1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. Electrical work and water installation work must be installed or serviced by a licensed electrician and licensed water system installer respectively. Be sure to use the correct rating and main circuit for the model installed. The caution items stated here must be followed because these important contents are related to safety.
Page 4
19. This equipment is strongly recommended to be installed with Residual Current Device (RCD) on-site according to the respective national wiring rules or country-specific safety measures in terms of residual current. 20. The unit is only for use in a closed water system. Utilization in an open water system may lead to excessive corrosion of the water piping and risk of incubating bacteria colonies, particularly Legionella, in water.
Page 6
Item Unit Mono Bloc Unit Maximum Input Power For Mono Bloc Unit 4.48 Power Supply 1: Phase (ø) / Max. Current (A) / Max. Input Power (W) Single / 20.5 / 4.48k Power Supply 2: Phase (ø) / Max. Current (A) / Max. Input Power (W) Single / 26.0 / 6.00k Power Supply 3: Phase (ø) / Max.
WH-MDC09E3E5 Item Unit Refrigerant System Performance Test Condition EN 14511 Cooling Capacity Condition A35W7 (Ambient/Water) 7.00 BTU/h 23900 kcal/h 6020 2.44 kcal/hW 2.10 Heating Capacity Condition A7W35 A2W35 (Ambient/Water) 9.00 7.45 BTU/h 30700 25400 kcal/h 7740 6410 4.15 3.14 kcal/hW 3.57 2.70 Air Flow...
Page 8
Item Unit Mono Bloc Unit Maximum Input Power For Mono Bloc Unit 5.01 Power Supply 1: Phase (ø) / Max. Current (A) / Max. Input Power (W) Single / 22.9 / 5.01k Power Supply 2: Phase (ø) / Max. Current (A) / Max. Input Power (W) Single / 26.0 / 6.00k Power Supply 3: Phase (ø) / Max.
3. Features Inverter Technology - Energy saving High Efficiency Compact Design Environment Protection - Non-ozone depletion substances refrigerant (R410A) Easy to use remote control Weekly Timer setting Quality Improvement - Random auto restart after power failure for safety restart operation - Gas leakage protection - Prevent compressor reverse cycle - Inner protector to protect compressor...
11.1 Select the Best Location 11.2 Mono Bloc Unit Installation Mono bloc unit will become heavy when filled with Install the Mono bloc unit in outdoor locations only. water. Please install the unit on a strong concrete floor Avoid installations in areas where the ambient and consider the weight of the unit and water.
11.3 Piping Installation WARNING This section is for authorized and licensed electrician / water system installer only. Work behind the front plate secured by screws must only be carried out under supervision of qualified contractor, installation engineer or service person. Please engage a licensed water circuit installer to install this water circuit.
11.4 Connect The Cord And Cable To Mono Bloc Unit (REFER TO WIRING DIAGRAM AT UNIT FOR DETAIL) An isolating device must be connected to the power supply cable. Isolating device (Disconnecting means) should have minimum 3.0 mm contact gap. Connect the approved polychloroprene sheathed power supply 1 cord (3 x 4.0 or 6.0 mm ) and power supply 2 cord (3 x 4.0 mm...
Page 34
Three-way Valve shall be spring and electronic type, refer to “Field Supply Accessories” table for details. Valve cable shall be (3 x min 0.5 mm ), of type designation 60245 IEC 57 or heavier, or similarly double insulation sheathed cable. * note: - Shall be CE marking compliance component.
Page 35
11.4.2 Connecting Requirement The equipment’s power supply 1 complies with IEC/EN 61000-3-12 provided that the short-circuit power S greater than or equal to 868.69kW at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power S greater than or equal to 868.69kW.
Page 36
Outlet box may be purchased separately. case circuit board. (Refer to the illustration at Medium-sized square outlet box (obtain locally) below) Part No. DS3744 (Panasonic Co., Ltd.) or Secure the remote control upper case to the equivalent. Secure the remote control lower case to the lower case with the tabs provided.
