1 Safety Precautions • Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. • Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating and main circuit for the model installed. •...
Page 4
19. The unit is only for use in a closed portable water system. Utilization in an open water circuit or non-portable water circuit, may lead to excessive corrosion of the water piping and risk of incubating bacteria colonies, particularly Legionella, in water. 20.
2 Specifications 2.1. WH-SDF07C3E5 WH-UD07CE5-A Item Unit Outdoor Unit Performance Test Condition EUROVENT Heating Capacity 7.00 BTU/h 23900 kJ/h 25200 4.40 BTU/hW 15.0 Noise Level dB (A) Power Level dB Air Flow 46.0 (1624) /min (ft /min) Refrigeration Control Device...
Page 6
Item Unit Power Factor Power factor means total figure of compressor and outdoor fan motor. Power Cord Number of core Length m (ft) Thermostat Electronic Control Protection Device Electronic Control Item Unit Indoor Unit Performance Test Condition EUROVENT °C Operation Range Outdoor Ambient -20 ~ 35 °C...
2.2. WH-SDF09C3E5 WH-UD09CE5-A Item Unit Outdoor Unit Performance Test Condition EUROVENT Heating Capacity 9.00 BTU/h 30700 kJ/h 32400 4.10 BTU/hW 14.0 Noise Level dB (A) Power Level dB Air Flow 51.0 (1800) /min (ft /min) Refrigeration Control Device Expansion Valve Refrigeration Oil FV50S (900) Refrigerant (R410A)
Page 8
Item Unit Power Cord Number of core Length m (ft) Thermostat Electronic Control Protection Device Electronic Control Item Unit Indoor Unit Performance Test Condition EUROVENT Operation Range Outdoor Ambient °C -20 ~ 35 °C Water Outlet 25 ~ 55 Internal Pressure Differential 35.0 Noise Level dB (A)
2.3. WH-SDF12C6E5 WH-UD12CE5-A Item Unit Outdoor Unit Performance Test Condition EUROVENT Heating Capacity 12.00 BTU/h 41000 kJ/h 43200 4.67 BTU/hW 16.0 Noise Level dB (A) Power Level dB Air Flow 80.0 (2830) /min (ft /min) Refrigeration Control Device Expansion Valve Refrigeration Oil FV50S (1200) Refrigerant (R410A)
Page 10
Item Unit Power Cord Number of core Length m (ft) Thermostat Electronic Control Protection Device Electronic Control Item Unit Indoor Unit Performance Test Condition EUROVENT Operation Range Outdoor Ambient °C -20 ~ 35 °C Water Outlet 25 ~ 55 Internal Pressure Differential 17400 Noise Level dB (A)
2.4. WH-SDF14C6E5 WH-UD14CE5-A Item Unit Outdoor Unit Performance Test Condition EUROVENT Heating Capacity 14.00 BTU/h 47800 kJ/h 50400 4.50 BTU/hW 15.4 Noise Level dB (A) Power Level dB Air Flow 84.0 (2970) /min (ft /min) Refrigeration Control Device Expansion Valve Refrigeration Oil FV50S (1200) Refrigerant (R410A)
Page 12
Item Unit Power Cord Number of core Length m (ft) Thermostat Electronic Control Protection Device Electronic Control Item Unit Indoor Unit Performance Test Condition EUROVENT Operation Range Outdoor Ambient °C -20 ~ 35 °C Water Outlet 25 ~ 55 Internal Pressure Differential 23000 Noise Level dB (A)
2.5. WH-SDF16C6E5 WH-UD16CE5-A Item Unit Outdoor Unit Performance Test Condition EUROVENT Heating Capacity 16.00 BTU/h 54600 kJ/h 57600 4.23 BTU/hW 14.4 Noise Level dB (A) Power Level dB Air Flow 90.0 (3180) /min (ft /min) Refrigeration Control Device Expansion Valve Refrigeration Oil FV50S (1200) Refrigerant (R410A)
Page 14
Item Unit Power Cord Number of core Length m (ft) Thermostat Electronic Control Protection Device Electronic Control Item Unit Indoor Unit Performance Test Condition EUROVENT Operation Range Outdoor Ambient °C -20 ~ 35 °C Water Outlet 25 ~ 55 Internal Pressure Differential 30200 Noise Level dB (A)
3 Features • Inverter Technology - Energy saving • High Efficiency • Compact Design • Environment Protection - Non-ozone depletion substances refrigerant (R410A) • Long Installation Piping - Long piping up to 30 meter with height difference 20 meter (UD07CE, UD09CE) - Long piping up to 40 meter with height difference 30 meter (UD12CE, UD14CE and UD16CE) - Flexible 4-way piping for outdoor unit •...
