1. Safety Precautions ..........4 ..............125 12.16 Force DHW mode ........125 2. Specifications .............7 12.17 Anti Freeze Control ........126 WH-SDC09H3E8 WH-UD09HE8....7 12.18 Solar Operation (Optional)......127 WH-SDC12H9E8 WH-UD12HE8....10 12.19 Boiler Bivalent Control ......129 WH-SDC16H9E8 WH-UD16HE8....13 12.20 External Room Thermostat Control (Optional) ..............
Page 3
17.9 To Remove Water Pump and Bottle Complete ..............212 17.10 To Remove Filter ........213 18. Technical Data ..........214 18.1 Operation Characteristics ......214 18.2 Heating Capacity Table ......232 18.3 Cooling Capacity Table ......233 19. Exploded View and Replacement Parts List ................234 19.1 Indoor Unit ..........234 19.2 Outdoor Unit ..........237...
1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before installation. Electrical work must be installed by a licensed electrician. Be sure to use the correct rating and main circuit for the model to be installed. The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Page 5
WARNING Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury. This equipment is strongly recommended to be installed with Residual Current Device (RCD) on-site according to the respective national wiring rules or country–specific safety measures in terms of residual current.
Page 6
CAUTION Power supply connection to Indoor Unit. Power supply point should be in easily accessible place for power disconnection in case of emergency. Must follow local national wiring standard, regulation and this installation instruction. Strongly recommended to make permanent connection to a circuit breaker. Power supply 1: Use approved 20A 4-poles circuit breaker with a minimum contact gap of 3.0 mm.
2. Specifications WH-SDC09H3E8 WH-UD09HE8 Item Unit Outdoor Unit Performance Test Condition EN 14511 Condition A35W7 (Ambient/Water) 7.00 Cooling Capacity BTU/h 23900 kcal/h 6020 3.17 Cooling EER kcal/hW 2.72 Condition A7W35 A2W35 (Ambient/Water) 9.00 9.00 Heating Capacity BTU/h 30700 30700 kcal/h...
Page 8
Item Unit Outdoor Unit Additional Gas Amount g/m (oz/ft) 50 (0.5) Refrigeration Charge Less m (ft) 10 (32.8) Type Hermetic Motor Compressor Motor Type Brushless (4-poles) Rated Output 4.50 Type Propeller Fan Material Motor Type DC (8-poles) Input Power — Output Power Cooling: 550 (Top), 590 (Bottom) Fan Speed...
Page 9
Item Unit Indoor Unit Performance Test Condition EN 14511 Cooling: 16 ~ 43 Outdoor Ambient °C Heating: -20 ~ 35 Operation Range Cooling: 5 ~ 20 Water Outlet °C Heating: 20 ~ 55 Cooling: 19 Internal Pressure Differential Heating: 30 Condition A35W7 A7W35...
Page 11
Item Unit Outdoor Unit Type Hermetic Motor Compressor Motor Type Brushless (4-poles) Rated Output 4.50 Type Propeller Fan Material Motor Type DC (8-poles) Input Power — Output Power Cooling: 600 (Top), 640 (Bottom) Fan Speed Heating: 510 (Top), 550 (Bottom) Fin material Aluminium (Pre Coat) Fin Type...
Page 12
Item Unit Indoor Unit Performance Test Condition EN 14511 Cooling: 16 ~ 43 Outdoor Ambient °C Heating: -20 ~ 35 Operation Range Cooling: 5 ~ 20 Water Outlet °C Heating: 20 ~ 55 Cooling: 36 Internal Pressure Differential Heating: 52 Condition A35W7 A7W35...
Page 14
Item Unit Outdoor Unit Type Hermetic Motor Compressor Motor Type Brushless (4-poles) Rated Output 4.50 Type Propeller Fan Material Motor Type DC / Transistor (8-poles) Input Power — Output Power Cooling: 630 (Top), 670 (Bottom) Fan Speed Heating: 580 (Top), 620 (Bottom) Fin material Aluminium (Pre Coat) Fin Type...
Page 15
Item Unit Indoor Unit Performance Test Condition EN 14511 Cooling: 16 ~ 43 Outdoor Ambient °C Heating: -20 ~ 35 Operation Range Cooling: 5 ~ 20 Water Outlet °C Heating: 20 ~ 55 Cooling: 48 Internal Pressure Differential Heating: 82 Condition A35W7 A7W35...
3. Features Inverter Technology - Energy saving High Efficiency Environment Protection - Non-ozone depletion substances refrigerant (R410A) Long Installation Piping - Long piping up to 30 meter with height difference 20 meter - Flexible 4-way piping for outdoor unit ...
4. Location of Controls and Components Indoor Unit 4.1.1 Location of Control Water pressure gauge • Do not press or hit the glass cover using hard and sharp objects. Failure to do so may cause damage to the unit. • Ensure that the water pressure is between 0.05 and 0.3 MPa (0.1 MPa = 1 bar).
Page 18
10:34am, Mon ˚ c ˚ c ˚ c ˚ c Display Mode selection AUTO • Depending on the preset outdoor COOL • The fan coil unit is either turned temperature, the system selects ON or OFF. HEAT or * COOL operation mode. •...
4.1.2 Initialization Before starting to install the various menu settings, please initiate the Remote Controller by selecting the language of operation and installing the date and time correctly. It is recommended that the installer conducts the following initialization of the Remote Controller. Selecting the language LCD blinking Press...
Page 20
4.1.3.1 Before Use This Quick Guide explains how to use the Quick Menu. Please read the Operating Instructions thoroughly before using the Quick Menu. 4.1.3.2 How to use the Quick Menu After the initial settings have been completed, you can select a quick menu from the following options and edit the setting.
Page 21
Notes on operation icon Example: • Operation icon indicate with “ ” = OFF • Operation icon indicate with “ ” = ON Select this icon to turn the Tank DHW on or off. Press to confirm your selection. • Force DHW is turned off. •...
Page 22
Select this icon to operate quietly. Press to confirm your selection. (The quiet operation starts approximately 1 minute after is pressed.) • Quiet mode is set off. • The Quiet mode operates at level 1. Quiet • The Quiet mode operates at level 2. •...
Page 23
Select to force the Heater on. Press to confirm your selection. (The Force Heater mode starts approximately 1 minute after pressed.) • Force Heater is turned off. Force • Force Heater is turned on. Heater ■ Note: • Force Heater is disabled whenever operation is already on and ‘Disabled due to Operation ON!’...
Page 24
Select this icon to delete (cancel) or change the pre-set Weekly Timer. Press to confirm your selection. • Timer is not ON. • Timer is set. Weekly Timer After 1 sec delay. Select “Yes”. • If you select “No”, the screen will return to the Main Screen. •...
Page 25
Select to defrost the frozen pipes. Press to confirm your selection. (When the mode is accepted, below screen will be displayed.) Force Defrost Select to restore the previous settings when error has occurred. Press to confirm your selection. (When the mode has been accepted, below screen will be displayed.) •...
Page 26
4.1.4 Menus For user Select menus and determine settings according to the system available in the household. All initial settings must be done by an authorised dealer or a specialist. It is recommended that all alterations of the initial settings are also done by an authorised dealer or a specialist.
t l u i t t i t t o i t Holiday timer To save energy, a holiday period may be set to either turn OFF the system or lower the temperature during the period. Holiday start and end. Date and time OFF or lowered temperature •...
