using 3-phase tester. If it shows reverse phase, please change the current 3-phase tester power line connection. 4) After completing above, press reset key (K3) then check the power again. Samsung Electronics...
Check the leakage on sub-cooler Normal Change the sub-cooler Failure Check the leakage on indoor unit EEV Normal Change the indoor unit EEV Check the piping connection Connect liquid-gas pipe) Re-install the pipe Check the amount of refrigerant Samsung Electronics...
On the high-pressure sensor Replace the PCB of the PCB, is the value of voltage 5V, between pins 3 and 4? mark is the 1st pin on the PCB. Replace the high/low-pressure sensor Samsung Electronics...
Is high pressure sensor correctly connected to PCB? Check and reconnect the connector Is there leakage of refrigerant in the system or charging inferior? (Check with manifold gauge) Refill or recharge the refrigerant Replace the high pressure sensor Samsung Electronics...
* Do not change the outdoor unit PBA with fan motor problem If the 7-segment on the outdoor unit main PBA shows error, there is no problem with outdoor unit main PBA Control related problems can be solved by S/W update Samsung Electronics...
Do the values of S-net and Manifold gauge Replace a high pressure sensor correspond? Does indoor/outdoor EEV Check the relevant EEV operate well? Is there any clogged place Check the piping in the piping (ex. filter)? Check the amount of refrigerant Samsung Electronics...
3. Is there any noise when the 3. Change the compressor: When loud compressor rotates? abnormal noise generates (such as metal grinding), or severe vibration Is the resistance between Change the compressor compressor body and chassis MegaΩ? Cont. Samsung Electronics...
Page 38
It is Compressor, inverter PBA related error, therefore it is not related to above PBA * Make sure to check if service valve is open If the service valve is close, damage could occur due to pressure difference during operation Samsung Electronics...
2. Remove obstacles on air outlet and secure enough space Is the service valve completely open? Open the valve Is the compressor operating normally? Change the compressor Change the outdoor unit inverter PBA and check for normal operation End service Samsung Electronics...
1. Remove obstacles on air inlet and secure enough space Is the indoor unit installed correctly?? 2. Remove obstacles on air outlet and secure enough space Is piping/wiring between Re-install them correctly the indoor and outdoor unit done correctly? Cont. Samsung Electronics...
Page 41
Is the resistance between Change the compressor compressor body and chassis MegaΩ? Is the location and Turn off the power and change the location measured value of the of the temperature sensor or replace it temperature sensor normal? Cont. Samsung Electronics...
Page 42
End service Change the PCB FXMDCH series] * Do not change the EMI/outdoor unit main/ Indoor unit main PBA when E464 error occurs It is Compressor, inverter PBA related error, therefore it is not related to above PBA Samsung Electronics...
Check for outdoor unit inverter PBA normal? normal operation End service 2. Is there any problem on reactor coil? 2. Change the reactor Check for normal operation (such as scratch/pressed/ End service broken terminal/ loose terminal) FXMDCH series] Cont. Samsung Electronics...
Page 44
End service 2. Connect the terminal and the power cable in the power terminal cabinet Check for normal operation End service Change the outdoor unit inverter PBA and check for normal operation End service Samsung Electronics...
3. Is there any noise when 3. Change the compressor: When loud abnormal the compressor rotates? noise generates (such as metal grinding), or severe vibration Is the outdoor and indoor unit Install them correctly pipes/cables correctly installed? Cont. Samsung Electronics...
Page 46
Gas leak error (Error Code : E554) (cont.) Cont. Open the valve Is the service valve completely open? Is the EVA sensor correctly connected? Re-connect the sensor connector Charge the refrigerant Is the refrigerant charged? Is the refrigerant charged? Samsung Electronics...
When error occurs, turn on/off the power for number of time and if same error occurs while the power is off, change the inverter PBA 7. EEPROM read/write error: E470 Error occurs when there is no EEPROM data in the set. Check the model name and insert EEPROM for corresponding model or load the EEPROM data. Samsung Electronics...
Page 50
#2 : COMP. V-phase(BLU) #3 : GND #3 : GND #3 : COMP. U-phase(YEL) #4 : DC 15V #4 : DC 15V #5 : FAN RPM #5 : FAN RPM #6 : FAN RPM feedback #6 : FAN RPM feedback Samsung Electronics...
Page 51
PCB Diagram Outdoor Unit PCB (cont.) - EMI PCB : 1Phase L1-AC POWER L phase N1-AC POWER N phase CN01-AC POWER L1 : BRN N1 : SKY-BLU #1-#3 : AC 220~240V Samsung Electronics...
Wiring Diagram 1 Phase This Document can not be used without Samsung’s authorization. This Document can not be used without Samsung’s authorization. Samsung Electronics...
- Check the drainage of the Indoor Unit cooling operation. - More operation : Checking status by using the S-NET. (5) Refer to manual and explain air conditioner usage to user. (6) Deliver this installation guide so that customer retain. Samsung Electronics...
Page 56
- Oblique line marked area in the during operation of the system can be protection control. (Check operation of normal judgment can be difficult by the protection control operation.) - If out of warranty coverage and the boundary area : Check operation judgment accuracy may be reduced. Samsung Electronics...
Page 57
Is deviations of the Indoor Unit Temperature sensors, less than 10 ? Complete [Caution] - If the Outdoor Unit with a history of operation (Automatic commissioning inclusion) : Must be carried out Automatic Commissioning after 1 hour from final operation stopped. Samsung Electronics...
Page 58
Outdoor Unit Temperature sensors, less than 1 0 ? Complete [Caution] - If the Outdoor Unit with a history of operation (Automatic commissioning inclusion) : Must be carried out Automatic Commissioning after 1 hour from final operation stopped. Samsung Electronics...
Page 59
Max Replace PCB /Min deviation : less than 2" Complete [Caution] - If the Outdoor Unit with a history of operation (Automatic commissioning inclusion) : Maintain the vacuum mode for more than 5 minutes. Samsung Electronics...
Page 60
CT Replace Inverter PCB sensor have the same value ? Is refrigerant Is Compressor current(CT) value normal? in the system properly? Adjusts the refrigerant (Addition / Emitted) IIs operation current of Compressor normal? Replace Compressor Complete Samsung Electronics...
Page 61
1 8 . 3 2 . 5 9 . 2 0 0 . Adjusts the refrigerant Is refrigerant in the system properly ? 2 4 2 . (Addition / Emitted) 3 6 2 . 5 5 3 . Complete Samsung Electronics...
Page 62
Is 4Way Valve coil normal? Replace Valve coil (Wire breaking, operation impossible, etc.) Is PCB Output signal normal ? Replace PCB Replace 4Way Valve Body (Retry the Automatic Commissioning : If the continuous "Undetermined" is displayed. ) Complete Samsung Electronics...
Remark E503 Service Valve is closed Refer to "Service Valve" Dedicated Error Code E505 High pressure sensor breakdown Refer to "High/Low pressure sensor (Module installed)" E506 Low pressure sensor breakdown Other error codes : Refer to Service Manual. Samsung Electronics...
Deficiency of refrigerant amount : After the 5% addition of calculated total refrigerant amount, retry refrigerant detection operation. Undetermined : Refrigerant detection operation confirms that is performed in warranty temperatures area. Ensure that there is no other problems in the system by Commissioning. Samsung Electronics...