Page 37
11.4.3.3 Connecting The Remote 11.4.3.4 Disposal of Mono Bloc Unit Control Cable To Mono Bloc Drain Water Unit When a Drain elbow is used, please ensure to follow below: CAUTION The unit should be placed on a stand which is Be sure to turn off the main power before installing and connecting taller than 50mm.
12. Operation and Control 12.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
Page 39
Cool Mode Operation Time Chart 12.1.4 Cool + Tank Mode Operation...
Page 40
12.1.5 Tank Mode Operation Control contents: 3 ways valve direction - 3 ways valve switch and fix to tank side. Heat pump Thermostat characteristic - Water set temperature = Tank set temperature or [51°C] whichever lower. - Heat pump Water Outlet set temperature is set to Maximum (53°C) at tank mode. i.
Page 43
12.1.6 Heat + Tank Mode Operation Setting 1: When Heating priority is set by control panel: 3 ways valve control: 3 ways valve switch to room side during External Room Thermo ON OR Solar 3 ways valve ON OR Tank Thermo OFF time, and switch to tank side at External Room Thermo OFF AND Solar 3 ways valve Heat pump operation control:- During External Room Thermo ON time: (When room thermo ON, heat pump must operate to room side)
Page 44
Switch back 3 ways valve to room side, Heat pump and water pump turn OFF, IF External Room Thermo ON back OR Under Solar Priority Set condition: Tank temperature > Tank THERMO OFF TEMP. for continuous 3 minutes OR Solar Valve Under Solar Priority Not Set condition: Tank temperature >...
Page 45
Solar 3 way valve: Solar 3 way valve operates follow solar operation specification. * Under solar priority is set condition, when solar 3WV turn ON, booster heater will turn OFF and 3 ways valve switch to room side. * Under solar priority is not set condition, solar 3WV will OFF when heat pump operate to tank side. 2 way valve opens.
Page 46
Setting 2: When heating priority is not set by remote control: When Solar Priority is set / not set by remote control: 3 ways valve control: 3 ways valve switch to room side during heating heat-up interval, and switch to tank side during tank heat-up interval.
Page 47
- Tank interval will end and start heating interval timer, IF When this condition happen at tank side before case 1 thermo-off. 3WV switch to room side compulsory and continue until complete room interval. Tank interval timer finish AND External Room Thermo ON OR Fulfill above Case 1 of thermo off condition.
Page 50
12.1.7 Setting Water Outlet Temperature for Heat Mode The set temperature define the parameters for the outdoor ambient temperature dependent operation of the unit. Where by the internal water setting temperature is determined automatically depending on the outdoor temperature. The colder outdoor temperatures will result in warmer water and vice versa. The user has the possibility to shift up or down the target water temperature by remote control setting.
12.1.9 Fan Motor Operation Fan motor is adjusted according to operation condition. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation. 12.2 Water Pump 12.2.1 Water Pump Control Once the indoor unit is ON, the water pump will be ON immediately and no error judgement for 9 minutes. However, during this 9 minutes operation, if there is any abnormality cause at outdoor or malfunction, the compressor should be OFF immediately and restart delay after 3 minutes.
12.3 Pump Down Operation Purpose Ensure the pump down operation when relocating or disposing of the unit. The pump down operation will extract all refrigerant from the piping into the mono bloc unit. Pump down operation control: Press the SERVICE S/W for continuous 5 secs to enter Service mode. In service mode, select Sr:01 and press SET S/W to start Pump Down operation.
12.6 Mono Bloc Unit Safety 12.6.1 Mono Bloc Unit Safety Control When water pump is ON, the system will start checking flow switch status (ON/OFF). If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds. If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal mode.
12.9 Back-Up Heater Control 12.9.1 Electric Heater Control Normal Heating Mode Heater On condition: a. Heater switch is ON b. After Heatpump thermo ON for [30] mins c. After water pump operate [9] mins d. Outdoor air temperature < Outdoor set temperature for heater e.
Booster heater Turn Off condition: Tank temperature > Tank set temperature + [0°C] for continuous 15 secs When BOOSTER HEATER DELAY TIMER start count after switch from heating heat-up interval to tank heat-up interval * DELAY TIMER can be set by remote control. 12.11 Base Pan Heater Control (Optional) To enable the base pan heater function, pin 3 of SW2 of water system PCB has to be switched from OFF to ON position.
