SAFETY PRECAUTIONS • Before doing repair work, please read the " SAFETY PRECAUTIONS" carefully and fully understand them. • The precautionary items here are divided into " Warning" and " Caution" items. Items in particular which may cause death or serious injury to the service personnel if the work is not performed correctly, are included in the "...
Page 3
Warning If refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite. Prohibit If refrigerant gas leaks during the work, ventilate the room. If refrigerant gas catches fire, harmful gas may be generated. Do not mix any gas other than the specified refrigerant gas in the refrigerating cycle.
Table of Contents Page ......................SAFETY PRECAUTIONS ........................TABLE OF CONTENTS ..................APPLICABLE MULTI-OUTDOOR UNITS ........................1. OPERATING RANGE 2. SPECIFICATIONS ......................2-1. Unit Specifications ..................2-2. Major Component Specifications ..................2-3. Other Component Specifications ........................3. DIMENSIONAL DATA 4. REFRIGERANT FLOW DIAGRAM ....................
1. OPERATING RANGE Combination with cooling outdoor unit CU-3KS19NBU, CU-4KS24NBU or CU-4KS31NBU Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 95 °F DB / 71 °F WB 115 °F DB Cooling Minimum 67 °F DB / 57 °F WB 14 °F DB...
2-2. Major Component Specifications 2-2-1. Indoor Unit Indoor Unit CS-MKS7NKU Control PCB Part No. CB-CU-MKS7NKU Controls Microprocessor Control Circuit Fuse 250V 3A Type Cross-Flow Q'ty ... Dia. and Length inch (mm) 1 ... D3-5/8 / L24-31/32 (D92 / L634) Fan Motor...
Page 18
Indoor Unit CS-MKS9NKU Control PCB Part No. CB-CU-MKS9NKU Controls Microprocessor Control Circuit Fuse 250V 3A Type Cross-Flow Q'ty ... Dia. and Length inch (mm) 1 ... D3-5/8 / L24-31/32 (D92 / L634) Fan Motor Type DC Motor Model ... Q'ty SIC-41CVJ-D847-4 ...
Page 19
Indoor Unit CS-MKS12NKU Control PCB Part No. CB-CU-MKS12NKU Controls Microprocessor Control Circuit Fuse 250V 3A Type Cross-Flow Q'ty ... Dia. and Length inch (mm) 1 ... D3-5/8 / L24-31/32 (D92 / L634) Fan Motor Type DC Motor Model ... Q'ty SIC-41CVJ-D847-4 ...
Page 20
Indoor Unit CS-MKS18NKU Control PCB Part No. CB-CU-MKS18NKU Controls Microprocessor Control Circuit Fuse 250V 3A Type Cross-Flow Q'ty ... Dia. and Length inch (mm) 1 ... D3-5/8 / L33-9/32 (D92 / L845) Fan Motor Type DC Motor Model ... Q'ty SIC-41CVJ-D847-3 ...
Page 21
Indoor Unit CS-MKS24NKU Control PCB Part No. CB-CU-MKS24NKU Controls Microprocessor Control Circuit Fuse 250V 3A Type Cross-Flow Q'ty ... Dia. and Length inch (mm) 1 ... D3-5/8 / L33-9/32 (D92 / L845) Fan Motor Type DC Motor Model ... Q'ty SIC-41CVJ-D847-3 ...
2-3. Other Component Specifications Quantity of Sensor Model No. Sensor Name of sensor CS-MKS7NKU CS-MKS9NKU CS-MKS12NKU CS-MKS18NKU CS-MKS24NKU PTM-D51H- S3 TH2 Indoor air temp sensor PTM-D51H- S3-2 TH2 (10) (15) (20) (25) (30) (35) (40) Temperature °F (°C) Quantity of Sensor Model No.
7. FUNCTIONS 7-1. Operation Functions Emergency operation SENSOR DRY Emergency operation is available when the remote During DRY operation, the system adjusts the room temperature and fan speed according to the conditions in the controller malfunctions, has been lost, or otherwise room, in order to maintain a comfortable room environment.
HIGH POWER NIGHT SETBACK This function acts to raise the power but keeps the AC system in When NIGHT SETBACK operation is set, the temperature and the same operating mode. fan speed settings will be adjusted automatically to allow This function is set with the HIGH POWER button on the remote comfortable sleep.
7-2. Protective Functions Freeze prevention During COOL or DRY operation, freezing is detected and operation is stopped when the temperature of the indoor heat exchanger matches the conditions below. 1. Freeze-prevention operation is engaged when the temperature of the indoor heat exchanger is below 43°F(6°C). 2.
