BACnet Gateway ® MIM-B17N Air Conditioner installation manual imagine the possibilities Thank you for purchasing this Samsung product. EN DB68-03719A(1) NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 69 2013-04-25 오전 10:14:43...
Safety Precautions This installation manual describes how to install the BACnet Gateway. For installation of other optional accessories, refer to the appropriate installation manual. Read carefully this installation manual before WARNING installation and check if the BACnet Gateway is installed correctly after installation.
Before Installing the BACnet Gateway Checks before installation BACnet Gateway IP A public IP is needed to access the BACnet Gateway over the internet. (One public IP is needed for each BACnet Gateway) A private IP may be used if the BACnet Gateway need not be accessed over the internet.
Accessories Make sure you have each item. Supplied items may vary depending on your country or service provider. BACnet Item Adapter Power cable M4 x16 Screw Gateway Quantity Shape Installation User’s manual Cable tie manual The BACnet Gateway must be installed by a trained ...
Viewing the Parts Main Parts BACnet Gateway Exterior LCD Display Shows current time and IP address. Various messages will be displayed depending on button input. LCD operation button There are 4 buttons(Menu, (Down), (Up), Set) and you can access to menu and move, check the menu.
Page 8
BACnet Gateway Cable Connection Part RS485 Communication Terminal DI Terminal1 DO Terminal4 DO Terminal3 DI Terminal2 Serial Terminal Cable tie groove Power Terminal SD Card Socket Reset Button Ethernet Terminal Name Description DI Terminal1 Digital Input connection terminal, Channel1~Channel5 DI Terminal2 Digital Input connection terminal, Channel6~Channel10 DO Terminal3 Digital Output connection terminal, Channel1~Channel5...
Viewing the Parts (Continued) Main Parts BACnet Gateway Interior Display Board 20-pin Cable Main Board 40-pin Cable Sub Board Note If you need external circuit configuration, consult with the manufacturer. Product Dimensions (Unit : mm) 64.80 NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 8 2013-04-25 오전 10:14:33...
System Architecture BMS system BMS Engineering Internet TRANE Engineering BACnet Gateway OnOff controller RS 485 Outdoor Unit Max 256 Indoor units (DVM Series) Connecting outdoor units and BACnet Gateway - You can control up to 80 outdoor units and 256 indoor units using BACnet Gateway. *Each communication channel of BACnet Gateway can be connected with 16 outdoor units.
Pulse Width: 20~400(ms) Pulse: 1~10000(Wh/Pulse) Products with ‘* ’ are not Samsung products and must be purchased separately. (Only selected power meters may be used for protocol compatibility issues.) Samsung is not responsible for BMS engineering which creates each device and objects.
Page 12
Maximum Devices Attachable Devices Max. Note Indoor Unit Tracking error occurs if exceeded OnOff Must not exceed 15 units per each RS485 controller communication terminal Must not exceed 16 units per each RS485 Outdoor unit communication terminal SIM/PIM Communication mode : IM Watt-hour Maximum 8 units can be connected to 1 SIM/PIM.
Installing the BACnet Gateway Separate the installation plate on the rear side of BACnet Gateway. Fix the installation plate on the wall using 4 screws. Hang the BACnet Gateway on the groove which is on the top of the installation plate. Installation plate Fix the installation plate and BACnet Gateway using 2 screws.
Page 14
Connecting Outdoor Unit Unfasten the 2 screws on the bottom of the BACnet Gateway front cover. Hold the bottom 2 sides of the BACnet Gateway and push downwards to slide open the cover. Connect the adapter to the power terminal. ...
Page 15
Installing the BACnet Gateway (Continued) Connecting SIM/PIM Unfasten the 2 screws on the bottom of the BACnet Gateway front cover. Hold the bottom 2 sides of the BACnet Gateway and push downwards to slide open the cover. Connect the adapter to the power terminal. ...
Setting the Computer Environment Device related to network (Purchase separately) Computer with a LAN Card HUB or network cable(Cross·Direct cable) Computer web browser specification Internet Explorer 7.0 or later version * You can use Internet Explorer 6.0 but it is not recommended.
Page 17
Setting the Computer Environment (Continued) Computer Settings for BACnet Gateway Connection All settings of BACnet Gateway will be arranged in web page which built in BACnet Gateway. You should access to BACnet Gateway IP to use BACnet Gateway web page. Set your computer settings as follows.