Page 28
t l u i t t i t t o i t Error history • Refer to Troubleshooting for error codes. • The most recent error code is Select and retrieve displayed at the top. Compressor Shows the compressor performance. Select and retrieve Heater Total hours of ON time for...
Page 29
t l u i t t i t t o i t Date & Time Sets the present date and time. Year / Month / Day / Hour / Min Language Sets the display language for ENGLISH / FRANÇAIS / the top screen.
Page 30
4.1.5 Menus For installer t l u i t t i t t o i t 5 Installer setup System setup Optional PCB connectivity To connect to the external PCB required for servicing. • If the external PCB is connected (optional), the system will have following additional functions: Buffer tank connection and control over its function and temperature.
Page 31
t l u i t t i t t o i t Tank heater To select external or internal tank heater and if External is selected, set a timer for the Internal heater to come on. i t p l i a Tank connection is selected External (YES).
Page 32
t l u i t t i t t o i t Control pattern Advanced parallel Heat Selection of the tank • “Heat” implies Buffer Tank and “DHW” implies Domestic Hot Water Tank. Control pattern Advanced parallel Heat Yes • Buffer Tank is activated only after selecting “Yes”.
Page 33
t l u i t t i t t o i t 5.11 External SW 5.12 Solar connection • The optional PCB connectivity must be selected YES to enable the function. • If the optional PCB connectivity is not selected, the function will not appear on the display.
Page 34
t l u i t t i t t o i t 5.13 External error signal 5.14 Demand control 5.15 SG ready Capacity (1) & (2) of 120 % Buffer Tank and DHW Tank (in %) 5.16 External compressor SW 5.17 Circulation liquid To select whether to circulate...
Page 35
t l u i t t i t t o i t Installer setup Operation setup Heat To set various water & Water temp. for heating ON / ambient temperatures for Outdoor temp. for heating OFF / heating. T for heating ON / Outdoor temp.
Page 36
t l u i t t i t t o i t T for heating ON Set T for heating 5 °C Outdoor temp. for heater ON Temperature for 0 °C heater ON Cool To set various water & ambient Water temperatures for cooling ON temperatures for cooling.
Page 37
t l u i t t i t t o i t Auto Automatic switch from Heat to Outdoor temperatures for switching from Heat Cool or Cool to Heat. to Cool or Cool to Heat. Outdoor temp. for (Heat to Cool) / Outdoor temp.
Page 38
t l u i t t i t t o i t Sterilization Sterilization may be set for 1 or more days of the week. Sun / Mon / Tue / Wed / Thu / Fri / Sat Sterilization: Time Time of the selected day(s) of the week to sterilize the tank.
Page 39
t l u i t t i t t o i t Installer setup Service setup Dry concrete Edit to set the temperature of dry concrete. To dry the concrete (floor, walls, etc.) during construction. ON / Edit Do not use this menu for any other purposes and in period other than during Edit...
Page 40
4.1.6 Main Components Cabinet front plate Cabinet side plate (2 pieces) Remote controller 3 Phase RCCB/ELCB (Main Power) Single Phase RCCB/ELCB (Booster Heater) for S*C09*3E8 3 Phase RCCB/ELCB for S*C12*9 E8, S*C16*9E8 Control board cover Control board Flow sensor Air purge valve Backup heater Overload protector (4 pieces) Expansion vessel...
5. Dimensions Indoor Unit <Top View> <Front View> <Side View> 58.9 141.9 326.9 <Bottom View> 424.5 404.1 54.6 69.5 437.3 Relative position between the indoor unit and the installation plate <Front View> More than 375 More than 375 Wall Wall Installation plate Indoor Unit...
6. Refrigeration and Water Cycle Diagram Outdoor Indoor Side Side Water Pressure Gauge Expansion Liquid Vessel Water Side Capillary Flow Expansion (3-Way Tube Switch Valve Strainer Strainer Valve) Water Inlet (Connect Water Refrigerant Pump Sanitary Temp. Tank) Sensor Water Inlet Defrost Temp.
Standard System (Optional PCB not connected) Room Thermo (4 option) Expansion Vessel (10L) External Internal Thermostat Thermostat Fan Coil Unit Air purge valve Indoor Unit (Heating / Cooling) Water External Nothing Inlet Pressure Thermistor Gauge Panel Heater Unit (Heating) OLP × 4 3-Way valve 2-Way valve Extra Pump...
8. Wiring Connection Diagram Indoor Unit 8.1.1 WH-SDC09H3E8 EXTERNAL COMP. SW HEAT/COOL SWITCH SIGNAL SOLAR TEMP. SENSOR DEMAND SIGNAL WATER TEMP. ZONE 1 WATER TEMP. ZONE 2 POOL TEMP. SENSOR BUFFERTANK SENSOR ROOM TEMP. ZONE 1 ROOM TEMP. ZONE 2...
Page 49
8.1.2 WH-SDC12H9E8 WH-SDC16H9E8 EXTERNAL COMP. SW HEAT/COOL SWITCH SIGNAL SOLARTEMP. SENSOR DEMAND SIGNAL WATER TEMP. ZONE 1 WATER TEMP. ZONE 2 POOL TEMP. SENSOR BUFFERTANK SENSOR ROOM TEMP. ZONE 1 ROOM TEMP. ZONE 2...
9. Electronic Circuit Diagram Indoor Unit 9.1.1 WH-SDC09H3E8 EXTERNAL COMP. SW HEAT/COOL SWITCH SIGNAL SOLARTEMP. SENSOR DEMAND SIGNAL WATER TEMP. ZONE 1 WATER TEMP. ZONE 2 POOL TEMP. SENSOR BUFFERTANK SENSOR ROOM TEMP. ZONE 1 ROOM TEMP. ZONE 2...
Page 52
9.1.2 WH-SDC12H9E8 WH-SDC16H9E8 EXTERNAL COMP. SW HEAT/COOL SWITCH SIGNAL SOLAR TEMP. SENSOR DEMAND SIGNAL WATER TEMP. ZONE 1 WATER TEMP. ZONE 2 POOL TEMP. SENSOR BUFFERTANK SENSOR ROOM TEMP. ZONE 1 ROOM TEMP. ZONE 2...
11. Installation Instruction The centre of installation plate should be at more than 11.1 Indoor Unit 375 mm at right and left of the wall. The distance from installation plate edge to ground should more than 1556 mm. 11.1.1 Select the Best Location ...
2. Gently pull the lower section of the front plate This water circuit must comply with all relevant towards you to remove the front plate from left and European and national regulations, i.e. IEC/EN right hooks. 61770. 3. Hold the left edge and right edge of front plate to ...
Page 60
If necessary, use hose clamp to further tighten the hose at drain hose connector to prevent leakage. Spanner or Water will drip from this hose, therefore the outlet Wrench Torque wrench of this hose must be installed in an area where the outlet cannot become blocked.
Page 61
For model S*C09*3E8 Main Power Supply Terminal on the outdoor unit or Main + Backup Booster Heater Colour of wires (Connecting cables) Heater Power Supply Power Supply Terminal on the indoor unit (Power Supply Cord) Indoor unit/Outdoor unit Terminals on the isolating device connection from power supply (Disconnecting means)
11.1.5.4 Connecting Requirement 11.1.6.2 Remote Controller Wiring For S*C09*3E8 Indoor unit The equipment’s Power Supply 1 complies with IEC/EN 61000-3-2. The equipment’s Power Supply 1 complies with Remote Controller IEC/EN 61000-3-3 and can be connected to current supply network. ...