8. TROUBLESHOOTING (BEFORE CALLING FOR SERVICE) 8-1. Precautions before Performing Inspection or Repair After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair. High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge (charging voltage DC 310V) even after the power is turned OFF, and some time is required for the charge to dissipate.
Page 36
(1) Self-diagnostics Lamps INDOOR UNIT (1) OPERATION lamp (2) TIMER lamp (3) QUIET lamp OPERATION button REMOTE CONTROL receiver Since the indications cover various units, the corresponding parts listed below may not be present in some models..OFF ..BLINKING ..
Page 37
(2) If the self-diagnostics function fails to operate No indicators illuminate and the Check the indoor unit. indoor fan does not rotate. Check the power voltage. Blown Is the fuse blown? Normal Replace the circuit board or the fuse. Replace the controller.
8-3. Checking the Indoor and Outdoor Units (1) Checking the indoor unit Control Check items (unit operation) • The rated voltage must be present between inter-unit wirings 1 and 2. Use the remote controller to operate the unit in "TEST run" mode. To determine •...
Page 39
(3) How to Identify a Serial Communication Error If the lamps on the main body show the following conditions after the completion of self-diagnosis, a communication error between the indoor unit and outdoor unit might be considered. In such a case, identify the breakdown section by using the following procedure. NOTE Refer to "Method of Self-Diagnosis"...
Page 40
(3-2) Condition: E12 1. Disconnect the inter-unit wiring on the indoor unit side. 2. Operate the system in TEST RUN mode. Then, five minutes later, perform the self-diagnosis. Condition: E01 What is the self-diagnosis result ? Condition: E12 1. Disconnect the inter-unit wiring on the outdoor An error in the P.
8-4. Trouble Diagnosis of Fan Motor 8-4-1. Indoor Fan Motor This indoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resistance, and the following procedure should be used to check the motor. To perform diagnosis, operate the unit in cooling mode with indoor fan speed "High".
8-5. Noise Malfunction and Electromagnetic Interference An inverter A/C operates using pulse signal control and high frequencies. Therefore, it is susceptible to the effects of external noise, and is likely to cause electromagnetic interference with nearby wireless devices. A noise filter is installed for ordinary use, preventing these problems. However, depending on the installation conditions, these effects may still occur.
Operating Instructions Split System Air Conditioner Model No. Indoor Units Outdoor Units CS-MKS7NKU CU-3KS19NBU CS-MKS9NKU CU-4KS24NBU CS-MKS12NKU CU-4KS31NBU This air conditioner uses the refrigerant R410A. Before operating the unit, read these operating instructions thoroughly and keep them for future reference.
FEATURES This air conditioner is an inverter type unit that automatically adjusts capability as appropriate. Details on these functions are provided below; refer to these descriptions when using the air conditioner. • Microprocessor Controlled Operation • Air Sweep Control The interior compartment of the remote controller This function moves a flap up and down in the air outlet, contains several features to facilitate automatic operation, directing air in a sweeping motion around the room and...
INSTALLATION LOCATION • We recommend that this air conditioner be installed properly by qualified installation technicians in accordance with the Installation Instructions provided with the unit. • Before installation, check that the voltage of the electric supply in your home or office is the same as the voltage shown on the nameplate.
Page 48
• To prevent possible hazards from insulation failure, the unit must be grounded. • Do not clean inside the indoor and outdoor units by users. Engage authorized dealer or specialist for cleaning. • In case of malfunction of this appliance, do not repair by yourself. Contact to the sales dealer or service dealer for a repair.
NAMES OF PARTS Air Intakes INDOOR UNIT Air Outlet Remote Controller Drain Hose Refrigerant Tubes OUTDOOR UNIT Air Outlet This illustration is based on the external view of a standard model. NOTE Consequently, the shape may differ from that of the air conditioner which you have selected.
Page 50
UNIT DISPLAY AND OPERATION BUTTON INDOOR UNIT IMPORTANT OPERATION lamp TIMER lamp Avoid using radio equipment QUIET lamp QUIET such as mobile phone near (within 4 ft. (1.2m)) the remote control receiver. Some radio OPERATION button equipment may cause malfunction of the unit. If the trouble happens, disconnect power and restart REMOTE CONTROL receiver...