Setting the BACnet Gateway BACnet Gateway Connection and Login Address bar Click internet explorer icon( ) twice on your computer. When internet explorer window appears, enter IP address (http://192.168.0.100) on the address bar then press [ENTER]. If it is the first time to access BACnet Gateway, “ Install Microsoft Silverlight”...
Page 19
Setting the BACnet Gateway (Continued) Click [Run] button and continue installation. After installation, access to BACnet Gateway again. Silverlight operates normally with Windows XP SP2 or later version. It may not operate normally with previous version of Windows. NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 18 2013-04-25 오전...
Page 20
Enter ID and password when BACnet Gateway main web page appears, Then click [LOGIN]. If you use accounts with general authorization level to login, you cannot use the BACnet Gateway settings. Depending on authorization level set by the administrator, access to some functions may be restricted.
Page 21
Setting the BACnet Gateway (Continued) If you login successfully, 'Control and Monitoring' screen will appear. Click [System Setting]➔[BACnet configuration] menu to switch to BACnet Gateway. If you use accounts with authorization level lower than management group or accounts with general authorization level, BACnet configuration will not be displayed on the menu.
Page 22
If you access BACnet Gateway, 'Device Configuration' screen will appear initially. If you click [DMS2 Connect] button, screen will be switched to initial screen. NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 21 2013-04-25 오전 10:14:37...
Reading EHP Watt-hour Meter Setting and checking watt-hour meter Click [System and Checking Watt-hour meter]. You can change settings on watt-hour meter only when SIM/PIM interface module is connected. Click [Edit] from the 'Setting and checking Watt-hour meter' screen. ...
Page 24
Monthly baseline setting Click [System and Checking Watt-hour meter]. Click [Edit] from the ‘Monthly baseline setting’ screen. You can make changes when list box enables. Set the Monthly baseline setting. You can select from 1~31. If you select the last day of the month, it will automatically set the last day of corresponding month as baseline.
Page 25
Reading EHP Watt-hour Meter (Continued) Period setting Click [System and Checking Watt-hour meter]. Click [Edit] from the ‘Period setting’ screen. You can select checkbox to set period in daily or monthly unit. If you select daily period setting, text box will be enabled and you can enter the period in daily unit.
Page 26
Channel setting by indoor unit Click [Channel setting by indoor unit]. Click [Edit] from the ‘Channel setting by indoor unit’ screen. Check the address and the channel information of the SIM/PIM interface module which is connected to the watt-hour meter. ...
Page 27
Reading EHP Watt-hour Meter (Continued) Check the SIM/PIM interface module channel (Watt-hour meter) information of indoor/outdoor unit. You can set the channel when SIM/PIM interface module is installed in BACnet Gateway. When the indoor unit’s power is supplied from outdoor unit, set the ‘Outdoor unit SIM/PIM channel’...
System Setting Initialization Press [Menu], [], [] or [Set] from the screen where IP and current time is displayed. Main menu screen appears. Initialization is not possible in the screen where time information is displayed. 192.168.0.100 06:12:13(AM) Press [Menu] [] [] [] buttons in order from the main menu screen.
System Settings You can set and check information about BACnet Gateway installation and operation. BACnet Gateway network information Click [System Settings]. Click [Edit] from the ‘BACnet network information’ section. When text boxes of IP, Subnet mask, Default gateway, Network No. and DNS server are enabled.
Page 30
When the pop-up window appears, click [OK]. If you click [OK], current internet explorer will be closed. Then you may run the web browser again and access to BACnet Gateway by entering the IP set and saved manually. Note Factory setting is as follows. 1.
Page 31
System Settings (Continued) System time Click [System Settings]. Click [Edit] from the 'System time' section. Enter system time when text boxes enables. You can only enter numbers. Year: You can enter from 1980 to 2035. Month: You can enter from 1 to 12. ...
Selecting the language Click [System Settings]. Click [Edit] from the 'Select language' section. Select a language you want and click [Save]. When the pop-up window appears, click [OK]. BACnet Gateway will restart and the system will be changed to selected language. NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 31 2013-04-25 오전...
Page 33
System Settings (Continued) BACnet Gateway Name Setting Click [System Settings]. Click [Edit] from BACnet Gateway name setting window. Enter name of BACnet Gateway when BACnet Gateway name field enabled. You can use maximum 30 letters including English alphabets and special symbols. ...
Page 34
Click [OK] when “This information will be modified. Do you want to proceed?” message window appears. “Reading data from BACnet Gateway. Please wait. ” message appears and saving is completed. Afterwards, system environment setting screen appears again as all items are disabled. ...