12.13 Sterilization Mode Purpose: Boil tank temperature to customer set boiling temperature to operate sterilization. Control start condition: Tank connection set to YES by remote controller Sterilization function selection is YES Sterilization signal received from remote controller by timer. Control stop condition: After boiling timer completed.
2. Backup heater anti freeze control: Backup heater turns ON when ALL the below conditions are fulfilled: Water inlet/outlet temp. < 6°C Water pump circulation anti freeze control activated, and water pump ON for 4 minutes Backup heater turns OFF when ANY of the below conditions is fulfilled: Water inlet/outlet temp.
Page 58
Stop condition: Solar pump stops operating when: No power supply to unit OR There is NO operation request from solar pump station OR Tank hot water temp is above solar off upper limit temp [EEPROM 2 : 77]°C. Heat pump thermo ON and operate to tank side. (During operation ON and tank mode selected) Heat + Tank Mode (Heating Priority Not Set) (Solar Priority Set)
Page 59
(Solar Priority Not Set) Heat + Tank Mode (Heating Priority Set)
Page 60
Tank Mode (Solar Priority Set) (Solar Priority Not Set)
12.17 External Room Thermostat Control (Optional) Purpose: Better room temperature control to fulfill different temperature request by external room thermostat. Recommended external room thermostat: Maker Characteristic Siemen (REV200) Touch panel Siemen (RAA20) Analog Connection external room thermostat: Wire Connection and thermo characteristic of Siemen REV200: Setting L/L1 (H) Heat Thermo...
12.18 Two ways valve control Functionality of 2 ways valve: Use to allow hot water to floor heating panel or block cold water to floor heating panel. Control contents: When indoor running in heat mode, OPEN the 2 ways valve. When indoor running in cool mode, CLOSE the 2 ways valve.
13. Protection Control 13.1 Protection Control For All Operations 13.1.1 Time Delay Safety Control The compressor will not start for three minutes after stop of operation. 13.1.2 30 Seconds Forced Operation Once the compressor starts operation, it will not stop its operation for 30 seconds. However, it can be stopped using remote control.
13.1.6 Low Pressure Protection Control Purpose: To protect the system operation. Detection period: After compressor on for 5 minutes. Detection conditions: When detection of Tem above 30°C. Calculation of average evaporation temperature (Tem). Use outdoor piping temperature sensor. Tem use the value calculated for discharge temperature setting value. After detection: Compressor stops restart again after 3 mins.
13.1.10 Crank Case Heater Control Purpose: - For compressor protection during low outdoor ambient operation (during heating low temperature operation). Control content: a. Trigger heater START condition When the outdoor air temperature is 4°C or below, and discharge temperature is 12°C or below. b.
13.3 Protection Control for Cooling Operation 13.3.1 Outdoor Air Temperature Control The Compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below. This control will begin 1 minute after the compressor starts. Compressor frequency will adjust base on outdoor air temperature.
14. Servicing Mode 14.1 Test Run Fill up the Tank Unit with water. For details refer to Tank Unit installation instruction and operation instruction. Antifreeze agent must be added into water circuit to prevent freezing of water when outdoor ambient temperatures is low.
15. Maintenance Guide In order to ensure optimal performance of the unit, seasonal inspections on the unit, external filter and field wiring have to be carried out at regular intervals. This maintenance should be carried out by authorized dealer. Water pressure Water pressure should not lower than 0.05 MPa (with inspects the pressure gauge).
Page 69
Reset overload protector Overload Protector serves the safety purpose to prevent the water over heating. When the Overload Protector trip at high water temperature, take below steps to reset it. Take out OLP Cover. Use a test pen to push the centre button gently in order to reset the Overload protector. Fix the OLP Cover to the original fixing condition.