Page 51
REMOTE CONTROLLER (DISPLAY) Displayed when transmitting data Displayed when indoor unit sensor is in use Displayed when setting temperature Displayed when temperature is shown Displayed when setting timer Displayed when the time display is set to 12-hour time. Symbols (1) Operation mode (4) Timer 24-hour clock with ON/OFF MILD DRY ......
REMOTE CONTROLLER Sensor Transmitter (Cover closed) Display ON/OFF operation button QUIET button 1 HR. TIMER button Temperature setting buttons (TEMP.) MODE selector button FAN SPEED selector button NIGHT SETBACK button FLAP button HIGH POWER button ON TIME Advance button OFF TIME Advance button setting setting...
Page 53
REMOTE CONTROLLER (CONTINUED) Temperature setting buttons Press the button to increase the set temperature. (TEMP.) Press the button to reduce the set temperature. The temperature setting changes by 1 °C or 2 °F each time one of the TEMP. buttons is pressed. MODE selector button Use this button to select DRY, COOL or FAN mode.
REMOTE CONTROLLER (CONTINUED) Temperature Display Selector This switches the temperature display between °C and °F. button Time Display Selector button This switches the time display between 24-hour time and 12-hour time. ACL button (ALL CLEAR) Puts the remote controller into pre-operation status. Always press this button after replacing the batteries.
Page 55
USING THE REMOTE CONTROLLER (CONTINUED) How to Use the Remote When using the remote controller, always point the unit’s transmitter head directly Controller at the air conditioner’s receiver. Air Conditioner (Indoor unit) Receiver Remote Controller (Transmitter head) Remote Controller Installation The remote controller may be operated either from a non-fixed position or from a Position wall-mounted position.
OPERATION WITH THE REMOTE CONTROLLER 1. Operation STEP 2 STEP 3 STEP 1 STEP 4 STEP 5 NOTE Check that the circuit breaker on the power panel is turned on. Press the setting buttons as described below and change the settings as desired. STEP 1 Press the MODE selector button and select the desired mode.
OPERATION WITH THE REMOTE CONTROLLER (CONTINUED) • Choose the best position in the room for the remote controller, which also acts NOTE as the sensor for room comfort and transmits the operating instructions. Once you’ve found this best position, always keep the remote controller there. •...
OPERATION WITH THE REMOTE CONTROLLER (CONTINUED) 4. Night Setback Mode Night Setback Mode is used for saving energy. Press the NIGHT SETBACK button while unit is operating. mark appears in the display. To release the night setback function, press the NIGHT SETBACK button again. NOTE Pressing the MODE selector button cancels Night Setback mode.
OPERATION WITH THE REMOTE CONTROLLER (CONTINUED) 5. QUIET Mode QUIET Mode is used to reduce the fan sound of the indoor unit. Press the QUIET button. mark appears in the display. To cancel, press QUIET button again. • In QUIET Mode, the fan rotates at a slower speed than the fan speed setting. •...
SPECIAL REMARKS ‘‘DRY’’ ( ) Operation How it works? • Once the room temperature reaches the level that was set, the unit’s operation frequency is changed automatically. • During DRY operation, the fan speed automatically runs at lower speed for providing a comfortable breeze.
SETTING THE TIMER In the descriptions below, the following settings are used for the temperature and NOTE time indicator selector button on the bottom front section of the remote controller. • Temperature: °F • Time: AM, PM 1. How to set the present (Example) To set to 10:30 pm.
Page 62
SETTING THE TIMER (CONTINUED) 3. How to set the ON time (Example) To start operation at 7:10 am. Operation Indication 1. Press the ON TIME setting The timer indication is displayed, button once. and the present ON time is shown. 2.
USING THE 1-HOUR OFF TIMER 1. 1-Hour OFF Timer This function causes the unit to operate for one hour and then stop, regardless of whether the unit is on or off when this button is pressed. indicator in the display indicates that this function is operating. Setting procedure: Regardless of whether the unit is operating or stopped, press the 1 HR.
ADJUSTING THE AIRFLOW DIRECTION 1. Horizontal The horizontal airflow can be adjusted by moving the vertical vanes with your hands to the left or right. When the humidity is high, the vertical vanes should be in the front CAUTION position during the cooling or dehumidifying operation. If the vertical vanes are positioned all of the way to the right or left, condensation may begin to form around the air vent and drip down.
OPERATION WITHOUT THE REMOTE CONTROLLER INDOOR UNIT If you have lost the remote controller or it has trouble, follow the steps below. When the air conditioner is not running Each time the OPERATION button is pressed, the operation mode changes cyclically.