6 Refrigeration And Water Cycle Diagram Piping size Min. Max. Rated Common Additional Piping Piping Length Length Elevation Refrigerant Length Length Model Liquid (g/m) UD07CE5-A 5/8” 1/4” UD09CE5-A 5/8” 1/4” UD12CE5-A 5/8” 3/8” UD14CE5-A 5/8” 3/8” UD16CE5-A 5/8” 3/8” * If piping length is over common length, additional refrigerant should be added as shown in the table.
11 Installation Instruction WH-UD07CE5-A WH-UD09CE5-A 11.1. Select The Best Location Piping size Rated Min. Max. Addi- Length Eleva- Piping Piping tional INDOOR UNIT Model tion Length Length Refrige- • There should not be any heat source or steam near the unit.
11.3. Indoor Unit 11.3.3. INDOOR UNIT INSTALLATION 11.3.3.1. Install The Indoor Unit 11.3.1. HOW TO FIX INSTALLATION PLATE 1. When connecting solar pump station cable between The mounting wall is strong and solid enough to prevent it from indoor unit and solar pump station, the distance between the vibration.
Page 45
11.3.3.3. Indoor Unit Refrigerant Pipe • Connect the external filter inlet to boiler tank outlet. Then, connect water outlet connector of indoor unit (indicate with Installation “WATER OUT”) to boiler tank inlet. Fail to connect the tube 1. Please make flare after inserting flare nut (located at joint appropriately might causing the indoor unit malfunction.
11.3.4. CONNECT THE CABLE TO THE INDOOR UNIT 1. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 4.0 or 6.0 mm flexible cord, type designation 60245 IEC 57 or heavier cord. • Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor unit’s respectively. •...
Page 47
Terminal screw Tightening torque N cm {kgf•cm} 157~196 {16~20} 196~245 {20~25} 11.3.4.1. Wire Stripping and Connecting Requirement...
Page 48
11.3.4.2. Connecting Requirement • The equipment’s power supply 1 complies with IEC/EN 61000-3-12 provided that the short-circuit power S is greater than or equal to 828.38kW (for WH-SDF07C3E5/UD07CE5** and WH-SDF09C3E5/UD09CE5**) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power S greater than or equal to 828.38kW.
11.4. Outdoor Unit 11.4.1. INSTALL THE OUTDOOR UNIT • After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram. 1. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). 2. When installing at roof, please consider strong wind and earthquake.
11.4.3. EVACUATION OF THE EQUIPMENT WHEN INSTALLING AN AIR-TO-WATER HEAT PUMP, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. 1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve. •...
4. Select required direction and apply protective bushing provided in accessories to protect cables from sharp edges. 5. Once all wiring work has been completed, tie the cable and cord together with the binding strap so that they do not touch other parts such as the compressor and bare copper pipes.
12 Installation Instruction WH-UD12CE5-A WH-UD14CE5-A WH-UD16CE5-A 12.1. Select The Best Location Piping size Rated Min. Max. Addi- Length Eleva- Piping Piping tional INDOOR UNIT Model tion Length Length Refrige- • There should not be any heat source or steam near the unit. Liquid rant •...