Page 63
11.1.6.4 Mounting The Remote 11.1.6.5 Replace The Remote Controller Controller Cover For exposed type Replace the existing Remote controller cover with Preparation: Make 2 holes for screws using a driver. Remote controller cover to close the hole left after remove the Remote controller. 1.
Page 64
Contact authorized dealer if the RCCB/ELCB 2. Set the Pressure Relief Valve level “DOWN”. malfunction. Pressure relief Turn off the power supply to the Indoor Unit. valve If RCCB/ELCB functions normal, set the lever to “ON” again after testing finish. Lever This product contains fluorinated greenhouse gasses.
Page 65
11.1.10 Maintenance 11.1.10.2 Check Items In order to ensure safety and optimal performance of the unit, seasonal inspections on the unit, Is there any gas leakage at flare nut connections? functional check of RCCB/ELCB, field wiring and Has the heat insulation been carried out at flare nut connection? piping have to be carried out at regular intervals.
11.2 Variation of system This section introduces variation of various systems using Air-To-Water Heatpump and actual setting method. 11.2.1 Introduce application related to temperature setting. 11.2.1.1 Temperature setting variation for heating 1. Remote Controller Outdoor Indoor Setting of remote controller Installer setting System setup Optional PCB connectivity - No...
Page 67
Connect floor heating or radiator directly to indoor unit. Remote controller is installed on indoor unit. Install separate external room thermistor (specified by Panasonic) in the room where floor heating is installed. This is an application that uses external room thermistor.
Page 68
Connect floor heating and swimming pool to 2 circuits through buffer tank as shown in figure. Install mixing valves, pumps and thermistors (specified by Panasonic) on both circuits. Then, install additional pool heat exchanger, pool pump and pool sensor on pool circuit.
Page 69
Connects pool heat exchanger directly to indoor unit without using buffer tank. Install pool pump and pool sensor (specified by Panasonic) at secondary side of the pool heat exchanger. Remove remote controller from indoor unit and install in room where floor heating is installed.
Page 70
This is an application that connects the DHW tank to the indoor unit through 3-way valve before connect the solar water heater to heat up the tank. DHW tank’s temperature is detected by tank thermistor (specified by Panasonic). Solar panel’s temperature is detected by solar thermistor (specified by Panasonic).
(It must connect to buffer tank especially when selecting Advanced Parallel setting.) WARNING Panasonic is NOT responsible for incorrect or unsafe situation of the boiler system. CAUTION Make sure the boiler and its integration in the system complies with applicable legislation.
Page 72
Tank Sensor Resistant Vs Temperature 11.2.3 How To Fix Cable 16000 14000 12000 11.2.3.1 Connecting with external 10000 device (optional) 8000 6000 All connections shall follow to the local national 4000 wiring standard. 2000 It is strongly recommended to use manufacturer- recommended parts and accessories for -30 -20 -10 installation.
Page 73
For connection to optional PCB Bind all optional cables Optional 1. By connecting optional PCB, 2 Zone temperature with these bands control can be achieved. Please connect mixing valves, water pumps and thermistors in zone 1 Bind optional and zone 2 to each terminals in optional PCB. cables with these bands Temperature of each zone can be controlled...
Page 74
Tank sensor AW-A2W-TSOD (Total cable length Room sensor Outdoor air sensor shall be 30m or less) Outdoor air sensor Tank sensor Please use Panasonic specified part Tank OLP Buffer tank sensor 11.2.3.4 Connection of Optional PCB Pool water sensor (CZ-NS4P)
Page 75
Use for measurement of the solar panel This section explains about the external devices temperature. (optional) recommended by Panasonic. Please Insert the sensor into the sensor pocket and paste always ensure to use the correct external device it on the solar panel surface.
Page 76
For optional pump. Power supply: AC230V/50Hz, <500W CN-CNT cable Recommended part: Yonos 25/6: made by Wilo For S*C09*3E8 For optional mixing valve. Power supply: AC230V/50Hz (input open/output close) For S*C12/16*9E8 Operating time: 30s~120s With Optional PCB Recommended part: 167032: made by Caleffi 2.
Page 77
5. Use the included cord clamp to fix the CN-CNT cable to the wall. Pull the cable around as shown in the diagram so that external forces cannot act on the connector in the adaptor. Furthermore, on the Indoor Unit end, use the included cable tie to fix the cables together.
11.3 System Installation 11.3.1 Remote Controller Outline Name Function Main screen Display information Menu Open/Close main menu Triangle (Move) Select or change item Operate Start/Stop operation Back Back to previous item Quick Menu Open/Close Quick menu Confirm 10:34am, Mon 40 ˚ c ˚...
Page 79
First time of power ON (Start of installation) 12:00, Mon Initialization When power is ON, firstly initialization screen appears (10 sec) Initializing. 17:26, Wed When initialization screen ends, it turns to normal screen. Start 12:00, Wed Language ENGLISH When any button is pressed, language FRANCAIS setting screen appears.
Page 80
11.3.2 Installer Setup System setup Optional PCB connectivity Yes/No Only when the selection for optional PCB is Yes Zone & Sensor 1 Zone/2 Zone Zone settings Heater capacity Capacity select Anti freezing Yes/No Tank connection Yes/No Only when the selection for optional PCB is Yes Buffer Tank connection Yes/No ∆T setup...
Page 81
Compensation Operation setup Heat Water temp. for heating ON Compensation curve curve setup Direct Direct temp. setup Heating OFF Temp. setup Outdoor temp. for heating OFF ∆T for heating ON ∆T for heating setup O/D temp for heater ON setup Outdoor temp.
Page 82
11.3.3 System Setup System setup 17:26, Wed 1. Optional PCB connectivity Initial setting: No Optional PCB connectivity If function below is necessary, please purchase and install optional PCB. Zone & Sensor Please select Yes after installing optional PCB. Heater capacity •...
Page 83
System setup 17:26, Wed 6. Buffer Tank connection Initial setting: No Heater capacity Select whether it is connected to buffer tank for heating or not. Anti freezing If buffer tank is used, please set Yes. Tank connection Connect buffer tank thermistor and set, ∆T (∆T use to increase primary side temp against secondary side target temp).
Page 84
System setup 17:26, Wed 10. Bivalent connection Initial setting: No Tank heater Set if heat pump linked with boiler operation. Base pan heater Connect the start signal of the boiler in boiler contact terminal (main PCB). Alternative outdoor sensor Set Bivalent connection to YES. After that, please begin setting according to remote controller instruction.
Page 85
System setup 17:26, Wed 13. External Error Signal Initial setting: No Bivalent connection Set when external error display unit is installed. External SW Turn on Dry Contact SW when error happened. Solar connection (CAUTION) Does not display when there is no Optional PCB. External error signal When error occurs, error signal will be ON.
Page 86
17:26, Wed 17. Circulation Liquid System setup Initial setting: Water Demand control Set circulation of heating water. SG ready External compressor SW There are 2 types of settings, water and anti-freeze function. Circulation liquid (CAUTION) Please set glycol when using anti-freeze function. Select Confirm It may cause error if setting is wrong.
Page 87
Cool 20°C 24. Water temp. for cooling ON Initial setting: compensation curve Set target water temperature to operate cooling operation. Compensation curve: Target water temperature change in conjunction with outdoor ambient temperature change. 5°C Direct : Set direct circulation water temperature. In 2 zone system, zone 1 and zone 2 water temperature can be set separately.
Page 88
30. Tank re-heat temp. Initial setting: -8°C Set temp to perform reboil of tank water. (When boiled by heat pump only, (51°C – Tank re-heat temp) shall become max temp.) -12°C ~ -2°C Setting range is -12°C ~ -2°C 31. Sterilization Initial setting: 65°C 10min ②...