16. Troubleshooting Guide 16.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan.
16.2 Relationship Between The Condition Of The Mono Bloc Unit And Pressure And Electric Current Heating Mode Cooling Mode Condition of the Electric current Electric current Mono bloc Unit Low Pressure High Pressure Low Pressure High Pressure during operation during operation Water leakage or insufficient water flow rate in the system...
16.3 Breakdown Self Diagnosis Function 16.3.1 Self Diagnosis Function (Three Digits Alphanumeric Code) When abnormality occur during operation, the system will stop operation, and OFF/ON remote control LED will blink and error code will display on the remote control Timer display LCD. Even error code is reset by turning OFF power supply or by pressing ERROR RESET button, if the system abnormality is still un-repaired, system will again stop operation, and OFF/ON remote control LED will again blink.
16.4 Error Codes Table Diagnosis display Abnormality/Protection control Abnormality Judgement Primary location to verify No abnormality detected — — Indoor/Outdoor capacity unmatched 90s after power supply Indoor/outdoor connection wire Indoor/outdoor PCB Specification and combination table in catalogue Outdoor compressor temperature sensor Continue for 5 sec.
Page 74
Diagnosis display Abnormality/Protection control Abnormality Judgement Primary location to verify Outdoor heat exchanger temperature Continue for 5 sec. Outdoor heat exchanger temperature sensor abnormality sensor (defective or disconnected) Outdoor defrost sensor abnormality Continue for 5 sec. Outdoor defrost sensor (defective or disconnected) Indoor water outlet temperature sensor Continue for 5 sec.
16.5 Self-diagnosis Method 16.5.1 Connection Capability Rank Abnormality (H12) Malfunction Decision Conditions: During startup operation of cooling and heating, the capability rank of indoor checked by the outdoor is used to determine connection capability rank abnormality. Malfunction Caused: Wrong model interconnected. Wrong indoor unit or outdoor unit PCB (main) used.
Page 76
16.5.2 Compressor Tank Temperature Sensor Abnormality (H15) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the compressor tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 77
16.5.3 Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor refrigerant liquid temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
16.5.4 Compressor Low Pressure Protection (H42) Malfunction Decision Conditions: During operation of heating and after 5 minutes compressor ON, when outdoor pipe temperature below -29°C or above 26°C is detected by the outdoor pipe temperature sensor. Malfunction Caused: Dust accumulation on the outdoor unit heat exchanger. Air short circuit at outdoor unit.
Page 79
16.5.5 Water Flow Switch Abnormality (H62) Malfunction Decision Conditions: During operation of cooling and heating, the water flow detected by the indoor water flow switch is used to determine water flow error. Malfunction Caused: Faulty water pump. Water leak in system. Faulty connector connection.
Page 80
16.5.6 Outdoor High Pressure Abnormality (H64) Malfunction Decision Conditions: During operation of cooling and heating, when the outdoor high pressure sensor output signal is 0Vdc or 5Vdc. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 4 times in 20 minutes.
Page 81
16.5.7 Indoor Backup Heater OLP Abnormality (H70) Malfunction Decision Conditions: During operation of indoor backup heater, when no power supplies to indoor backup heater or OLP open circuit. Malfunction Caused: Faulty power supply connector connection. Faulty connector connection. Faulty indoor backup heater overload protector (OLP). Faulty indoor unit PCB (main).
Page 82
16.5.8 Tank Temperature Sensor Abnormality (H72) Malfunction Decision Conditions: When tank connection is set to ON, the temperatures detected by the tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 83
16.5.9 Indoor-Control Panel Communication Abnormality (H76) Malfunction Decision Conditions: During standby and operation of cooling and heating, indoor-remote control error occur. Malfunction Caused: Faulty connector connection. Faulty remote control. Faulty indoor unit PCB (main).
Page 84
16.5.10 Indoor/Outdoor Abnormal Communication (H90) Malfunction Decision Conditions: During operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused: Faulty outdoor unit PCB (main). Faulty indoor unit PCB (main). Indoor-outdoor signal transmission error due to wrong wiring.
Page 85
16.5.11 Tank Booster Heater OLP Abnormality (H91) Malfunction Decision Conditions: During operation of tank booster heater, and tank booster heater OLP open circuit. Malfunction Caused: Faulty connector connection. Faulty tank booster heater overload protector (OLP). Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 60 seconds.