Page 35
System Settings (Continued) Error Mail Forwarding Setting Click [System Settings]. Click [Edit] from error mail forwarding setting. Set all the items as the value you want when all items fields are enabled. If you select ‘Apply’ , you should enter e-mail address, SMTP server ID, password, and SMTP server address.
Page 36
Click [OK] when “This information will be modified. Do you want to proceed?” message window appears. “Reading data from DMS2. Please wait. ” message appears and saving is completed. Afterwards, system environment setting screen appears again with all items are disabled. Note In factory setting, ‘Not apply’...
Page 37
System Settings (Continued) Setting Public IP of upper controller Click [System Settings]. Click [Edit] when Public IP of upper controller screen appears. Enter the public IP of upper controller and select either ‘Apply’ or ‘Not apply’ . Click [Save]. When the setting is done, you may access BACnet Gateway from upper controllers (S-NET3, S-NET mini).
Page 38
Selecting the contact point control pattern Click [System Settings]. Click [Edit] from the 'Select the contact point control pattern' section. Select the pattern you want to check when checkboxes enables. Pattern 1[No external input]: No operation will be made when inputting contact point control signal.
Page 39
System Settings (Continued) When the pop-up window appears, click [OK]. When message with “Reading data from DMS. Please wait” appears saving is completed. Then, 'System Settings' screen appears again with all items disabled. Note Contact point control pattern is set to pattern 1 as factory default. For extension purpose, BACnet Gateway has total of 10 DI/DO ports.
Page 40
Contact point control pattern Pattern Control ▶ No external input (Factory default setting) Pattern1 When you input contact control signal in port 1, there will be no response. ▶ Level input (Emergency stop) 1. If the contact control signal is changed to ON, emergency stop status and all the indoor units are given ‘Stop’...
Page 41
System Settings (Continued) DI(Digital Input) Circuitry according to Control Switch Pattern Pattern 2 (May be used for connection with a fire sensor) BACnet Gateway Emergency Stop/Resume Operation No Connection Pattern 3 (External contact signal control) BACnet Gateway Operation/Stop A/C Enable/Disable remote control Pattern 4 (Pulse signal control) ...
Page 42
BACnet gateway information Click [System Settings]. You can check the basic BACnet gateway information from 'BACnet gateway information' section. Click [Edit] from the ‘BACnet gateway information’ section. If you want to initialize ‘Recipient_list’ , Check and click [Save]. When the pop-up window appears, click [OK]. BACnet Gateway will restart and the system will initialize ‘Recipient_list’...
Tracking What is tracking? Tracking is an operation that finds devices connected to BACnet Gateway. Through tracking operation, devices will be recognize if they are connected to BACnet Gateway. To supervise and control system air conditioner using BACnet Gateway, tracking should be done first.
Page 44
Setting communication mode for each channel Click [Device Configuration]. Click [Edit] from the 'Communication mode by channel' screen. [Edit] button will be switched to [Cancel]. All selection buttons will be enabled. However, the channels with searched device maintain its button in disabled status. NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 43 2013-04-25 오전...
Page 45
Tracking (Continued) When each channel is enabled, check the communication mode you want to set for each channel. You cannot change the communication mode of channel which has currently connected device. When ‘NEW’ is set as communication mode, setting will allow tracking, monitoring and controlling devices that support NEW communication mode.
Page 47
Tracking (Continued) Enter administrator’s password. Click [OK]. Tracking information window pops up. Check it and click [OK] to continue. Execute tracking depending on the communication mode set by communication mode setting for each channel. Tracking will be executed only to the channels, which communication mode is ...
Page 48
Message will appear to alert that tracking is completed. Select the zone initializing mode and click [OK]. No initialization: No zone information initialization will be made. Individual initialization: Initialize zone information as individual mode. Group initialization: Initialize zone information as group mode. Page will be refreshed by clicking [OK].
Device Configuration Disconnect all devices Function Initialize searched device status in BACnet Gateway. Monitoring and controlling of all the connected devices to BACnet Gateway will be stopped when you use this function. ◆ Connect searched device to the other channel and execute tracking. If the other device is searched in the channel you want to use, use ‘Disconnect all devices’function.
Page 50
When the information window pops up, you must check the information and click [OK] to continue. When message with “Reading data from DMS. Please wait” appears and all the devices are disconnected, page will be refreshed. Note After executing 'Disconnect all device function' , device search status of BACnet Gateway will be initialized.