11.4.2 Custom menu 11.4 Service and maintenance Setting method of Custom menu When connect CN-CNT connector with computer Custom menu 17:26, Wed Please use optional USB cable to connect with CN-CNT connector. Cool mode After connected, it requests for driver. If PC is under Windows Back-up heater Vista or later version, it automatically installs the driver under Reset energy monitor...
11.5 Outdoor Unit 11.5.1 Select the Best Location If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed. Avoid installations in areas where the ambient temperature may drop below -20°C for UD models and -28°C for UX models.
11.5.2 Install The Outdoor Unit 11.5.2.1 Installation Diagram It is advisable to avoid more than 2 blockage directions. For better ventilation & multiple-outdoor installation, please consult authorized dealer/specialist. This illustration is for explanation purposes only. Vinyl tape (Wide) Saddle Indoor/Outdoor connecting cable - For UX09*E5*, UX12*E5*, UD12*E5*, UD16*E5* use 4-CORE WIRE...
Service panel 11.5.3 Connecting The Piping CAUTION Do not over tighten, over tightening cause gas leakage. Piping size (Torque) Model Liquid Rear direction UX09*E5*, UX12*E5*, UD12*E5*, UD16*E5*, ø15.88 mm (5/8") Ø9.52 mm (3/8") UX09*E8*, UX12*E8*, Rear pipe panel [65 N•m] [42 N•m] UX16*E8*, UD09*E8*, UD12*E8*, UD16*E8*...
Page 93
11.5.4 Evacuation Of The Equipment WHEN INSTALLING AN AIR-TO-WATER HEAT PUMP, BE SURE TO EVACUATE THE AIR INSIDE THE UNIT AND PIPES in the following procedure. Liquid side Indoor unit Outdoor unit Two-way valve Close Gas side Three-way valve Vacuum pump Close adaptor...
Page 94
8. Next, insert a small amount of same refrigerant into the system through the centre hose, until the pressure reaches about 1MPa (10 BarG). (Low/Gas) pressure gauge (High/Liquid) pressure gauge R-### An example illustrations of setup for refrigerant leak detection. Step 2: Refrigerant leak detection through Electronic halogen leak detector and/or ultrasonic leak detector: 1.
11.5.5 Connect The Cable To The Outdoor Unit (FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT) 1. Remove the control board cover from the unit by loosening the screw. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed flexible cable (see below table), type designation 60245 IEC 57 or heavier cable.
WIRE STRIPPING AND CONNECTING REQUIREMENT Wire stripping Conductor not Conductor over Conductor fully Indoor/outdoor fully insert insert insert connecting terminal board 5 mm or more (gap between wires) ACCEPT PROHIBITED PROHIBITED No loose strand when insert 11.5.6 Pipe Insulation 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
12. Operation and Control 12.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
12.1.3 Cooling Operation 12.1.3.1 Thermostat control Compressor is OFF when Water Outlet Temperature – Internal Water Setting Temperature > -1.5°C for continuously 3 minutes. Compressor is ON after waiting for 3 minutes, if the Water Outlet Temperature – Water Inlet Temperature (temperature at thermostat OFF is triggered) >3°C.
Page 99
Maximum/minimum regulation of Target Water Temperature. Heating Cooling 55°C 20°C 20°C 5°C Compensation Type: (Operation under Heat Mode and Cool Mode) The set temperature defines the parameters for the ambient (Outdoor temperature) dependent operation of the unit. The water temperature is determined automatically depending on the outdoor temperature. Default setting is the colder outdoor temperature will result in warmer water and vice versa.
Page 100
12.1.5 Target Water Temperature at Extension System (Optional PCB is connected) Target water temperature is calculated as below. Heat Mode: Target water temperature setting: Max= 55°C Min= 20°C When buffer tank selection is “YES:” Target water temperature = Target buffer tank temperature + [2°C] When buffer tank selection is “NO”...
Page 101
12.1.6 Target Zone Water Temperature Control Purpose:- To control zone mixing and zone pump according to the zone sensor temperature 12.1.6.1 Target Zone 1 water temperature setting control Start condition Heating zone 1 is ON by remote control or Timer or Auto Mode OR Cooling zone 1 is ON by remote control or Timer or Auto Mode.
Page 102
12.1.6.2 Target Zone 2 water temperature setting control Start condition Heating zone 2 is ON by remote control or Timer or Auto Mode OR Cooling zone 2 is ON by remote control or Timer or Auto Mode. Cancel condition Heating zone 2 is OFF by remote control or Timer or Auto mode AND Cooling zone 2 is OFF by remote control or Timer or Auto mode.
Page 103
12.1.6.3 Zone Temperature Control Contents During Standard System (Optional PCB not connected) a) Only 1 zone temperature control is available b) This zone room temperature is control by either one of the 4 room sensor (Room Th, Int/Ext Room Thermostat, Water temperature) c) Target Zone Water Temperature is calculated based on selected temperature control type (Compensation or Direct) and selected room sensor.
Page 104
2) Buffer Tank Connection select "YES" & 1 zone system or 2 zone system select a) Each zone control by each sensor which select from either one of the 4 room sensor b) Target Zone 1 & 2 Water Temperature calculate base on selected temperature control type (Compensation or Direct) and selected room sensor.
Page 105
12.1.8 Auto Cooling Mode Operation Limit Compressor 19°C 16°C Compressor Outdoor Ambient Temperature Auto Mode Cooling Only operation will start once the outdoor ambient temperature reaches 19°C and compressor will continue to run until the outdoor ambient temperature drops to 16°C. ...
Page 106
Characteristic of heat pump thermos ON/OFF under tank mode condition: 1) Water Outlet Thermo Condition Heat pump thermos OFF temperature: 1. Heat pump thermo OFF temperature = Target Water outlet temperature + (2°C) 2. Water outlet temperature > heat pump thermo OFF temperature for continuously 3 minutes, heat pump OFF but water pump continue ON.
Page 107
Room heater turn OFF condition: Tank temperature > tank set temperature for continuously 15 seconds OR Heat pump thermo ON OR Mode change or operation is off by control panel. Tank Heater control Tank heater only operate to tank side if tank heater ON.
Page 108
12.1.10 Heat + Tank Mode Operation 1. 3 ways valve control: 3 ways valve switch to room side during room heat-up interval and switch to tank side during tank heat-up interval. Both modes will switch alternately. Tank mode is the initial running mode of Heat + Tank mode. 2.
Page 109
12.1.11 Cool + Tank Mode Operation 1. 3 ways valve control: 3 ways valve switch to room side during room cooling interval and switch to tank side during tank heat-up interval. Both mode will switch alternately. Tank mode is the initial mode of cool + tank mode. 2.
Page 110
5. 2 ways vale is close. 6. Indoor water pump control: Indoor water pump always turn ON if room heat pump thermo ON OR Tank thermo ON. 12.1.12 Outdoor Fan Motor Operation Outdoor fan motor is adjusted according to operation condition. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.
12.2 Water Pump 12.2.1 Water Pump Control Once the indoor unit is ON, the water pump will be ON immediately and no error judgment for 70 seconds. However, during this 70 seconds operation, if there is any abnormality cause at outdoor or malfunction, the compressor should be OFF immediately and restart delay after 3 minutes.