Page 66
CARE AND CLEANING (CONTINUED) Filter The filter behind the air intake grille should be checked and cleaned at least once every two weeks. How to remove the filter 1. Grasp both ends of the air Air intake grille intake grille, and remove it by opening towards the front and pulling towards you.
CARE AND CLEANING (CONTINUED) Cleaning the main unit and • Wipe clean using a soft, dry cloth. Remote Controller • To remove stubborn dirt, moisten a cloth in warm water no hotter than 104 °F, wring thoroughly, and then wipe. •...
TROUBLESHOOTING (BEFORE CALLING FOR SERVICE) If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or service center. Trouble Possible Cause Remedy Air conditioner does not run at all. 1.
Page 70
APPENDIX B Operating Instructions CS-MKS18NKU CS-MKS24NKU (852-6-4181-215-00-1)
Page 71
Indoor Units Outdoor Units CS-MKS18NKU CU-3KS19NBU CS-MKS24NKU CU-4KS24NBU CU-4KS31NBU This air conditioner uses the refrigerant R410A. Before operating the unit, read these operating instructions thoroughly and keep them for future reference. Panasonic Corporation 1006 Kadoma, Kadoma City, Osaka, Japan 85264181215001 CV6233187631...
FEATURES This air conditioner is an inverter type unit that automatically adjusts capability as appropriate. Details on these functions are provided below; refer to these descriptions when using the air conditioner. • Microprocessor Controlled Operation • Air Sweep Control The interior compartment of the remote controller This function moves a flap up and down in the air outlet, contains several features to facilitate automatic operation, directing air in a sweeping motion around the room and...
INSTALLATION LOCATION • We recommend that this air conditioner be installed properly by qualified installation technicians in accordance with the Installation Instructions provided with the unit. • Before installation, check that the voltage of the electric supply in your home or office is the same as the voltage shown on the nameplate.
Page 74
• To prevent possible hazards from insulation failure, the unit must be grounded. • Do not clean inside the indoor and outdoor units by users. Engage authorized dealer or specialist for cleaning. • In case of malfunction of this appliance, do not repair by yourself. Contact to the sales dealer or service dealer for a repair.
NAMES OF PARTS Air Intakes INDOOR UNIT Air Outlet Remote Controller Drain Hose Refrigerant Tubes OUTDOOR UNIT Air Outlet This illustration is based on the external view of a standard model. NOTE Consequently, the shape may differ from that of the air conditioner which you have selected.
Page 76
UNIT DISPLAY AND OPERATION BUTTON INDOOR UNIT IMPORTANT OPERATION lamp TIMER lamp Avoid using radio equipment QUIET lamp QUIET such as mobile phone near (within 4 ft. (1.2m)) the remote control receiver. Some radio OPERATION button equipment may cause malfunction of the unit. If the trouble happens, disconnect power and restart REMOTE CONTROL receiver...
Page 77
REMOTE CONTROLLER (DISPLAY) Displayed when transmitting data Displayed when indoor unit sensor is in use Displayed when setting temperature Displayed when temperature is shown Displayed when setting timer Displayed when the time display is set to 12-hour time. Symbols (1) Operation mode (4) Timer 24-hour clock with ON/OFF MILD DRY ......
Page 78
REMOTE CONTROLLER Sensor Transmitter (Cover closed) Display ON/OFF operation button QUIET button 1 HR. TIMER button Temperature setting buttons (TEMP.) MODE selector button FAN SPEED selector button NIGHT SETBACK button FLAP button HIGH POWER button ON TIME Advance button OFF TIME Advance button setting setting...
Page 79
REMOTE CONTROLLER (CONTINUED) Temperature setting buttons Press the button to increase the set temperature. (TEMP.) Press the button to reduce the set temperature. The temperature setting changes by 1 °C or 2 °F each time one of the TEMP. buttons is pressed. MODE selector button Use this button to select DRY, COOL or FAN mode.
REMOTE CONTROLLER (CONTINUED) Temperature Display Selector This switches the temperature display between °C and °F. button Time Display Selector button This switches the time display between 24-hour time and 12-hour time. ACL button (ALL CLEAR) Puts the remote controller into pre-operation status. Always press this button after replacing the batteries.
Page 81
USING THE REMOTE CONTROLLER (CONTINUED) How to Use the Remote When using the remote controller, always point the unit’s transmitter head directly Controller at the air conditioner’s receiver. Air Conditioner (Indoor unit) Receiver Remote Controller (Transmitter head) Remote Controller Installation The remote controller may be operated either from a non-fixed position or from a Position wall-mounted position.