12.3. Indoor Unit 12.3.3. INDOOR UNIT INSTALLATION 12.3.3.1. Install The Indoor Unit 12.3.1. HOW TO FIX INSTALLATION PLATE 1. When connecting solar pump station cable between The mounting wall is strong and solid enough to prevent it from indoor unit and solar pump station, the distance between the vibration.
Page 54
12.3.3.3. Indoor Unit Refrigerant Pipe • Connect the external filter inlet to boiler tank outlet. Then, connect water outlet connector of indoor unit (indicate with Installation “WATER OUT”) to boiler tank inlet. Fail to connect the tube 1. Please make flare after inserting flare nut (located at joint appropriately might causing the indoor unit malfunction.
Page 55
12.3.4. CONNECT THE CABLE TO THE INDOOR UNIT 1. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 4.0 or 6.0 mm flexible cord, type designation 60245 IEC 57 or heavier cord. • Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor unit’s respectively. •...
Page 57
12.3.4.2. Connecting Requirement • The equipment’s power supply 1 complies with IEC/EN 61000-3-12 provided that the short-circuit power S is greater than or equal to 787.57kW (for WH-SDF12C6E5/UD12CE5**, WH-SDF14C6E5/UD14CE5** and WH-SDF16C6E5/UD16CE5**) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power S greater than or equal to 787.57kW.
12.4. Outdoor Unit 12.4.1. INSTALL THE OUTDOOR UNIT • After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram. 1. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). 2. When installing at roof, please consider strong wind and earthquake.
Page 59
CUTTING AND FLARING THE PIPING 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. 3.
Page 60
12.4.4. CONNECT THE CABLE TO THE OUTDOOR UNIT (FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT) 1. Remove the control board cover from the unit by loosening the screw. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 × (4.0 or 6.0 mm flexible cord, type designation 60245 IEC 57 or heavier cord.
13 Operation and Control 13.1. Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
Page 62
ii. Case 2 - Heat pump THERMO OFF TEMP: 1. Heat pump THERMO OFF TEMP = 55°C + [+2°C]. 2. Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump OFF but water pump ON. - Heat pump THERMO ON TEMP: 1.
Page 63
13.1.4. Heat + Tank Mode Operation Setting 1:- When heating priority is set by control panel: 1. 3 ways valve control: • 3 ways valve switch and fix to room side. 2. Heat pump operation control:- • Heat pump operate follow normal operation. 3.
Page 64
• During tank heat-up interval - Heat pump tank target temperature = tank set temperature or [55°C] whichever lower - Heat Pump Water Outlet set temperature is set to Maximum [55°C] during tank interval i. Case 1 - THERMO OFF TEMP : 1.
Page 65
* Under solar priority is not set condition, solar 3WV only can ON during heating heat-up interval.
Page 66
13.1.5. Setting Water Outlet Temperature For Heat Mode • The set temperature define the parameters for the outdoor ambient temperature dependent operation of the unit. Where by the internal water setting temperature is determined automatically depending on the outdoor temperature. The colder outdoor temperatures will result in warmer water and vice versa.
Page 67
• Once enter this setting mode, “SETTING” display is ON. This setting mode is used to easily shift the target water outlet temperature. 13.1.7. Outdoor Fan Motor Operation Outdoor fan motor is adjusted according to operation condition. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.
13.2. Water Pump 13.2.1. Water Pump Control 1. Once the indoor unit is ON, the water pump will be ON immediately and no error judgement for 9 minutes. However, during this 9 minutes operation, if there is any abnormality cause at outdoor or malfunction, the compressor should be OFF immediately and restart delay after 3 minutes.
13.5. Force Heater Mode Operation The backup heater also serves as backup in case of malfunctioning of the outdoor unit. 1. Make sure the OFF/ON control panel LED is OFF (no operation). 2. Press the Force button to start the force heater mode operation. 3.