Page 112
However, the following sequences do not follow maximum pump duty setting by remote control. Pump down mode Air purge mode Normal deice 1) P-Q graph for different pump HEX duty WH-SDC09H3E8 & WH-SDC12H9E8 (P - Q) Max Duty C5 12kW Rated Duty 8B Min Duty 50...
Page 113
12.2.2 Zone Water Pump Control Purpose: Water pump install at each zone to circulate the water inside each zone during buffer tank connection selected “YES” or 2 zone systems. Content: AC type water pump install for this zone water pump control. When optional PCB connected, 230V output will drive this zone pump.
Page 114
Zone Pump Control during Anti-Freeze Zone pump control during Zone Anti-Freeze Control: When Zone Anti-Freeze Flag=1, Zone Pump Turn ON. When Zone Anti-Freeze Flag=0, Zone Pump Turn OFF. Zone pump control during Indoor Anti-Freeze Control: Zone pump only ON/OFF if the Extension PCB connected and Buffer Tank select "NO" condition When Indoor Anti-Freeze flag=1, Zone Pump Turn ON When Indoor Anti-Freeze flag=0, Zone Pump Turn OFF * Pool Water Pump will not affected by both Indoor anti-freeze control or zone anti-freeze control.
12.3 Indoor Unit Safety 12.3.1 Indoor Unit Safety Control When water pump is ON, the system will start checking flow switch status (ON/OFF). If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds. If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal mode.
12.6 Indoor Back-Up Heater Control 12.6.1 Indoor Electric Heater Control Normal Heating Mode Heater On condition: a. Heater switch is ON b. After Heatpump thermo ON for [30] mins c. After water pump operate [9] mins d. Outdoor air temperature < Outdoor set temperature for heater e.
Page 117
12.6.2 Room Heater Operation during Deice Purpose: To protect the indoor Heat Exchanger from ice forming and prevent heat exchanger plate breakage. Control content: This Heater protection control will activate only if the backup heater is enable at custom setup by remote controller.
12.7 Tank Heater Control 12.7.1 Tank Heater Remote Control Setting 1) Tank heater selection: External: - Booster Heater use to heat up tank when select external Internal: - Backup Heater use to heat up tank when select internal * When select External Tank Heater, Heater Delay ON Timer need to set. (range 20 min ~ 3 hrs) 2) Tank Heater ON/OFF selection by user.
Page 119
12.7.3 Internal Heater Control at Tank Mode Internal heater turn ON condition: 1) Internal Heater select for Tank heater by remote controller 2) Tank Heater select ON by user. 3) Backup Heater Enable 4) Tank Temperature < Tank Set Temperature 5) Heat Pump Thermo OFF 6) 20 minutes from previous heater off.
12.8 Base Pan Heater Control (Optional) To enable the base pan heater function, control panel initial setting has to be manually adjusted by activating Base Pan Heater menu. There are 2 optional start condition can be selected, Type A or Type B. ...
12.10 Force Heater Mode Purpose of Force Heater Mode As a backup heat source when heat pump error. Force heater Mode control backup heater to heat up the room circuit, and turn ON back up heater or booster heater to boil up tank water base on the tank heater selection (internal or external) Force Heater Control start condition: Force heater request ON by user OR auto turn ON by remote controller during error AND...
Tank side (Tank mode) 1) When tank mode select and force heater bit received, turn ON backup heater (INTERNAL) or Booster Heater (External) depend on the tank heater selection. 2) If tank heater selection is INTERNAL, follow normal thermo judgement to switch 3 ways valve to tank side and room side.
12.12 Quiet Operation Quiet mode is use to reduce the noise of outdoor unit by reducing the frequency or fan speed. Quiet level There are 3 level (Level 1, Level 2, Level 3) to set by quick menu function on remote control. Control content Once the quiet function is select, the remote control will transmit the signal to indoor and outdoor unit.
12.14 Outdoor Ambient Thermo OFF Control Purpose Stop provides heating to room side during high outdoor ambient condition. Outdoor thermo off set temperature +3°C Outdoor thermo off set temperature +1°C Control content Heating outdoor ambient thermos OFF control only applicable when heat pump operate in heat mode. (This control will not activate when running in tank side) Heat pump and water pump will turn OFF when outdoor ambient is higher than outdoor thermo OFF set temperature.
12.15 Alternative Outdoor Ambient Sensor Control Purpose of the Alternative Outdoor Ambient Sensor: It is some possibility that the air to water heat pump unit will install at a location where the original ambient sensor is expose to direct sunlight. Therefore, another optional ambient sensor can be connect to indoor PCB and locate at new and better reading location to improve the heat pump performance.
12.17 Anti Freeze Control Anti freeze protection control menu can be set YES or NO by control panel. In heatpump system, there are 3 types of anti freeze control: 1. Expansion tank anti-freeze control Expansion tank anti freeze heater ON condition: Outdoor ambient temp.
12.18 Solar Operation (Optional) 12.18.1 Solar Operation: Solar function: This function allow user to control the solar pump to operate depend on the solar sensor reading compare to the tank installed. Solar pump will circulate the hot water energy store at solar panel to heat up the DHW Tank or Buffer Tank.
Page 128
Solar remote control setting 1) Solar Setting can only be set when the optional PCB connection is select "YES" 2) By remote controller, Setting as below list can be set for solar function operation (Installer Menu) Solar Function ("YES" or "NO) Tank Connection Direction ("DHW TANK"...
12.19 Boiler Bivalent Control Boiler is an additional or alternative heat source to heat up the room when necessary. Purpose of this control is to turn ON and turn OFF the Boiler output signal when boiler heating capacity needed in the system. Boiler is possible to connect to DHW Tank and Buffer Tank depends on the installer.
Page 130
Control detail: During operation ON at Heat Mode Boiler signal turns ON when a. Outdoor ambient < Outdoor Ambient Set AND b. Buffer tank temperature < Target Buffer Tank Temperature + [START_TEMP] for [START_TIMER] c. Heat pump operate at room side AND d.
12.20 External Room Thermostat Control (Optional) Purpose: Better room temperature control to fulfill different temperature request by external room thermostat. Recommended external room thermostat: Maker Characteristic Siemen (REV200) Touch panel Siemen (RAA20) Analog Connection of external room thermostat: Wire Connection and thermo characteristic of Siemen REV200: Setting L/L1 (H) Heat Thermo...
12.21 Three Ways Valve Control Purpose: - 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side. Control contents: 3 ways valve switch Off: During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side. 3 ways valve switch On: During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
12.23 External OFF/ON Control Communication circuit between indoor unit and external controller is as per below. External Controller mico Panasonic CN-THERMO Maximum length of communication cable is 50 meter. Control content: External Control Switch Control Panel OFF/ON...
12.24 External Compressor Switch (Optional PCB) External compressor switch port can have two purpose of control as below: a) Heat source ON/OFF function (Dip switch Pin 3 on PCB "OFF") b) Heater ON/OFF function (Dip switch Pin 3 on PCB "ON") a) Heat source ON/OFF function Purpose: Heat pump ON/OFF function is use to turn OFF the high power consumption device (Heat pump, &...
12.25 Heat/Cool Switch (Optional PCB) Purpose: User can switch the running mode from heat to cool or cool to heat through external installed Heat/Cool switch. This kind of heat / cool switch may built in inside the field supply room remocon as well. Control contents: Heat/Cool Switch can only be set when Cool Function is "enable"...
12.26 SG Ready Control (Optional PCB) Purpose: To set ON/OFF of heat pump and target temperature by digital input of third party device if necessary in field. Optional PCB Remote Station + DI2 Com + DI1 Com - Com Remote control setting For this function, following items need to be set on R/C (installer menu) –...