OPERATION WITH THE REMOTE CONTROLLER 1. Operation STEP 2 STEP 3 STEP 1 STEP 4 STEP 5 NOTE Check that the circuit breaker on the power panel is turned on. Press the setting buttons as described below and change the settings as desired. STEP 1 Press the MODE selector button and select the desired mode.
OPERATION WITH THE REMOTE CONTROLLER (CONTINUED) • Choose the best position in the room for the remote controller, which also acts NOTE as the sensor for room comfort and transmits the operating instructions. Once you’ve found this best position, always keep the remote controller there. •...
OPERATION WITH THE REMOTE CONTROLLER (CONTINUED) 4. Night Setback Mode Night Setback Mode is used for saving energy. Press the NIGHT SETBACK button while unit is operating. mark appears in the display. To release the night setback function, press the NIGHT SETBACK button again. NOTE Pressing the MODE selector button cancels Night Setback mode.
OPERATION WITH THE REMOTE CONTROLLER (CONTINUED) 5. QUIET Mode QUIET Mode is used to reduce the fan sound of the indoor unit. Press the QUIET button. mark appears in the display. To cancel, press QUIET button again. • In QUIET Mode, the fan rotates at a slower speed than the fan speed setting. •...
SPECIAL REMARKS ‘‘DRY’’ ( ) Operation How it works? • Once the room temperature reaches the level that was set, the unit’s operation frequency is changed automatically. • During DRY operation, the fan speed automatically runs at lower speed for providing a comfortable breeze.
SETTING THE TIMER In the descriptions below, the following settings are used for the temperature and NOTE time indicator selector button on the bottom front section of the remote controller. • Temperature: °F • Time: AM, PM 1. How to set the present (Example) To set to 10:30 pm.
Page 88
SETTING THE TIMER (CONTINUED) 3. How to set the ON time (Example) To start operation at 7:10 am. Operation Indication 1. Press the ON TIME setting The timer indication is displayed, button once. and the present ON time is shown. 2.
USING THE 1-HOUR OFF TIMER 1. 1-Hour OFF Timer This function causes the unit to operate for one hour and then stop, regardless of whether the unit is on or off when this button is pressed. indicator in the display indicates that this function is operating. Setting procedure: Regardless of whether the unit is operating or stopped, press the 1 HR.
ADJUSTING THE AIRFLOW DIRECTION 1. Horizontal The horizontal airflow can be adjusted by moving the vertical vanes with your hands to the left or right. When the humidity is high, the vertical vanes should be in the front CAUTION position during the cooling or dehumidifying operation. If the vertical vanes are positioned all of the way to the right or left, condensation may begin to form around the air vent and drip down.
OPERATION WITHOUT THE REMOTE CONTROLLER INDOOR UNIT If you have lost the remote controller or it has trouble, follow the steps below. When the air conditioner is not running Each time the OPERATION button is pressed, the operation mode changes cyclically.
Page 92
CARE AND CLEANING (CONTINUED) Filter The filter behind the air intake grille should be checked and cleaned at least once every two weeks. How to remove the filter 1. Grasp both ends of the air Air intake grille intake grille, and remove it by opening towards the front and pulling towards you.
CARE AND CLEANING (CONTINUED) Cleaning the main unit and • Wipe clean using a soft, dry cloth. Remote Controller • To remove stubborn dirt, moisten a cloth in warm water no hotter than 104 °F, wring thoroughly, and then wipe. •...
TROUBLESHOOTING (BEFORE CALLING FOR SERVICE) If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or service center. Trouble Possible Cause Remedy Air conditioner does not run at all. 1.
1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit Model No. 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation Indoor Unit Outdoor Unit CS-MKS7NKU CU-3KS19NBU INSTALLATION SITE SELECTION ....5 CS-MKS9NKU CU-4KS24NBU 2-1. Indoor Unit CS-MKS12NKU CU-4KS31NBU 2-2.
IMPORTANT! When Transporting Please Read Before Starting Be careful when picking up and moving the indoor and out- door units. Get a partner to help, and bend your knees when This air conditioning system meets strict safety and operating lifting to reduce strain on your back. Sharp edges or thin alu- standards.
Page 99
the flare and union tubes before connecting them, then that no metal scraps or bits of wiring have been left inside tighten the nut with a torque wrench for a leak-free the unit being serviced. connection. Others or re-installation, and while repairing refrigeration parts. CAUTION Handle liquid refrigerant carefully as it may cause frost- bite.