13.8. Indication Panel Operation Color Green Light ON Operation ON Light OFF Operation OFF Note: • If Operation LED is blinking, there is an abnormality operation occurs. 13.9. Indoor Back-Up Heater Control 13.9.1. Indoor Electric Heater control 1. Normal Heating Mode •...
13.10. Tank Booster Heater Control 13.10.1. Tank booster heater control Heating operation condition: 1. Booster heater Turn On condition: • After BOOSTER HEATER DELAY TIMER fulfil during heat pump startup time in tank mode, or during switching from heating heat-up interval to tank heat-up interval in heat+tank mode (heating priority not set). •...
13.14. Solar operation (Optional) 13.14.1. Solar operation 1. Control according to preset whether Solar Priority is set or not. 2. When tank connection is NOT set at SETTING mode, Solar operation is disabled. 3. When Pump A (from Solar pump station) is detected On through connection Y3 and Y4, then the Solar pump 3 Way Valve is requested ON (Refer to figure below).
13.15. External Room Thermostat Control (Optional) Purpose: 1. Better room temperature control to fulfill different temperature request by external room thermostat. Recomended external room thermostat: Maker Characteristic Siemen (REV200) Touch panel Siemen (RAA20) Analog Connection of external room thermostat: Wire connection and thermo characteristic of Siemen REV200: Setting L/L1 (H) Heat Thermo...
14 Protection Control 14.1. Protection Control For All Operations 14.1.1. Time Delay Safety Control 1. The compressor will not start for three minutes after stop of operation. 14.1.2. 30 Seconds Forced Operation 1. Once the compressor starts operation, it will not stop its operation for 30 seconds. 2.
14.1.7. Low Frequency Protection Control 2 • When all the below conditions comply, the compressor frequency will change to lower frequency. Temperature, T, for: Heating Outlet water (°C) T < 14 or T Outdoor air (°C) T < 4 or T Indoor heat exchanger (°C) 14.1.8.
15 Servicing Mode 15.1. Test Run 1. Fill up the boiler tank with water. For details refer to boiler tanks installation instruction and operation instruction. 2. Set ON to the indoor unit and RCCB. Then, for control panel’s operation please refers to air-to-water heatpump’s operation instruction.
16 Maintenance Guide In order to ensure optimal performance of the unit, checks and inspections on the unit and the field wiring must be carried out regularly. Please request a licensed technician for carry out maintenance job. Before carried out any maintenance or repair work, and removing the front plate of heat exchanger unit, always switch off all power supply (i.e.
Page 80
b. Use a test pen to push the centre button gently in order to reset the Overload protector. c. After finish, install back the Overload protector following the reverse order of step a & b. 7. External water filter (field supply) Clean the external water filter in regularly basic.
17 Troubleshooting Guide 17.1. Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan. The normal pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table on the right.
17.2. Relationship Between The Condition Of The Air-to-Water Heatpump Indoor And Outdoor Units And Pressure And Electric Current Heating Mode Condition of the Air-to-Water Heatpump indoor and outdoor Low Pressure High Pressure Electric current during operation units Water leakage or insufficient water flow rate in the system Excessive amount of refrigerant Inefficient compression...
17.3. Breakdown Self Diagnosis Function 17.3.1. Self Diagnosis Function (Three Digits Alphanumeric Code) • When abnormality occur during operation, the system will stop operation, and OFF/ON control panel LED will blink and error code will display on the control panel Timer display LCD. •...
17.4. Error Codes Table Diagnosis display Abnormality / Protection control Abnormality Judgement Primary location to verify No abnormality detected — — Indoor/Outdoor capacity unmatched 90s after power supply • Indoor/outdoor connection wire • Indoor/outdoor PCB • Specification and combination table in catalogue Outdoor compressor temperature sensor Continue for 5 sec.