Page 137
While digital input is detected " 10 " (Capacity 1) Setting temperature for heating and Tank is changed. However, which setting temperature is change depend on system setting. If Buffer selection is “YES” Room side New Target Buffer tank temperature = Current Target Buffer Tank Temperature * Remote Control setting ("...
12.27 Demand Control (Optional PCB) Remote control setting: When Optional PCB connection select 'YES", Demand Control function can select "YES" or "NO". Purpose: After the demand control select YES, below control will activated. 0-10V Demand control 0-10V Demand control Demand control is use to reduce the current usage of heat pump unit by third party device. Control start condition: Select “YES”...
12.28 Holiday Mode Purpose: Promotes energy saving by allowing the user to stop the system during holiday and enables the system to resume at the preset temperature after holiday. Control details: Indoor operate the unit according running mode request. Target temperature will follow holiday setting temperature.
13. Protection Control 13.1 Protection Control for All Operations 13.1.1 Time Delay Safety Control The compressor will not start for three minutes after stop of operation. 13.1.2 30 Seconds Forced Operation Once the compressor starts operation, it will not stop its operation for 30 seconds. However, it can be stopped using control panel at indoor unit.
Page 141
13.1.5 High Pressure Sensor Control Purpose: - To protect the system operation. Detection period: - After compressor on for 1 minute. Detection conditions: - When abnormal high voltage detection, 5 V or when open circuit detection 0V for 5 seconds continuously. ...
13.2 Protection Control for Heating Operation 13.2.1 Outdoor Air Temperature Control The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid compressor overloading. 13.2.2 Deice Operation When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor stop.
13.3 Protection Control for Cooling Operation 13.3.1 Outdoor Air Temperature Control The Compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below. This control will begin 1 minute after the compressor starts. ...
14. Servicing Mode 14.1 How to Take Out Front Plate Please follow the steps below for take out front plate. Before removing the front plate of indoor unit, always switch off all power supply (i.e. indoor unit power supply, heater power supply and Tank Unit power supply). Remove the 2 mounting screws which located at bottom of the front plate.
14.5 How To Adjust Pump Speed 11 : 00am, M on Press & scroll to “Installer setup” [Screen 4] - Press SW to select & confirm maximum duty. (Range: 0 x40~0xFF) [Screen 5] - Range (0.1~99.9)L/min [Screen 6] Press SW to select & confirm operation...
14.8 EEPROM Factory Default Data Setup Procedure - EEPROM default data setup is only possible during initialization process. - Press simultaneously for 5secs continuously, initialization process will stop & EEPROM default data setup process will start. During EEPROM default data setup process, display should be as shown below. 0.2s Later 0.2s...
14.9 Dry Concrete Setup 11 : 00am, M on Press & scroll to “Installer setup” [Screen 4] [Screen 5] [Screen 6] Once ‘ON’ is confirm, stage 1 setup will start Every day stage will increment with its respective setup Next Page...
Page 151
- Press button to select no. of stages. - Press to store latest status. - Press button, display will return to [Screen 6]. - If suppose to select 10 stages, then setup will start from stage 1/10. - Press button to select set temperature. - Press button to store latest status.
15. Maintenance Guide In order to ensure safety and optimal performance of the unit, seasonal inspections on the unit, functional check of RCCB/ELCB, field wiring and piping have to be carried out at regular intervals. This maintenance should be carried out by authorized dealer.
Reset overload protector Overload Protector a serves the safety purpose to prevent the water over heating. When the Overload Protector a trip at high water temperature, take below steps to reset it. a. Take out the cover. b. Use a test pen to push the centre button gently in order to reset the Overload Protector. c.
Page 154
15.1.3 Custom menu Setting method of Custom menu Custom menu 17:26, Wed Cool mode Back-up heater Reset energy monitor Select Confirm Please press for 10 sec. Items that can be set Cool mode (Set With/Without Cooling function) Default is without (CAUTION) As with/without Cool mode may affect electricity application, please be careful and do not simply...
16. Troubleshooting Guide 16.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan.
16.2 Relationship between the Condition of the Air-to-Water Heatpump Indoor and Outdoor Units and Pressure and Electric Current Heating Mode Cooling Mode Condition of the Air-to-Water Heatpump Low Pressure High Pressure Electric current Low Pressure High Pressure Electric current indoor and during operation during operation outdoor units...
16.3 Breakdown Self Diagnosis Function 16.3.1 Self Diagnosis Function (Three Digits Alphanumeric Code) When abnormality occur during operation, the system will stop operation, and OFF/ON control panel LED will blink and error code will display on the control panel. ...
Page 158
Press button and select “System Check” Press SW to select [Screen 4] “Error history” Display last 4 error retrieved from EEPROM...
16.5 Self-diagnosis Method 16.5.1 Connection Capability Rank Abnormality (H12) Malfunction Decision Conditions: During startup operation of cooling and heating, the capability rank of indoor checked by the outdoor is used to determine connection capability rank abnormality. Malfunction Caused: Wrong model interconnected. Wrong indoor unit or outdoor unit PCB (main) used.
Page 162
16.5.2 Compressor Tank Temperature Sensor Abnormality (H15) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the compressor tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 163
16.5.3 Water Pump Abnormality (H20) Malfunction Decision Conditions: During startup and operation of cooling and heating, the rotation speed detected by the IPM of water pump motor during water pump operation is used to determine abnormal water pump (feedback of rotation > 6,000rpm or < 1,000rpm).
Page 164
16.5.4 Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor refrigerant liquid temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
Page 165
16.5.5 Service Valve Error (H27) Malfunction Decision Conditions: During cooling operation, when:- [a] Indoor refrigerant pipe temperature at compressor startup - present indoor refrigerant pipe temperature < 2°C [b] Present high pressure - high pressure at compressor startup < 5kg/cm **Judgment only for first time cooling operation and not during pump down operation.
Page 166
16.5.6 Abnormal Solar Sensor (H28) Malfunction Caused: Faulty connector connection. Faulty solar sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component. Caution Abnormal solar sensor ●...
Page 167
16.5.7 Abnormal Swimming Pool Sensor (H31) Malfunction Caused: Faulty connector connection. Faulty swimming pool sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component. Caution Abnormal swimming pool sensor Correct connection...
Page 168
16.5.8 Abnormal Buffer Tank Sensor (H36) Malfunction Caused: Faulty connector connection. Faulty buffer tank sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component. Caution Abnormal buffer tank sensor ●...
Page 169
Troubleshooting: always switch off the power before remove and connect the component. Caution Brand code not match ● Use only Panasonic units. Check the brand of indoor and outdoor unit both Panasonic? ● Change to Panasonic unit. Change PCB outdoor...
Page 170
16.5.10 Compressor Low Pressure Protection (H42) Malfunction Decision Conditions: During operation of heating and after 5 minutes compressor ON, when outdoor pipe temperature below -29°C or above 26°C is detected by the outdoor pipe temperature sensor. Malfunction Caused: Dust accumulation on the outdoor unit heat exchanger. Air short circuit at outdoor unit.
Page 171
16.5.11 Abnormal Zone 1 Sensor (H43) Faulty connector connection. Faulty buffer tank sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component. Caution Abnormal zone 1 sensor Check the turn off power check connector connection...
Page 172
16.5.12 Abnormal Zone 2 Sensor (H44) Malfunction Caused: Faulty connector connection. Faulty buffer tank sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component. Caution Abnormal zone 2 sensor Turn off power check connector connection normal?