Page 51
Device Configuration (Continued) Renaming the devices From the list of devices searched by tracking, click [Edit] in the bottom of the list. [Edit] will be changed to [Cancel]. Note If you click [Cancel] button, [Cancel] button will be switched to [Edit] button and the changed name of devices will be restored to original name.
Page 52
Enter the name of the devices when the text box enables. You cannot use special characters within the device name. The device name should be within 16 letters. Click [Save] after setting is completed. If you click [Cancel], text boxes will be disabled and the [Cancel] button will be switched to [Edit].
Page 53
Device Configuration (Continued) Checking device information Click one of the Object ID from 'Object ID' column. Detail information of the selected device will be displayed in device information. NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 52 2013-04-25 오전 10:14:41...
Page 54
Analog data of the selected device will be displayed in Analog data. Object ID: Displays ID of the corresponding object. Type: Displays type of the corresponding object. - AI: Input (Read Only) - AO: Output (Read/Write) - AV: Value (Read/Write) ...
Page 55
Device Configuration (Continued) Binary data of the selected device will be displayed in Binary data. Object ID: Displays ID of the corresponding object. Type: Displays type of the corresponding object. - BI: Input (Read Only) - BO: Output (Read/Write) - BV: Value (Read/Write) ...
Page 56
Multi-state Data of the selected device will be displayed in Multi-state data. Object ID: Displays ID of the corresponding object. Type: Displays type of the corresponding object. - MI: Input (Read Only) - MO: Output (Read/Write) - MV: Value (Read/Write) ...
Page 60
If this product is a communication gateway, describe the types of non-BACnet equipment/ networks(s) that the gateway supports: This gateway switches SAMSUNG air conditioner protocol to BACnet protocol to make RS-485 communication possible with the air conditioners connected to gateway.
Standard Object Types Supported Object Type Support Description [Indoor temperature], [The power value after the basic date], [The number of hours usage of an indoor unit after the basic date], [Power value within period], [The number of hours usage of an indoor unit within period], [Indoor unit error code], [AHU error code], [ERV error code], [EHS error code], Analog Input ...
Detail Description of Object Device Following table shows regulation of device ID and they are created automatically. DNET – Range CPP – Range INDOOR – Range Item [Digit 2] [Digit 3] [Digit 2] Centralized 1~40 000~015 Controller 1~40 100~115 DMS DI/DO 1~40 300~315 400~655...
BACnet Point List Indoor Unit Single indoor unit has following point list. Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Text-5 Indoor Temperature AC_RoomTemp_xx_xxxxxx °C Set temperature AV AC_Temp_Set_xx_xxxxxx °C Setting lower temperature limit AV AC_Cool_LimitTemp_xx_xxxxxx °C Setting upper temperature limit...
Page 64
AHU Kit Single AHU unit has following point list. Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Text-5 Indoor Temperature AHU_RoomTemp_xx_xxxxxx °C Set temperature AHU_Temp_Set_xx_xxxxxx °C Setting lower temperature AHU_Cool_LimitTemp_xx_ °C limit xxxxxx Setting upper temperature AHU_Heat_LimitTemp_xx_...
Page 65
BACnet Point List (Continued) Single EHS Unit has following point list. Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Room temperature EHS_RoomTemp_xx_xxxxxx °C Use when displayed temperature type Set temperature EHS_Temp_Set_xx_xxxxxx °C is set to 'Room' .
Single ERV unit has following point list. Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Text-5 Power On/Off operation ERV_Power_xx_xxxxxx Filter sign status ERV_FilterSign_xx_xxxxxx False True Filter sign reset ERV_FilterSign_Reset_xx_xxxxxx False True MV ERV_Operation_Mode_xx_ Operation mode status Auto HeatEx Bypass Sleep...
Page 67
BACnet Point List (Continued) BACnet Gateway BACnet Gateway has following point list. Instance Control and Object Object Name Status Value Number Monitoring Type All device OFF ALL_OFF_xx Inactive : All devices Off 0: Normal, 8: Emergency stop, 105 : Tracking in progress, DMS2 Status DMS2_Status_xx 108 : Tracking failed...
Other Information Object setting when there is communication error If any communication error occurs between the air conditioner devices, the property will be set as below. 1. Reliability property will be set as COMMUNICATION_FAILURE. 2. Fault / Alarm flag of Status_Flags property will be set as TRUE. 3.