Page 85
Diagnosis display Abnormality / Protection control Abnormality Judgement Primary location to verify PFC control 4 times occurrence within 10 • Voltage at PFC minutes Outdoor heat exchanger temperature Continue for 5 sec. • Outdoor heat exchanger temperature sensor abnormality sensor (defective or disconnected) Outdoor defrost sensor abnormality Continue for 5 sec.
17.5. Self-diagnosis Method 17.5.1. Connection Capability Rank Abnormality (H12) Malfunction Decision Conditions: During startup operation of cooling and heating, the capability rank of indoor checked by the outdoor is used to determine connection capability rank abnormality. Malfunction Caused: 1. Wrong model interconnected. 2.
Page 87
17.5.2. Compressor Tank Temperature Sensor Abnormality (H15) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the compressor tank temperature sensor are used to determine sensor error. Malfunction Caused: 1. Faulty connector connection. 2. Faulty sensor. 3.
Page 88
17.5.3. Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor refrigerant liquid temperature sensor are used to determine sensor error. Malfunction Caused: 1. Faulty connector connection. 2.
Page 89
17.5.4. Compressor Low Pressure Protection (H42) Malfunction Decision Conditions: During operation of heating and after 5 minutes compressor ON, when outdoor pipe temperature below -29°C or above 26°C is detected by the outdoor pipe temperature sensor. Malfunction Caused: 1. Dust accumulation on the outdoor unit heat exchanger. 2.
Page 90
17.5.5. Water Flow Switch Abnormality (H62) Malfunction Decision Conditions: During operation of cooling and heating, the water flow detected by the indoor water flow switch is used to determine water flow error. Malfunction Caused: 1. Faulty water pump. 2. Water leak in system. 3.
Page 91
17.5.6. Outdoor High Pressure Abnormality (H64) Malfunction Decision Conditions: During operation of cooling and heating, when the outdoor high pressure sensor output signal is 0Vdc or 5Vdc. Malfunction Caused: 1. Faulty connector connection. 2. Faulty sensor. 3. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 4 times in 20 minutes.
Page 92
17.5.7. Indoor Backup Heater OLP Abnormality (H70) Malfunction Decision Conditions: During operation of indoor backup heater, when no power supplies to indoor backup heater or OLP open circuit. Malfunction Caused: 1. Faulty power supply connector connection. 2. Faulty connector connection. 3.
Page 93
17.5.8. Tank Temperature Sensor Abnormality (H72) Malfunction Decision Conditions: When tank connection is set to ON, the temperatures detected by the tank temperature sensor are used to determine sensor error. Malfunction Caused: 1. Faulty connector connection. 2. Faulty sensor. 3. Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 94
17.5.9. Indoor-Control Panel Communication Abnormality (H76) Malfunction Decision Conditions: During standby and operation of cooling and heating, indoor-control panel error occur. Malfunction Caused: 1. Faulty connector connection. 2. Faulty control panel. 3. Faulty indoor unit PCB (main).
Page 95
17.5.10. Indoor/Outdoor Abnormal Communication (H90) Malfunction Decision Conditions: During operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused: 1. Faulty outdoor unit PCB (main). 2. Faulty indoor unit PCB (main). 3.
Page 96
17.5.11. Tank Booster Heater OLP Abnormality (H91) Malfunction Decision Conditions: During operation of tank booster heater, and tank booster heater OLP open circuit. Malfunction Caused: 1. Faulty connector connection. 2. Faulty tank booster heater overload protector (OLP). 3. Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 60 seconds.
Page 97
17.5.12. Unspecified Voltage between Indoor and Outdoor (H95) Malfunction Decision Conditions: The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused: 1. Insufficient power supply. 2. Faulty outdoor unit PCB (noise filter/main).
Page 98
17.5.13. Outdoor High Pressure Protection (H98) Malfunction Decision Conditions: During operation of heating, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: 1. Faulty water pump. 2. Insufficient water flow rate in system. 3. Water leak in system. 4.