Page 173
16.5.13 Water Flow Switch Abnormality (H62) Malfunction Decision Conditions: During operation of cooling and heating, the water flow detected by the indoor water flow switch is used to determine water flow error. Malfunction Caused: Faulty water pump. Water leak in system. Faulty connector connection.
Page 174
16.5.14 Outdoor High Pressure Abnormality (H64) Malfunction Decision Conditions: During operation of cooling and heating, when the outdoor high pressure sensor output signal is 0 Vdc or 5 Vdc. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 4 times in 20 minutes.
Page 175
16.5.15 Deice Circulation Error (H65) Malfunction Decision Conditions: During startup and operation of deice (mode 2), the water flow (> 10l/min) detected by the water flow switch is used to determine deice circulation error. Malfunction Caused: Water flow in air-to-water heatpump indoor unit circuitry. Faulty indoor unit water flow switch.
Page 176
16.5.16 Abnoraml External Thermistor 1 (H67) Malfunction Caused: Faulty connector connection. Faulty room temperature zone 1 sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component. Caution Abnormal external thermistor 1 ●...
Page 177
16.5.17 Abnoraml External Thermistor 2 (H68) Malfunction Caused: Faulty connector connection. Faulty room temperature zone 2 sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component. Caution Abnormal external thermistor 2 ●...
Page 178
16.5.18 Indoor Backup Heater OLP Abnormality (H70) Malfunction Decision Conditions: During operation of indoor backup heater, when no power supplies to indoor backup heater or OLP open circuit. Malfunction Caused: Faulty power supply connector connection. Faulty connector connection. Faulty indoor backup heater overload protector (OLP). Faulty indoor unit PCB (main).
Page 179
16.5.19 Tank Temperature Sensor Abnormality (H72) Malfunction Decision Conditions: When tank connection is set to ON, the temperatures detected by the tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 180
16.5.20 PCB Communication Error (H74) Malfunction Decision Conditions: When External PCB connection is select “YES” and no communication with External PCB micon for 10 seconds and above. Malfunction Caused: Faulty connector connection. Faulty indoor PCB. Faulty indoor sub PCB. Abnormality Judgment: After 1 minute operation started.
Page 181
16.5.21 Indoor-Control Panel Communication Abnormality (H76) Malfunction Decision Conditions: During standby and operation of cooling and heating, indoor-control panel error occur. Malfunction Caused: Faulty connector connection. Faulty control panel. Faulty indoor unit PCB (main). For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component.
Page 182
16.5.22 Indoor/Outdoor Abnormal Communication (H90) Malfunction Decision Conditions: During operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused: Faulty outdoor unit PCB (main). Faulty indoor unit PCB (main). Indoor-outdoor signal transmission error due to wrong wiring.
Page 183
16.5.23 Tank Booster Heater OLP Abnormality (H91) Malfunction Decision Conditions: During operation of tank booster heater, and tank booster heater OLP open circuit. Malfunction Caused: Faulty connector connection. Faulty tank booster heater overload protector (OLP). Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 60 seconds.
Page 184
16.5.24 Unspecified Voltage between Indoor and Outdoor (H95) Malfunction Decision Conditions: The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused: Insufficient power supply. Faulty outdoor unit PCB (noise filter/main). For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component.
Page 185
16.5.25 Outdoor High Pressure Protection (H98) Malfunction Decision Conditions: During operation of heating, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 2/3 way closed.
Page 186
16.5.26 Indoor Freeze-up Protection (H99) Malfunction Decision Conditions: During anti-freezing control in cooling operation, when the indoor refrigerant liquid temperature < 0°C. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 2 way valve partially closed. Clogged expansion valve or strainer.
Page 187
16.5.27 Outdoor High Pressure Switch Activate (F12) Malfunction Decision Conditions: During operation of cooling and heating, when pressure 4.5 MPa and above is detected by outdoor high pressure switch. Malfunction Caused: Dust accumulation on the outdoor unit heat exchanger. Air short circuit at outdoor unit. Faulty water pump.
Page 188
16.5.28 Compressor Rotation Failure (F14) Malfunction Decision Conditions: A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused: Compressor terminal disconnect. Faulty outdoor unit PCB (main). Faulty compressor. Abnormality Judgment: Continue 4 times in 20 minutes. For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component.
Page 189
16.5.29 Outdoor Fan Motor (DC Motor) Mechanism Locked (F15) Malfunction Decision Conditions: The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm). Malfunction Caused: Operation stop due to short circuit inside the fan motor winding.
Page 190
16.5.30 Input Over Current Detection (F16) Malfunction Decision Conditions: During operation of cooling and heating, when outdoor current above 11.8 A (UD09HE8, UD12HE8) and 16.5 A UD16HE8) is detected by the current transformer (CT) in the outdoor unit PCB. Malfunction Caused: Excessive refrigerant.
Page 191
16.5.31 Compressor Overheating (F20) Malfunction Decision Conditions: During operation of cooling and heating, when temperature above 107°C is detected by the compressor tank temperature sensor. Malfunction Caused: Faulty compressor tank temperature sensor. 2/3 way valve closed. Refrigerant shortage (refrigerant leakage). Clogged expansion valve or strainer.
Page 192
16.5.32 IPM Overheating (F22) Malfunction Decision Conditions: During operation of cooling and heating, when temperature 95°C is detected by the outdoor IPM temperature sensor. Malfunction Caused: Faulty outdoor unit fan motor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 30 minutes. For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component.
Page 193
16.5.33 Output Over Current Detection (F23) Malfunction Decision Conditions: During operation of cooling and heating, when outdoor DC current is above 34 A (UX09,12HE8) or 54 A ± 4.0 A (UD16HE8) is detected by the IPM DC Peak sensing circuitry in the outdoor unit PCB (main). Malfunction Caused: Faulty outdoor unit PCB (main).
Page 194
16.5.34 Refrigeration Cycle Abnormality (F24) Malfunction Decision Conditions: During operation of cooling and heating, compressor frequency > Frated. During operation of cooling and heating, running current: 0.65 A < I < 1.65 A. During operation of cooling, water inlet temperature - indoor refrigerant liquid temperature < 5°C. During operation of heating, indoor refrigerant liquid temperature - water inlet temperature <...
Page 195
16.5.35 Four Way Valve Abnormality (F25) Malfunction Decision Conditions: During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C. During cooling operation, when the indoor pipe temperature of thermostat ON indoor unit > 45°C. Malfunction Caused: Faulty sensor.
Page 196
16.5.36 Outdoor High Pressure Switch Abnormal (F27) Malfunction Decision Conditions: During compressor stop, and outdoor high pressure switch is remain opened. Malfunction Caused: Faulty connector connection. Faulty switch. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 1 minute. For safety reason and to prevent component breakdown, Troubleshooting: always switch off the power before remove and connect the component.
Page 197
16.5.37 Low Discharge Superheat (F29) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Faulty High Pressure Switch Refrigerant shortage (refrigerant leakage).
Page 198
16.5.38 Indoor Water Outlet Temperature Sensor 2 Abnormality (F30) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet temperature sensor 2 are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
Page 199
16.5.39 Outdoor Air Temperature Sensor Abnormality (F36) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 200
16.5.40 Indoor Water Inlet Temperature Sensor Abnormality (F37) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water inlet temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
Page 201
16.5.41 Outdoor Discharge Pipe Temperature Sensor Abnormality (F40) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
Page 202
16.5.42 Power Factor Correction (PFC) Abnormality (F41) Malfunction Decision Conditions: During operation of cooling and heating, when the PFC protection circuitry in the outdoor unit PCB (main) senses abnormal high DC voltage level. Malfunction Caused: Power supply surge. Compressor windings not uniform. Faulty outdoor unit PCB (main).