Page 86
16.5.12 Unspecified Voltage between Indoor and Outdoor (H95) Malfunction Decision Conditions: The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused: Insufficient power supply. Faulty outdoor unit PCB (noise filter/main).
Page 87
16.5.13 Outdoor High Pressure Protection (H98) Malfunction Decision Conditions: During operation of heating, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 2/3 way closed.
Page 88
16.5.14 Indoor Freeze-up Protection (H99) Malfunction Decision Conditions: During anti-freezing control in cooling operation, when the indoor refrigerant liquid temperature < 0°C. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 2 way valve partially closed. Clogged expansion valve or strainer.
Page 89
16.5.15 Outdoor High Pressure Switch Activate (F12) Malfunction Decision Conditions: During operation of cooling and heating, when pressure 4.5MPa and above is detected by outdoor high pressure switch. Malfunction Caused: Dust accumulation on the outdoor unit heat exchanger. Air short circuit at outdoor unit. Faulty water pump.
Page 90
16.5.16 Compressor Rotation Failure (F14) Malfunction Decision Conditions: A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused: Compressor terminal disconnect. Faulty outdoor unit PCB (main). Faulty compressor. Abnormality Judgment: Continue 4 times in 20 minutes.
Page 91
16.5.17 Outdoor Fan Motor (DC Motor) Mechanism Locked (F15) Malfunction Decision Conditions: The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm). Malfunction Caused: Operation stop due to short circuit inside the fan motor winding.
Page 92
16.5.18 Input Over Current Detection (F16) Malfunction Decision Conditions: During operation of cooling and heating, when outdoor current above 27.9A is detected by the current transformer (CT) in the outdoor unit PCB. Malfunction Caused: Excessive refrigerant. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 20 minutes.
Page 93
16.5.19 Compressor Overheating (F20) Malfunction Decision Conditions: During operation of cooling and heating, when temperature above 112°C is detected by the compressor tank temperature sensor. Malfunction Caused: Faulty compressor tank temperature sensor. 2/3 way valve closed. Refrigerant shortage (refrigerant leakage). Clogged expansion valve or strainer.
Page 94
16.5.20 IPM Overheating (F22) Malfunction Decision Conditions: During operation of cooling and heating, when temperature 95°C is detected by the outdoor IPM temperature sensor. Malfunction Caused: Faulty outdoor unit fan motor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 30 minutes.
Page 95
16.5.21 Output Over Current Detection (F23) Malfunction Decision Conditions: During operation of cooling and heating, when outdoor DC current is above 40.1 ± 5.0A (for: UD07~09CE) OR 44.7 ± 5.0A (for: UD12~16CE) is detected by the IPM DC Peak sensing circuitry in the outdoor unit PCB (main). Malfunction Caused: Faulty outdoor unit PCB (main).
Page 96
16.5.22 Refrigeration Cycle Abnormality (F24) Malfunction Decision Conditions: During operation of cooling and heating, compressor frequency > Frated. During operation of cooling and heating, running current: 0.65A < I < 1.65A. During operation of cooling, indoor water inlet temperature - refrigerant liquid temperature < 5°C. During operation of heating, indoor refrigerant liquid temperature - water inlet temperature <...
Page 97
16.5.23 Four Way Valve Abnormality (F25) Malfunction Decision Conditions: During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C. During cooling operation, when the indoor pipe temperature of thermostat ON indoor unit > 45°C. Malfunction Caused: Faulty sensor.
Page 98
16.5.24 Outdoor High Pressure Switch Abnormal (F27) Malfunction Decision Conditions: During compressor stop, and outdoor high pressure switch is remain opened. Malfunction Caused: Faulty connector connection. Faulty switch. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 1 minute.