Page 99
17.5.14. Indoor Freeze-up Protection (H99) Malfunction Decision Conditions: During anti-freezing control in cooling operation, when the indoor refrigerant liquid temperature < 0°C. Malfunction Caused: 1. Faulty water pump. 2. Insufficient water flow rate in system. 3. Water leak in system. 4.
Page 100
17.5.15. Outdoor High Pressure Switch Activate (F12) Malfunction Decision Conditions: During operation of cooling and heating, when pressure 4.5MPa and above is detected by outdoor high pressure switch. Malfunction Caused: 1. Dust accumulation on the outdoor unit heat exchanger. 2. Air short circuit at outdoor unit. 3.
Page 101
17.5.16. Compressor Rotation Failure (F14) Malfunction Decision Conditions: A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused: 1. Compressor terminal disconnect. 2. Faulty outdoor unit PCB (main). 3. Faulty compressor. Abnormality Judgment: Continue 4 times in 20 minutes.
Page 102
17.5.17. Outdoor Fan Motor (DC Motor) Mechanism Locked (F15) Malfunction Decision Conditions: The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm). Malfunction Caused: 1.
Page 103
17.5.18. Input Over Current Detection (F16) Malfunction Decision Conditions: During operation of cooling and heating, when outdoor current above 27.9A is detected by the current transformer (CT) in the outdoor unit PCB. Malfunction Caused: 1. Excessive refrigerant. 2. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 20 minutes.
Page 104
17.5.19. Compressor Overheating (F20) Malfunction Decision Conditions: During operation of cooling and heating, when temperature above 112°C is detected by the compressor tank temperature sensor. Malfunction Caused: 1. Faulty compressor tank temperature sensor. 2. 2/3 way valve closed. 3. Refrigerant shortage (refrigerant leakage). 4.
Page 105
17.5.20. IPM Overheating (F22) Malfunction Decision Conditions: During operation of cooling and heating, when temperature 95°C is detected by the outdoor IPM temperature sensor. Malfunction Caused: 1. Faulty outdoor unit fan motor. 2. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 30 minutes.
Page 106
17.5.21. Output Over Current Detection (F23) Malfunction Decision Conditions: During operation of cooling and heating, when outdoor DC current is above 40.1 ± 5.0A (for: UD07~09CE) OR 44.7 ± 5.0A (for: UD12~16CE) is detected by the IPM DC Peak sensing circuitry in the outdoor unit PCB (main). Malfunction Caused: 1.
Page 107
17.5.22. Refrigeration Cycle Abnormality (F24) Malfunction Decision Conditions: 1. During operation of cooling and heating, compressor frequency > Frated. 2. During operation of cooling and heating, running current: 0.65A < I < 1.65A. 3. During operation of cooling, water inlet temperature - indoor refrigerant liquid temperature < 5°C. 4.
Page 108
17.5.23. Four Way Valve Abnormality (F25) Malfunction Decision Conditions: 1. During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C. 2. During cooling operation, when the indoor pipe temperature of thermostat ON indoor unit > 45°C. Malfunction Caused: 1.
Page 109
17.5.24. Outdoor High Pressure Switch Abnormal (F27) Malfunction Decision Conditions: During compressor stop, and outdoor high pressure switch is remain opened. Malfunction Caused: 1. Faulty connector connection. 2. Faulty switch. 3. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 1 minute.
Page 110
17.5.25. Outdoor Air Temperature Sensor Abnormality (F36) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor error. Malfunction Caused: 1. Faulty connector connection. 2. Faulty sensor. 3.
Page 111
17.5.26. Indoor Water Inlet Temperature Sensor Abnormality (F37) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water inlet temperature sensor are used to determine sensor error. Malfunction Caused: 1. Faulty connector connection. 2.
Page 112
17.5.27. Outdoor Discharge Pipe Temperature Sensor Abnormality (F40) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor error. Malfunction Caused: 1. Faulty connector connection. 2.