Page 203
16.5.43 Outdoor Pipe Temperature Sensor Abnormality (F42) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 204
16.5.44 Outdoor Defrost Temperature Sensor Abnormality (F43) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor defrost temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 205
16.5.45 Indoor Water Outlet Temperature Sensor Abnormality (F45) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet temperature sensor are used to determine sensor errors. Malfunction Caused: Faulty connector connection. Faulty sensor.
Page 206
16.5.46 Outdoor Current Transformer Open Circuit (F46) Malfunction Decision Conditions: A current transformer (CT) open circuit is detected by checking the compressor running frequency ( rated frequency) and CT detected input current (< 0.65 A) for continuously 20 seconds. Malfunction Caused: CT defective.
Page 207
16.5.47 Cooling High Pressure Overload Protection (F95) Malfunction Decision Conditions: During operation of cooling, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Dust accumulation in the outdoor unit heat exchanger. Air short circuit at outdoor unit. 2 way valve closed.
17. Disassembly and Assembly Instructions WARNING High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 17.1 To Remove Front Plate Hook...
17.3 To Open Control Board Cover Screws Screws 1. Remove 6 screws from the Control Board Cover. 17.4 To Remove Control Panel Insert the driver and slightly turn. Flat-blade screwdriver Bottom case 1. Remove the top case from the bottom case. 2.
17.5 To Remove RCCB 1. Disconnect lead wires (Black and White). For model SDC12/16H9E8 2. Remove screws to remove RCCB 17.6 To Remove Transformer and Electronic Controller Board 2. Remove 2 screws to remove Reactor Electronic Controller Board Reactor 3. Disconnect all connectors and lead wire from the electronic controller board.
17.7 To Open Control Board Remove screw. 17.8 To Remove Pressure Relief Valve, Air Purge Valve and Flow Sensor Flow Sensor Air Purge Valve 4. Turn the Air Purge Valve anti-clockwise then remove. 5. Detach the flow sensor lead wire. 6.
During reinstall Flow Sensor Make sure the flow sensor is not slanting Make sure arrow point to left 17.9 To Remove Water Pump and Bottle Complete 1. Disconnect CN-PUMP1 from electronic controller. 2. Loosen the nut. 3. Remove 2 screws. Water Pump 4.
17.10 To Remove Filter 1. Set 2 valve for the Water Filter Set to “CLOSE”. Water Filter 2. Pull up the Water Filter set. 3. Remove the retaining ring, then remove the the Water Filter.
18. Technical Data 18.1 Operation Characteristics 18.1.1 WH-SDC09H3E8 WH-UD09HE8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 9.200...
Page 215
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 10.000 9.000 8.000 7.000 6.000 5.000 Outdoor Temperature (°C) 3.000 2.500 2.000...
Page 216
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 19°C Indoor water outlet temperature : 14°C Piping length : 7 m 12.000 11.000 10.000 9.000 8.000 7.000 Outdoor Temperature (°C) 3.500 3.000 2.500...
Page 217
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 23°C Indoor water outlet temperature : 18°C Piping length : 7 m 9.500 8.500 7.500 6.500 5.500 4.500 Outdoor Temperature (°C) 3.000 2.500 2.000...
Page 218
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 10.000 9.500 9.000 8.500 8.000 7.500 Piping Length (m) 2.100 2.000 1.900...
Page 219
Cooling Characteristics at Different Piping Length Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 7.500 7.000 6.500 6.000 5.500 5.000 Piping Length (m) 2.500 2.400 2.300...
Page 220
18.1.2 WH-SDC12H9E8 WH-UD12HE8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 13.000 12.000 11.000 10.000 9.000 8.000 Outdoor Temperature (°C)
Page 221
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 12.500 11.500 10.500 9.500 8.500 7.500 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 222
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 19°C Indoor water outlet temperature : 14°C Piping length : 7 m 16.000 15.000 14.000 13.000 12.000 11.000 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 223
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 23°C Indoor water outlet temperature : 18°C Piping length : 7 m 12.000 11.000 10.000 9.000 8.000 7.000 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 224
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 12.500 12.000 11.500 11.000 10.500 10.000 Piping Length (m) 4.000 3.500 3.000...
Page 225
Cooling Characteristics at Different Piping Length Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 11.000 10.000 9.000 8.000 7.000 6.000 Piping Length (m) 3.800 3.700 3.600...
Page 226
18.1.3 WH-SDC16H9E8 WH-UD16HE8 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 17.500 16.000 14.500 13.000 11.500 10.000 Outdoor Temperature (°C)
Page 227
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 16.000 14.000 12.000 10.000 8.000 6.000 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 228
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 19°C Indoor water outlet temperature : 14°C Piping length : 7 m 22.000 20.000 18.000 16.000 14.000 12.000 Outdoor Temperature (°C) 6.500 5.500 4.500...
Page 229
Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 23°C Indoor water outlet temperature : 18°C Piping length : 7 m 17.000 15.000 13.000 11.000 9.000 7.000 Outdoor Temperature (°C) 5.500 4.500 3.500...
Page 230
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 17.000 16.500 16.000 15.500 15.000 14.500 Piping Length (m) 4.200 4.000 3.800...
Page 231
Cooling Characteristics at Different Piping Length Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C Piping length : 7 m 13.500 12.500 11.500 10.500 9.500 8.500 Piping Length (m) 5.000 4.900 4.800...
18.2 Heating Capacity Table 18.2.1 WH-SDC09H3E8 WH-UD09HE8 Water Out (°C) Input Input Input Input Input Input Capacity Capacity Capacity Capacity Capacity Capacity Outdoor Air (°C) Power Power Power Power Power Power 8650 3060 8300 3210 7950 3410 7600 3610 7150...
18.3 Cooling Capacity Table 18.3.1 WH-SDC09H3E8 WH-UD09HE8 Water In (°C) Water Out (°C) Outdoor Air (°C) Capacity (W) Input Power (W) Capacity (W) Input Power (W) Capacity (W) Input Power (W) 7500 1150 9100 1200 7000 1130 8350 1770 10900...
19. Exploded View and Replacement Parts List 19.1 Indoor Unit Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 235
<Model: WH-SDC09H3E8 > REF. SAFETY DESCRIPTION & NAME QTY. WH-SDC09H3E8 REMARK BASE PAN CWD521450 HOT WATER COIL - COMPLETE ACXB90C00220 RECEIVER CWB141039 CATCHER CWH601011 FLARE NUT (5/8) CWT251064 FLARE NUT CWT251061 FLARE NUT (1/4) CWT251063 WATER PUMP CWB532116 FERRITE CORE...
Page 236
<Model: WH-SDC12H9E8 WH-SDC16H9E8> REF. SAFETY DESCRIPTION & NAME QTY. WH-SDC12H9E8 WH-SDC16H9E8 REMARK BASE PAN CWD521450 ← HOT WATER COIL - COMPLETE ACXB90C00220 ACXB90C00250 RECEIVER CWB141039 ← CATCHER CWH601011 ← FLARE NUT (5/8) CWT251064 ← FLARE NUT CWT251061 ← FLARE NUT (1/4) CWT251063 ←...
19.2 Outdoor Unit Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 238
Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 239
Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.