Page 99
16.5.25 Outdoor Air Temperature Sensor Abnormality (F36) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 100
16.5.26 Indoor Water Inlet Temperature Sensor Abnormality (F37) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water inlet temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
Page 101
16.5.27 Outdoor Discharge Pipe Temperature Sensor Abnormality (F40) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 102
16.5.28 Power Factor Correction (PFC) Abnormality (F41) Malfunction Decision Conditions: During operation of cooling and heating, when the PFC protection circuitry in the outdoor unit PCB (main) senses abnormal high DC voltage level. Malfunction Caused: Power supply surge. Compressor windings not uniform. Faulty outdoor unit PCB (main).
Page 103
16.5.29 Outdoor Pipe Temperature Sensor Abnormality (F42) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 104
16.5.30 Outdoor Defrost Temperature Sensor Abnormality (F43) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor defrost temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 105
16.5.31 Indoor Water Outlet Temperature Sensor Abnormality (F45) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet temperature sensor are used to determine sensor errors. Malfunction Caused: Faulty connector connection. Faulty sensor.
Page 106
16.5.32 Outdoor Current Transformer Open Circuit (F46) Malfunction Decision Conditions: A current transformer (CT) open circuit is detected by checking the compressor running frequency (≥ rated frequency) and CT detected input current (< 0.65A) for continuously 20 seconds. Malfunction Caused: CT defective.
Page 107
16.5.33 Cooling High Pressure Overload Protection (F95) Malfunction Decision Conditions: During operation of cooling, when pressure 4.0MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Dust accumulation in the outdoor unit heat exchanger. Air short circuit at outdoor unit. 2 way valve closed.
17. Disassembly and Assembly Instructions WARNING High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. WARNING Be sure to switch off all the power supply before performing each of the below action.
17.7 To Remove Pressure Relief Valve and Air Purge Valve When reinstall the water pipe, use grease or water at the joining. 17.8 To Remove Flow Switch When reinstall the water pipe, use grease or water at the joining. 17.9 To Remove Water Pump When reinstall the water pipe, use grease or water at the joining.
18. Technical Data 18.1 Operation Characteristics 18.1.1 WH-MDC06E3E5 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C 7.300 6.800 6.300 5.800 5.300...
Page 113
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C 6.000 5.500 5.000 4.500 Outdoor Air Temperature (°C) 2.400 1.900 1.400 0.900 Outdoor Air Temperature (°C)
Page 114
18.1.2 WH-MDC09E3E5 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C 9.300 8.800 8.300 7.800 7.300 6.800 -15 -13 -11 -9 11 13 15 17 19 21 23 25 Outdoor Air Temperature (°C) 3.800...
Page 115
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C 7.300 6.800 6.300 5.800 5.300 Outdoor Air Temperature (°C) 3.500 3.000 2.500 2.000 1.500 1.000...
18.2 Heating Capacity Table 18.2.1 WH-MDC06E3E5 Water Out Outdoor Input Input Input Input Input Input Capacity Capacity Capacity Capacity Capacity Capacity Power Power Power Power Power Power 6150 2500 5900 2660 5650 2820 5400 2980 5200 3150 5000 3320 5175...
19. Exploded View and Replacement Parts List 19.1 WH-MDC06E3E5 WH-MDC09E3E5 (Refrigerant System)
Page 120
Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 121
< Model: Refrigerant System > REF. NO. DESCRIPTION & NAME QTY. WH-MDC06E3E5 WH-MDC09E3E5 REMARK BASE PAN ASS’Y CWD52K1282 ← COMPRESSOR 5KD240XCC21 ← BUSHING - COMPRESSOR MOUNT CWH50055 ← NUT-COMPRESSOR MOUNT CWH561049 ← GASKET FOR TERMINAL COVER CWB811017 ← CRANKCASE HEATER CWA341043 ←...
Page 123
Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 124
< Model: Water System > REF. NO. DESCRIPTION & NAME QTY. WH-MDC06E3E5 WH-MDC09E3E5 REMARK BASE PAN ASS’Y CWD52K1279 ← HOT WATER COIL-COMPLETE CWB90C1067 ← RECEIVER CWB141066 ← FLOW SWITCH CWB621034 ← PUMP CWB532108 ← BOTTLE COMP. CWH90C0035 ← HEATER ASS'Y CWA34K1026 ←...