1-5. Additional Materials Required for Installation Refrigeration (armored) tape Insulated staples or clamps for connecting wire (See local codes.) Putty Refrigeration lubricant Clamps or saddles to secure refrigerant tubing Indoor unit 2. Installation Site Selection 2-1. Indoor Unit To prevent abnormal heat generation WARNING and the possibility of fire, do not place obstacles, enclosures and...
install the indoor unit more than 3.3' (1 m) away from any antenna or power lines or connecting wires used for tele- vision, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation. install in a sturdy manner to avoid increased operating noise.
Fig. 8 ment of the hose outlet. (Fig. 9a or 9b) (CS-MKS7NKU, CS-MKS9NKU, CS-MKS12NKU) (3) Before making the hole, check carefully that no 2-3/4" (70 mm) studs or pipes are directly run behind the spot to be cut.
If you are not able to line up the holes in the rear panel with the beam locations marked on the wall, (CS-MKS7NKU, CS-MKS9NKU, CS-MKS12NKU) use rawl plugs or toggle bolts to go through the holes on the panel or drill 3/16" (5 mm) dia. holes in the panel over the stud locations and then mount the rear panel.
Air intake grille 3-4. Removing and Installing the Grille 3-4-1. Indoor unit types (CS-MKS7NKU, CS-MKS9NKU, CS-MKS12NKU) Basically, these models can be installed and wired without removing the grille. If access to any internal part is needed, follow the steps as given below.
Page 106
3-4-2. Indoor unit types Grille Air intake grille (CS-MKS18NKU, CS-MKS24NKU) Basically, these models can be installed and wired with- out removing the grille. If access to any internal part is needed, follow the steps as given below. How to remove the grille (1) Grasp both ends of the air intake grille, and remove Fig.
3-5. Shape the Indoor Side Tubing (1) Arrangement of tubing by directions Frame a) Right or left tubing Cut out the corner of the right/left frame with a hacksaw or the like. (Figs. 20 and 21) Left tubing outlet b) Right-rear or left-rear tubing In this case, the corner of the frame need not be cut.
3-7. Wiring Instructions for Inter-unit Connections Rear (1) Insert the inter-unit wiring (according to local codes) Wall panel into the through-the-wall PVC pipe. Run the wiring Plastic toward the indoor side allowing approx. 10" (25 cm) cover to extend from the wall face. (Fig. 24) (2) Grasp both ends of the air intake grille, and remove Wiring it by opening towards the front and pulling towards...
Page 109
Loose wiring may cause the WARNING terminal to overheat or result in unit malfunction. A fire hazard may also exist. There- fore, be sure all wiring is tightly connected. When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal”...
3-8. Mounting (1) To install the indoor unit, mount the indoor unit onto the 2 tabs on the upper part of the rear plate. (2) Hold down the air discharge outlet and press the lower part of the indoor unit until it clicks to securely fasten to the 2 tabs on the lower part of the rear plate.
Left-side tubing Rear panel Hole in wall allowing sufficient length for connection. Then bend the tubing using a tube bender to make the attach- ment. (Fig. 38) Wide tube Bent part (2) Switch the drain hose and drain cap. Narrow tube Fig.
Page 112
To unmount indoor unit Press the 2 marks on the lower part of the indoor unit and unlatch the tabs. Then lift the indoor unit and unmount. (Fig. 42) 3-9. Drain Hose a) The drain hose should be slanted downward to the outdoors.
4. How to Test Run the Air Conditioner After turning on the power of the air conditioner, use the remote controller and follow the steps below to conduct the test run. (1) Set the remote controller in Test Run mode. (Fig.
5. Remote Controller Installation Position The remote controller can be operated from either a non-fixed position or a wall-mounted position. To ensure that the air conditioner operates correctly, do not install the remote controller in the following places: In direct sunlight Behind a curtain or other place where it is covered More than 26' (8 m) away from the air conditioner In the path of the air conditioner’s airstream...
6. Address Switch 6-1. Address Setting of the Remote Controller The address can be set in order to prevent interference between remote controllers when 2 indoor units are installed near each other. The address is normally set to “A.” To set a different address, it is necessary to change the address on the second remote controller.
7. Connecting a Home Automation Device The HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will be used, connect it to this terminal. 8. Installation Check Sheet The strength of the installation location is sufficient to support the air conditioner weight.