Page 113
17.5.28. Power Factor Correction (PFC) Abnormality (F41) Malfunction Decision Conditions: During operation of cooling and heating, when the PFC protection circuitry in the outdoor unit PCB (main) senses abnormal high DC voltage level. Malfunction Caused: 1. Power supply surge. 2. Compressor windings not uniform. 3.
Page 114
17.5.29. Outdoor Pipe Temperature Sensor Abnormality (F42) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor error. Malfunction Caused: 1. Faulty connector connection. 2. Faulty sensor. 3.
Page 115
17.5.30. Outdoor Defrost Temperature Sensor Abnormality (F43) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor defrost temperature sensor are used to determine sensor error. Malfunction Caused: 1. Faulty connector connection. 2. Faulty sensor. 3.
Page 116
17.5.31. Indoor Water Outlet Temperature Sensor Abnormality (F45) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet temperature sensor are used to determine sensor errors. Malfunction Caused: 1. Faulty connector connection. 2.
Page 117
17.5.32. Outdoor Current Transformer Open Circuit (F46) Malfunction Decision Conditions: A current transformer (CT) open circuit is detected by checking the compressor running frequency ( rated frequency) and CT detected input current (< 0.65A) for continuously 20 seconds. Malfunction Caused: 1.
Page 118
17.5.33. Cooling High Pressure Overload Protection (F95) Malfunction Decision Conditions: During operation of cooling, when pressure 4.0MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: 1. Dust accumulation in the outdoor unit heat exchanger. 2. Air short circuit at outdoor unit. 3.
18 Disassembly and Assembly Instructions WARNING High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 18.1.
19 Technical Data 19.1. Operation Characteristics 19.1.1. WH-SDF07C3E5 WH-UD07CE5-A Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7m...
Page 125
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7m...
Page 126
19.1.2. WH-SDF09C3E5 WH-UD09CE5-A Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7m...
Page 127
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7m...
Page 128
19.1.3. WH-SDF12C6E5 WH-UD12CE5-A Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7m...
Page 129
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7m...
Page 130
19.1.4. WH-SDF14C6E5 WH-UD14CE5-A Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7m...
Page 131
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7m...
Page 132
19.1.5. WH-SDF16C6E5 WH-UD16CE5-A Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7m...
Page 133
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7m...
20 Exploded View and Replacement Parts List 20.1. WH-SDF07C3E5 WH-SDF09C3E5 WH-SDF12C6E5 WH-SDF14C6E5 WH-SDF16C6E5 Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 137
<Model: WH-SDF07C3E5 WH-SDF09C3E5 WH-SDF12C6E5 WH-SDF14C6E5 WH-SDF16C6E5> REF. DESCRIPTION & NAME QTY. REMARKS SDF07C3E5 SDF09C3E5 SDF12C6E5 SDF14C6E5 SDF16C6E5 ← ← ← ← BASE PAN CWD521266 HOT WATER COIL-COMPLETE CWB90C1043 ← CWB90C1051 ← ← ← ← ← ← RECEIVER CWB141039 ← ← ←...
Page 140
Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 141
<Model: WH-UD07CE5-A WH-UD09CE5-A> REF. NO. DESCRIPTION & NAME QTY. WH-UD07CE5-A WH-UD09CE5-A REMARKS ← BASE PAN ASS’Y CWD52K1199 COMPRESSOR DC 280V 5KD240XCC21 ← ← BUSHING-COMPRESSOR MOUNT CWH50055 NUT FOR COMP. MOUNT. CWH561049 ← ← PACKING CWB811017 CONDENSER COMPLETE CWB32C2846 ← ←...
Page 144
Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 146
REF. NO. DESCRIPTION & NAME QTY. WH-UD12CE5-A WH-UD14CE5-A WH-UD16CE5-A REMARKS ← ← ELECTRO MAGNETIC SWITCH K6C1AYY00003 (Note) • All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488). • “O” marked parts are recommended to be kept in stock. [PHAAM] Printed in Malaysia SFYW1004 - 00...